Storage and Service

 Input Breakers 

 Prevents high input current from damaging the UPS or the attached load. If this breaker trips, make sure your UPS is 
connected to nominal 208V AC power before resetting the circuit breaker by pushing the breaker levers to reset.

 Output Breakers

 Your UPS features 3 breakers that protect your UPS from output overload. If one or more breakers trip, remove some of 
the load on the circuit(s) and allow the UPS to cool before resetting the circuit(s) by pressing the breaker switch(es).

Power Sensitivity Adjustment

 This dial is normally set fully counterclockwise, which enables the UPS to protect against waveform distortions in its AC 

input. When such distortion occurs, the UPS will normally switch to providing pure sine wave power from its battery 

reserves for as long as the distortion is present. In some such as in areas with poor utility power or where the UPS’s input 
power comes from a backup generator, chronic waveform distortion could cause the UPS to switch to battery too 

frequently, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to 
waveform distortion by experimenting with different settings for this dial. As the dial is turned clockwise, the UPS becomes 

more tolerant of variations in its input power’s AC waveform. 

Note: 

The further the dial is adjusted clockwise, the greater the degree of waveform distortion the UPS will allow to pass to connected 

equipment. 

When experimenting with different settings for this dial, operate connected equipment in a safe test mode so that the 
effect on the equipment of any waveform distortions in the UPS’s output can be evaluated without disrupting critical 

operations. 

Ground Screw

 Use this to connect any equipment that requires a chassis ground.

Storage

Before storing your UPS, place it in the OFF mode by reversing the Connection procedure: use the POWER button to place the UPS in 

STANDBY mode; unplug the UPS; set the double-pole input breaker to the "OFF" position; disconnect the external battery pack. If you store 
your UPS for an extended period of time, recharge the UPS batteries once every three months by following Steps 1, 2 and 3 in the 

Connection section and allowing the UPS to charge its batteries for 4-6 hours before placing it back in storage. If you leave your UPS 
batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.

Service

A variety of Extended Warranty and On-Site Service Programs are also available from Tripp Lite. For more information on service,  
visit www.tripplite.com/support. Before returning your product for service, follow these steps:
1.  Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading 

of the instructions.

2.  If the problem continues, do not contact or return the product to the dealer. Instead, visit www.tripplite.com/support.
3.  If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. From here you can request a 

Returned Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit's model and 
serial numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to 

you. Any damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized  
Tripp Lite service center is not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must 
have transportation charges prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period, 
enclose a copy of your sales receipt. Return the product for service using an insured carrier to the address given to you when you 
request the RMA.

Содержание SmartPro SMART5000RT3U

Страница 1: ...icker service and ultimate peace of mind You could also win an ISOBAR6ULTRA surge protector a 100 value www tripplite com warranty 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2016 Tripp Lite All rights reserved SmartPro is a registered trademark of Tripp Lite Important Safety Instructions 2 Mounting 3 Connection 4 Basic Operation 6 Storage and Service 8 Product Regi...

Страница 2: ...itrous oxide Do not connect surge suppressors or extension cords to the output of your UPS This might overload the UPS and will void the surge suppressor and UPS warranties Battery Warnings Batteries can present a risk of electrical shock and burn from high short circuit current Observe proper precautions Do not dispose of the batteries in a fire Do not open the UPS or batteries Do not short or br...

Страница 3: ...e mounting rails permanently using the included screws and cup washers C as shown Place 6 screws total at the front and 4 screws total at the back Tighten all screws before proceeding Warning Do not attempt to install your equipment until you have inserted and tightened the required screws The plastic pegs will not support the weight of your equipment 3 Attach your equipment s mounting brackets to...

Страница 4: ...ut breaker to the ON position towards the left side of the rear panel 3 Plug your UPS s line cord into an electrical outlet Once your UPS is plugged in the UPS will enter STANDBY mode The fan will activate and the LED will begin flashing The UPS system s outlets will not be active until the UPS is turned ON Your UPS features a 30 amp plug However a trained technician may replace this plug with a u...

Страница 5: ...O plug is disconnected Connection Optional 1 2 3 2 USB Port Connection Using the USB cable provided connect a USB port from a computer to a USB port on your UPS On the computer install the Tripp Lite power protection software appropriate to its operating system A second USB computer may be connected to the second USB port if desired 3 EPO Port Connection Using the RJ11 cable provided connect the E...

Страница 6: ... may test its batteries by pressing the MUTE TEST button for two seconds The UPS will switch to INVERT mode for several seconds Normally the INVERT alarm four short beeps will sound indicating that the system is working properly If the OVERLOAD alarm short rapid beeps sounds reduce the load on the UPS If the LOW BATTERY alarm a constant beep sounds your UPS s batteries may need replacing your exte...

Страница 7: ...onnect the UPS to a DB9 port on any workstation or server Use with Tripp Lite cabling and PowerAlert Software to monitor and manage network power and automatically save open files and shut down equipment during a blackout see Connection The DB9 port labeled SNMP Config is also used while configuring Tripp Lite SNMP Adapters Smart USB Ports Your UPS features 2 USB ports that may be used to connect ...

Страница 8: ...ce it in the OFF mode by reversing the Connection procedure use the POWER button to place the UPS in STANDBY mode unplug the UPS set the double pole input breaker to the OFF position disconnect the external battery pack If you store your UPS for an extended period of time recharge the UPS batteries once every three months by following Steps 1 2 and 3 in the Connection section and allowing the UPS ...

Страница 9: ...rdance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The user must use shielded cables and connectors with this equipment Any changes or modifications to this equipment not expressly app...

Страница 10: ...l Módulo de Baterías AGBP4860Y3U No conveniente para los usos móviles 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 2016 Tripp Lite Todos los derechos reservados SmartPro es una marca registrada de Tripp Lite Importantes Instrucciones 11 de Seguridad Montaje 12 Conexión 13 Operación Básica 15 Almacenaje y Servicio 18 English 1 Français 19 ...

Страница 11: ...nsiones o cables de extensión a la salida de su UPS Esto puede sobrecargar al UPS y anulará las garantías del supresor de sobretensiones y del UPS Advertencias Sobre las Baterías Debido a que las baterías presentan un peligro de choque eléctrico y quemaduras por las altas corrientes de cortocircuito tome las precauciones adecuadas No deseche las baterías en un incinerador No abra las baterías No p...

Страница 12: ...permanentemente los entrepaños B a los rieles de instalación usando los tornillos y las arandelas de copa C como se muestra Coloque 6 tornillos en total en el frente y 4 tornillos en total en la parte posterior Apriete todos los tornillos antes de continuar Advertencia No intente instalar su equipo hasta que haya insertado y apretado los tornillos requeridos Las espigas de plástico no soportarán e...

Страница 13: ...O hacia el lado izquierdo del panel trasero 3 Enchufe el cable del sistema UPS a una toma eléctrica Una vez conectado el sistema UPS éste se encuentra en modo STANDBY reserva Se activa el ventilador y el LED empieza a parpadear Las tomas del sistema UPS no se activarán hasta encender el sistema Este sistema UPS cuenta con una clavija para 30 amp Sin embargo un técnico debidamente capacitado puede ...

Страница 14: ... con un puerto USB Con ayuda del cable USB proporcionado conecte un puerto USB de una computadora a un puerto USB de su sistema UPS Instale en la computadora el software de protección de energía de Tripp Lite que corresponda al sistema operativo Si así lo desea es posible conectar otra computadora al segundo puerto USB computer may be connected to the second USB port if desired 3 Conexión con un p...

Страница 15: ...tema emite sonidos rápidos y breves para avisarle de la necesidad de reducir la carga La tercera alarma es la de Low Battery batería baja Cuando el sistema UPS está en modo INVERT y las baterías están casi agotadas emite un sonido constante para advertirle de la necesidad de apagar todo el equipo que está conectado Para silenciar las alarmas INVERT u OVERLOAD oprima el botón MUTE TEST silenciar ap...

Страница 16: ...era conexiones USB en su sistema UPS para reiniciar de manera remota el equipo conectado encienda y apague el sistema UPS con ayuda del software PowerAlert de Tripp Lite Para encender y apagar de manera remota e individual el equipo conectado a algunos contactos se usa el software del sistema UPS Tripp Lite sin necesidad de interrumpir el suministro de energía al resto del equipo conectado a los o...

Страница 17: ...o de onda presentes en la entrada de CA Cuando se producen dichas distorsiones el sistema UPS normalmente hace un cambio para entregar una alimentación sinusoidal pura mediante sus baterías y durante todo el tiempo que permanezca la distorsión En el caso de regiones en las cuales el suministro de energía es deficiente o en aquellos casos en los que el sistema UPS se alimenta con un generador de re...

Страница 18: ...servicio técnico En este sencillo formulario en línea se le solicitarán los números de serie y modelo de la unidad junto con otra información general del comprador El número RMA y las instrucciones para el envío se le enviarán por correo electrónico La presente garantía no cubre ningún daño directo indirecto especial o consecuencial del producto que ocurra durante el envío a Tripp Lite o a un cent...

Страница 19: ... module de batteries AGBP4860Y3U Non approprié aux applications mobiles 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Tripp Lite 2016 Tous droits réservés SmartPro est une marque déposée de Tripp Lite Importantes consignes 20 de sécurités Montage 21 Connexion 22 Exploration de base 24 Entreposage et entretien 27 English 1 Español 10 ...

Страница 20: ... de l oxygène ou de l oxyde nitreux Ne pas brancher de parasurtenseurs ou de rallonges électriques à la sortie de l onduleur Cela risquerait de surcharger l onduleur et annulerait la garantie du parasurtenseur et de l onduleur Mises en garde relatives à la batterie Parce que les batteries présentent un risque de choc électrique et de courant de court circuit élevé prenez les précautions nécessaire...

Страница 21: ... rebord du support de chaque étagère doit être tourné vers l intérieur 2 Retenir les étagères B aux rails de montage de façon permanente en utilisant les vis et les rondelles à collerette incluses C tel qu illustré Placer 6 vis au total à l avant et 4 vis au total à l arrière Serrer toutes les vis avant de continuer Avertissement n essayez pas d installer l équipement avant d avoir inséré et serré...

Страница 22: ... alimentation de votre système UPS dans une prise de secteur Dès que votre système UPS est branché ce dernier se met en mode STANDBY attente Le ventilateur démarre et les voyants se mettent à clignoter Les prises du système UPS ne seront pas actives avant que ce dernier ne soit mis sous tension ON Votre système UPS est doté d une prise de courant de 30 ampères Toutefois un technicien qualifié peut...

Страница 23: ...Connexion du port USB En utilisant le câble USB fourni reliez le port USB de l ordinateur à celui de votre système UPS Installez dans l ordinateur le logiciel de protection de l alimentation électrique Tripp Lite adapté à son système d exploitation Un deuxième ordinateur peut être connecté au deuxième port USB du système UPS si désiré 3 Connexion du port d arrêt d urgence EPO En utilisant le câble...

Страница 24: ...tale du matériel branché dépasse la capacité de sortie de l unité La troisième l alarme de batterie faible émet un signal sonore en continu quand le système UPS est en mode INVERT et que ses batteries sont presque épuisées pour vous prévenir qu il faut éteindre le matériel branché Pour amortir les alarmes INVERT ou OVERLOAD appuyez sur le bouton MUTE TEST L alarme de batterie faible ne s arrête qu...

Страница 25: ...ie ou USB à votre système UPS vous pouvez réinitialiser à distance le matériel branché en utilisant le logiciel PowerAlert de Tripp Lite pour allumer ou éteindre votre unité Vous pouvez même sélectionner à distance les prises à mettre hors tension et en marche individuellement en utilisant le logiciel de système UPS Tripp Lite sans couper le courant au matériel branché aux autres prises Le système...

Страница 26: ...illes d une montre pour protéger le système UPS contre la distorsion de l onde d entrée c a Quand une telle distorsion se produit le système UPS basculera normalement vers l alimentation de batterie pour fournir une onde sinusoïdale pure tant que la distorsion persiste Dans les régions où l alimentation électrique du secteur est de mauvaise qualité ou si l alimentation du système UPS provient d un...

Страница 27: ...tour du produit De cet endroit vous pouvez demander un numéro d autorisation de retour de matériel RMA qui est exigé pour une réparation Ce formulaire en ligne simple vous demandera le numéro de modèle et le numéro de série de votre unité ainsi que d autres renseignements généraux concernant l acheteur Le numéro RMA ainsi que les instructions concernant le transport vous seront acheminées par cour...

Страница 28: ...28 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 15 12 016 93 2159_rev C ...

Отзывы: