Enclosure Installation
Leveling
WARNING: Level the enclosure before attempting to install equipment. The casters are not designed to provide long-term support for the enclosure. Use the
levelers to provide long-term support. Install the enclosure in a structurally sound area with a level floor that is able to bear the weight of the enclosure, all
equipment that will be installed in the enclosure and any other enclosures and/or equipment that will be installed nearby.
1
After the enclosure has been moved to the installation location, use a carpenter's level to check the slope of
the floor. If the floor slopes more than 1%, choose an alternate installation site.
2
Use an 18 mm open-end wrench to lower each leveler
A
until it reaches the floor. (There are 4 levelers,
2 at the front and 2 at the rear.) Make sure each leveler contacts the floor solidly. Note: Lower a leveler by
turning it clockwise; raise a leveler by turning it counter-clockwise.
3
After lowering each leveler, use the carpenter's level to confirm that the enclosure is level in all directions.
Adjust the levelers as required until the enclosure is level.
4
(Optional) If you wish to provide an additional measure of stability, you can attach the 2 shipping brackets,
using the hardware that attached the enclosure to the shipping pallet. Use a 13 mm open-end wrench to
connect the brackets to the outer
A
or inner
B
bracket mounting points of the enclosure. Attach the
brackets to secure mounting points in the floor using user-supplied hardware or Tripp Lite's SmartRack
Bolt-Down Kit (Part # SR331).
Ground Connection
All the parts of the enclosure are grounded to the frame of the enclosure. Use the enclosure's front or rear
threaded grounding point
A
and an M6 screw (included) to connect the frame of the enclosure directly to your
facility's earth ground connection with an 8 AWG (3.264 mm) wire. Route the ground wire under the enclosure's
frame to ensure unhindered door operation. WARNING: Attach each enclosure to earth ground separately.
Do not use the enclosure without an earth ground connection.
EARTH
GROUND
FLOOR
1
2
3
A
B
4
A
A
201112001_L 93-2723.indd 6