8T

Horizontal Mount

(612 & 1250 models only)

Using the measurements from the diagram, install two user-sup-

plied ¼" (6 mm) fasteners into a rigid horizontal surface, leaving
the heads slightly raised. 

Slide the UPS System back over the

fasteners to engage the mounting slots molded on the bottom of the
UPS System cabinet. 

Install and tighten two user-supplied ¼"

(6 mm) fasteners into the mounting feet molded on the front of
the UPS System cabinet.

Horizontal Mount

(1012 and 2012 models only)

Using the measurements from the diagram, install two user-sup-

plied ¼" (6 mm) fasteners into a rigid horizontal surface, leaving
the heads slightly raised. 

Slide the UPS System forward over

the fasteners to engage the mounting feet molded on the front of
the UPS System cabinet. Install and tighten additional user-sup-
plied ¼" (6 mm) fasteners into the mounting feet molded on the
rear and sides of the UPS System cabinet*. The rear feet extend
beyond the unit’s cabinet to provide for adequate ventilation
space behind the cooling fan(s); they should not be removed.

5.87 in.

(14.91 cm.)

1.64 in.

(4.15 cm.)

5.87 in.

(14.91 cm.)

5.57 in.

(14.16 cm.)

5.57 in.

(14.16 cm.)

9.59 in.

(24.35 cm.)

9.59 in.

(24.35 cm.)

6.75 in.

(17.1 cm)

7.87 in.

(20 cm)

6.75 in.

(17.1 cm)

4.5 in.

(11.4 cm)

A

C

B

M

A

B

M

A

B

C

A

B

Note: Cabinets may have different front panel features, but all mount as per the figure above, or via the Lateral Mounting
Bracket, illustrated at left.

* All models include front and rear mounting feet. Select 

models include side mounting feet.

Mounting

WARNING! Mount your UPS System BEFORE DC battery and AC power 
connection. Failure to follow these instructions may lead to personal injury
and/or damage to the UPS System and connected systems.

Tripp Lite manufactures a variety of UPS Systems with a variety of mounting options. Tripp Lite recommends permanent mounting of your UPS
System in any of the configurations illustrated below. User must supply mounting hardware and is responsible for determining if the hard-
ware and mounting surface are suitable to support the weight of the UPS System. Contact Tripp Lite if you require further assistance in
mounting your UPS System.

Содержание TMU Series

Страница 1: ...abinets Premium Protection for Critical Equipment Built in ISOBAR power conditioning spike surge low voltage high voltage and lightning protection Rapid recharge high amp 3 stage battery charger Rapid automatic transfer switching from line power to inverter power Automatic overload protection Relay for low battery alarm flashing red mode traffic signals Cost Effective Features for All Budgets Powe...

Страница 2: ...ranty to register the warranty of your new Tripp Lite product You ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product No purchase necessary Void where prohibited Some restrictions apply See website for details Service Maintenance Service Before returning your UPS System for service follow these steps 1 Review the installation and operation instructions to ensur...

Страница 3: ...application in a dead air compartment Ideally any compartment would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC input terminals Do not short or bridge these terminals together Serious personal injury or property damage could result Equipment Connection War...

Страница 4: ... prolongs equipment service life Hardwire AC Input Output Cover Plate Battery Temperature Sensing Connector not on TMU612 models prolongs battery life by adjusting charge based on bat tery temperature Use with included cable See Configuration section for details Low Battery Relay not on TMU612 models when battery reaches low voltage this relay can signal traffic controller to go to flashing red mo...

Страница 5: ...upport The light will BLINK to alert you when the inverter shuts down due to a severe overload or over heating If this happens turn the operating mode switch OFF remove the overload and let the unit cool You may then turn the operating mode switch to AUTO REMOTE after it has adequate ly cooled This light will be off when AC power is supplying the load BATT VOLT CHRG CURR LEDs If the switch is in t...

Страница 6: ...el of your unit see dia gram as follows A1 A2 Most of your connected equipment will perform adequately when your UPS System s High AC Input Voltage Point DIP Switch 2 of Group A is set to 135V and its Low AC Voltage Input Point DIP Switches 3 and 4 of Group A or DIP Switch 3 for 612 models are set to 95V However if the unit frequently switches to battery power due to momentary high low line voltag...

Страница 7: ... any load size Configuration continued B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 Connect Battery Temperature Sensing Cable 1012 and 2012 models only The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature Connect the sensor cable the cable included with select models has an RJ style connector on one e...

Страница 8: ...equate ventilation space behind the cooling fan s they should not be removed 5 87 in 14 91 cm 1 64 in 4 15 cm 5 87 in 14 91 cm 5 57 in 14 16 cm 5 57 in 14 16 cm 9 59 in 24 35 cm 9 59 in 24 35 cm 6 75 in 17 1 cm 7 87 in 20 cm 6 75 in 17 1 cm 4 5 in 11 4 cm A C B M A B M A B C A B Note Cabinets may have different front panel features but all mount as per the figure above or via the Lateral Mounting ...

Страница 9: ...ow traffic managers to feel comfortable with fewer battery amp hours and shorter back up times thereby minimizing budgetary outlays for batteries auxilliary cabinets and battery maintenance STEP 1 Determine Total Wattage Required Add the wattage ratings of all equipment you will connect to your UPS System Wattage ratings are usually listed in equipment manuals or on nameplates If your equipment is...

Страница 10: ...fuse s and fuse block s within 18 inches of the battery The fuse s rating must equal or exceed the Minimum DC Fuse Rating listed in your UPS System s specifications See Specifications for fuse and fuse block rec ommendations See diagrams below for proper fuse placement Battery Connection Connect your UPS System to your batteries using the following procedures WARNING Failure to properly ground you...

Страница 11: ...e UPS System s AC input cord into an outlet providing 120V AC 60Hz power Make sure that the circuit you connect your UPS System to has adequate overload protection such as a circuit breaker or a fuse Plug your equipment into the UPS System s AC receptacles Any equipment you connect to it will benefit from your UPS System s built in ISOBAR power conditioning including surge spike and lightning prot...

Страница 12: ...ltage Check external are slowly flashing second flashes with prevent battery damage battery connections and fuse Unit automatically resets when Operating Mode Switch in the condition is cleared AUTO REMOTE position All Three BATT VOLT CHRG CURR LEDs Battery is overcharged Unit will shut down to prevent battery Disconnect any auxiliary chargers Reset by moving Operating Mode are rapidly flashing se...

Отзывы: