23
Troubleshooting and Event Log
Fault/Alarm
LCD Header
Message
LCD Screen Message
LCD Event Log Display (Event
Type with Date/Time Stamp)
Fault Or
Alarm?
Additional Comments
Load/Temperature Related Errors/Faults:
Over Temperature Fault
Over Temp
Fault
Check UPS ventilation and fan.
If issue persists, contact
Tripp Lite.
mm/dd/yyyy OverTempFault
hh:mm
Note:
mm/dd/yyyy OverTemp SD
hh:mm is also logged when the unit
actually shuts down after being in fault
mode.
UPS fault At the time the over
temperature threshold is
reached, the OverTempFault
event will be triggered and
if AC is available, then
depending on the fault
mode setting, the unit will
either transfer to Bypass
mode or Standby mode. If
AC is unavailable, the unit
will transition to fault mode
with output turned off, then
shuts down.
Over Temperature
(warning only)
Over Temp
Check UPS ventilation and fan.
If issue persists, contact
Tripp Lite.
mm/dd/yyyy OverTempAlert hh:mm Warning
This is a warning threshold
only. The unit should not
take action based on this
event other than to display
and log the warning.
Overload Fault
Overload
Reduce connected load.
Restart UPS.
mm/dd/yyyy Overload hh:mm
(mm/dd/yyyy Overload SD hh:mm
is also logged when the unit
actually shuts down after being in
fault mode)
UPS fault At the time the overload
fault is triggered, the
Overload event will be
logged and if AC is available,
then depending on the fault
mode setting, the unit will
either transfer to Bypass
mode or Standby mode. If
AC is unavailable, the unit
will transition to fault mode
with output turned off, then
shuts down. UPS will not
intentionally shut down due
to overload in this mode
regardless how high the
load is.
Note:
The circuit breaker may
trip due to the overload.
Overload Warning
Overload
Alarm
Reduce connected load.
mm/dd/yyyy Overload ALM hh:mm
Warning
Overload warning is triggered
when the load level is
between 100% to 105%
or when load level reaches
the preconfigured overload
warning level.
Other Warnings and Events:
EPO Active
EPO Active
Check EPO switch. If issue
persists, contact Tripp Lite.
mm/dd/yyyy EPO SD hh:mm
Warning
Bypass Out of Range
Bypass
Range Error
Check AC input volt. and freq.
If issue persists, contact
Tripp Lite.
mm/dd/yyyy Bypass Err 1 hh:mm
Warning
AC input voltage might be
meeting the preconfigured
bypass range requirement,
see
Operations
section for
more information.
Bypass Frequency
Unstable
Bypass Freq.
Error
Check AC input freq. If issue
persists, contact Tripp Lite.
mm/dd/yyyy Bypass Err 2 hh:mm
Warning
On Battery
N/A
N/A
mm/dd/yyyy On Batt hh:mm
Note:
If the UPS shuts down in Battery
Mode based on preconfigured delay,
“On Battery” will be replaced with
“Timed SD”, and logged as another
event.
Normal
AC Failure
N/A
N/A
mm/dd/yyyy AC Failure hh:mm
Note:
If valid AC returns, “On Utility "
is logged as another event.
Normal