5. Electrical Installation
Notes:
• All electrical connections shall be performed by a qualified electrician and must comply with local codes and regulations.
• The In-Row Cooler supplies power to the condenser.
• The In-Row Cooler accepts both delta and wye connections.
Disconnect power at the source prior to making electrical connections.
Supply power to the In-Row Cooler according to its nameplate.
Cable size should meet the electrical requirements.
Table: In-Row Cooler Nameplate Power Information
Model
SRCOOLDXRW12:
In-Row Condenser
SRCOOLOXRW25:
In-Row Condenser
Voltage
208V
208V
Phase
3ph
3ph
Frequency
60 Hz
60 Hz
MCA (Minimum Current Ampacity)
19A
33A
MOP (Maximum Overcurrent Protection)
25A
50A
Model
SRCOOLDXRW12:
Condenser Only
SRCOOLOXRW25:
Condenser Only
Voltage
208V
208V
Phase
1ph
1ph
Frequency
60 Hz
60 Hz
Table: Motor Protection Information
Model
SRCOOLDXRW12
SRCOOLOXRW25
Main breaker
63A 3-poles
63A 3-poles
Compressor fuse
15A
15A
Compressor breaker
32A 3-poles
20A 3-poles
Indoor fan breaker
20A 2-poles
20A 2-poles
Outdoor fan fuse
—
S505-5-R (5A)
Outdoor fan breaker
20A 2-poles (location indoor unit)
20A 3-poles