12T

Troubleshooting

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output (All Indicator Lights are OFF)

Unit is not properly connected to utility power

Connect unit to utility power.

Operating Mode Switch is set to “OFF” and AC 

Set Operating Mode Switch to “AUTO/REMOTE”.

input is present.
Operating Mode Switch is inadvertently set to  

Set Operating Mode Switch to “AUTO/REMOTE”

“CHARGE ONLY” and AC input is absent.
Circuit breaker is tripped.

Reset circuit breaker.

Unit has shut down due to battery overcharge (preventing 

Disconnect any auxiliary chargers. Reset by moving Operating Mode 

battery damage). The problem may be with connected 

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE”. If 

auxiliary chargers, if any, or with the unit’s charger.

unit remains in shutdown mode  after several attempts to reset, 
contact Tripp Lite Customer Service for assistance.

Unit has shut down due to excessive battery discharge.

Use an auxiliary charger* to raise battery voltage. Check external 
battery connections and fuse. Unit automatically resets when 
condition is cleared.

Connected batteries are dead.

Check and replace old batteries.

Unit has shut down due to overload.

Reduce load. Reset by moving Operating Mode Switch to “OFF”.
Wait 1 minute. Switch to “AUTO/REMOTE”.

Battery Not Recharging (AC Input Present)

Connected batteries are dead.

Check and replace old batteries.

Battery fuse* is blown.

Check and replace fuse.*

Battery cabling* is loose.

Check and tighten or replace cabling.*

Unit has shut down due to battery overcharge (preventing 

Disconnect any auxiliary chargers. Reset by moving Operating Mode 

battery damage). The problem may be with connected 

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE”. If

auxiliary chargers, if any, or with the unit’s charger.

unit remains in shutdown mode after several attempts to reset, 
contact Tripp Lite Customer Service for assistance.

Charger Enable/Inhibit Switch inadvertently set to “INHIBIT.”

Set Charger Enable/Inhibit Switch to “ENABLE”

Input circuit breaker is tripped.

Reset circuit breaker.

All Three “BATT VOLT/CHRG CURR” LEDs 

Battery is excessively discharged. Unit will shut down to

Use an auxiliary charger* to raise battery voltage. Check external

are slowly flashing (½ second flashes) with

prevent battery damage.

battery connections and fuse. Unit automatically resets when

Operating Mode Switch in the

condition is cleared.

“AUTO/REMOTE” position.
All Three “BATT VOLT/CHRG CURR” LEDs 

Battery is overcharged. Unit will shut down to prevent battery  Disconnect any auxiliary chargers. Reset by moving Operating Mode

are rapidly flashing (¼ second flashes)

damage. The problem may be with connected auxiliary  

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE.” If 

with Operating Mode Switch in the

chargers, if any, or with the unit’s charger.

unit remains in shutdown mode after several attempts

“AUTO/REMOTE” position.

to reset, contact Tripp Lite Customer Service for assistance.

Red “LOW” Battery Indicator Light is 

Battery voltage is low. Unit has shut down to protect battery

If AC power (utility- or generator-supplied) is present, the unit will

flashing with Operating Mode Switch in the 

from damage.

automatically reset itself and start recharging connected batteries.

“AUTO/REMOTE” position.

However, if an external charger is used to recharge the batteries, 
you will need to manually reset the unit by moving the Operating 
Mode Switch to “OFF” for two seconds then returning it to 
“AUTO/REMOTE”.

False reading due to undersized or insufficiently connected 

Use sufficient size DC cable sufficiently connected to UPS System.

DC cabling.

Red “LOAD” Operation Indicator Light 

Inverter is overloaded. Unit will automatically shut down after  Reduce load. Reset by moving Operating Mode Switch to “OFF”.

flashing

5 seconds.

Wait 1 minute. Switch to “AUTO/REMOTE”.

* User-supplied.

Try these remedies for common UPS System problems before calling for assistance. Call Tripp Lite Customer Service at (773) 869-1234
before returning your unit for service.

200409045  93-2400

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on
the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number.
The series number should not be confused with the marking name or model number of the product.

This product designed and engineered in the USA.

Содержание TMU Series

Страница 1: ...abinets Premium Protection for Critical Equipment Built in ISOBAR power conditioning spike surge low voltage high voltage and lightning protection Rapid recharge high amp 3 stage battery charger Rapid automatic transfer switching from line power to inverter power Automatic overload protection Relay for low battery alarm flashing red mode traffic signals Cost Effective Features for All Budgets Powe...

Страница 2: ...ranty to register the warranty of your new Tripp Lite product You ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product No purchase necessary Void where prohibited Some restrictions apply See website for details Service Maintenance Service Before returning your UPS System for service follow these steps 1 Review the installation and operation instructions to ensur...

Страница 3: ...application in a dead air compartment Ideally any compartment would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC input terminals Do not short or bridge these terminals together Serious personal injury or property damage could result Equipment Connection War...

Страница 4: ... prolongs equipment service life Hardwire AC Input Output Cover Plate Battery Temperature Sensing Connector not on TMU612 models prolongs battery life by adjusting charge based on bat tery temperature Use with included cable See Configuration section for details Low Battery Relay not on TMU612 models when battery reaches low voltage this relay can signal traffic controller to go to flashing red mo...

Страница 5: ...upport The light will BLINK to alert you when the inverter shuts down due to a severe overload or over heating If this happens turn the operating mode switch OFF remove the overload and let the unit cool You may then turn the operating mode switch to AUTO REMOTE after it has adequate ly cooled This light will be off when AC power is supplying the load BATT VOLT CHRG CURR LEDs If the switch is in t...

Страница 6: ...el of your unit see dia gram as follows A1 A2 Most of your connected equipment will perform adequately when your UPS System s High AC Input Voltage Point DIP Switch 2 of Group A is set to 135V and its Low AC Voltage Input Point DIP Switches 3 and 4 of Group A or DIP Switch 3 for 612 models are set to 95V However if the unit frequently switches to battery power due to momentary high low line voltag...

Страница 7: ... any load size Configuration continued B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 Connect Battery Temperature Sensing Cable 1012 and 2012 models only The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature Connect the sensor cable the cable included with select models has an RJ style connector on one e...

Страница 8: ...equate ventilation space behind the cooling fan s they should not be removed 5 87 in 14 91 cm 1 64 in 4 15 cm 5 87 in 14 91 cm 5 57 in 14 16 cm 5 57 in 14 16 cm 9 59 in 24 35 cm 9 59 in 24 35 cm 6 75 in 17 1 cm 7 87 in 20 cm 6 75 in 17 1 cm 4 5 in 11 4 cm A C B M A B M A B C A B Note Cabinets may have different front panel features but all mount as per the figure above or via the Lateral Mounting ...

Страница 9: ...ow traffic managers to feel comfortable with fewer battery amp hours and shorter back up times thereby minimizing budgetary outlays for batteries auxilliary cabinets and battery maintenance STEP 1 Determine Total Wattage Required Add the wattage ratings of all equipment you will connect to your UPS System Wattage ratings are usually listed in equipment manuals or on nameplates If your equipment is...

Страница 10: ...fuse s and fuse block s within 18 inches of the battery The fuse s rating must equal or exceed the Minimum DC Fuse Rating listed in your UPS System s specifications See Specifications for fuse and fuse block rec ommendations See diagrams below for proper fuse placement Battery Connection Connect your UPS System to your batteries using the following procedures WARNING Failure to properly ground you...

Страница 11: ...e UPS System s AC input cord into an outlet providing 120V AC 60Hz power Make sure that the circuit you connect your UPS System to has adequate overload protection such as a circuit breaker or a fuse Plug your equipment into the UPS System s AC receptacles Any equipment you connect to it will benefit from your UPS System s built in ISOBAR power conditioning including surge spike and lightning prot...

Страница 12: ...ltage Check external are slowly flashing second flashes with prevent battery damage battery connections and fuse Unit automatically resets when Operating Mode Switch in the condition is cleared AUTO REMOTE position All Three BATT VOLT CHRG CURR LEDs Battery is overcharged Unit will shut down to prevent battery Disconnect any auxiliary chargers Reset by moving Operating Mode are rapidly flashing se...

Отзывы: