background image

6

Buttons (Front Panel)

Basic Operation

 

Use the 

POWER

 button to switch your UPS between its four modes of operation.

 OFF: 

No indicator lights are on. The UPS is completely shut down for storage or shipping. If the UPS is connected to AC 

power, it will start up in 

STANDB

Y mode. If the UPS is not connected to AC power and the 

POWER

 button is pressed for 

two seconds, the UPS will “cold start” into

 INVERT

 mode.

 STANDBY: 

The “ ” light is flashing. The UPS is receiving AC power and using it to charge its batteries, but its outlets are 

not active. Pressing the 

POWER

 button while the UPS is in 

STANDBY

 will put the UPS in the ON mode. Unplugging the 

UPS or cutting AC power while the UPS is in 

STANDBY

 will put the UPS in the 

OFF 

mode.

 ON:

 The “ ” light is on. The UPS is receiving AC power, charging its batteries and delivering power to connected 

equipment. If AC power is lost while the UPS is 

ON

 (i.e. a blackout occurs), the UPS will switch into 

INVERT

 mode. 

Pressing the 

POWER

 button while the UPS is 

ON 

will put the UPS in 

STANDBY

 mode. 

 INVERT:

 The “

” light is flashing. The UPS is powering connected equipment from battery backup. If AC power is 

restored, the UPS will switch to the 

ON

 mode. Pressing the 

POWER

 button while the UPS is in 

INVERT

 will put the UPS 

into the 

OFF

 mode. If the UPS is in 

INVERT

 and its batteries are drained, the UPS will switch to the 

OFF

 mode until AC 

power is restored, then switch to the 

ON

 mode.

 Use the 

MUTE/TEST

 button to do two things:

SILENCE ALARM:

 Your UPS has three alarms. The first, the 

INVERT

 alarm, emits four short beeps every ten seconds when 

the UPS is in 

INVERT

 mode, to warn you that AC power has failed. The second, the 

OVERLOAD

 alarm, emits short, rapid 

beeps when the UPS is in 

INVERT

 mode if the total power draw of connected equipment exceeds the UPS’s output 

capacity, to warn you to reduce the load. The third, the Low Battery alarm, emits a constant beep when the UPS is in 

INVERT

 mode and its batteries are very nearly depleted, to warn you that connected equipment must shut down. To silence 

the 

INVERT

 or 

OVERLOAD

 alarms, press the 

MUTE/TEST

 button. The 

LOW BATTERY

 alarm will only stop when the UPS 

switches to the 

OFF

 or 

ON

 mode. 

SELF-TEST:

 If your UPS is in the 

ON

 mode and has a load connected, you may test its batteries by pressing the 

MUTE/

TEST

 button for two seconds. The UPS will switch to 

INVERT

 mode for several seconds. Normally, the 

INVERT

 alarm (four 

short beeps) will sound, indicating that the system is working properly. If the 

OVERLOAD 

alarm (short, rapid beeps) sounds, 

reduce the load on the UPS. If the 

LOW BATTERY

 alarm (a constant beep) sounds, your UPS’s batteries may need 

replacing, your external battery connection may be loose or the batteries may simply be less than fully charged. Check the 

external battery connection, let the UPS charge for 12 hours, then perform a second self-test. If the 

LOW BATTERY

 alarm 

sounds again, contact Tripp Lite for service. Do not unplug your UPS to test its batteries, or you will remove safe electrical 

grounding and may introduce a damaging surge into your network connections.

Indicator Lights (Front Panel)

All Indicator Light descriptions apply when the UPS is plugged into a wall outlet and turned ON.

 POWER:

 Lights green when the UPS is receiving AC power. Illuminates constantly when the UPS is in the 

ON

 mode, 

indicating that batteries are charging and connected equipment is receiving filtered AC power. Flashes while in 

STANDBY 

mode to indicate that batteries are charging but connected equipment is not receiving power.

 

VOLTAGE CORRECTION:

 Lights green whenever your UPS is automatically correcting high or low AC line voltage. The UPS 

will also click gently. These are normal, automatic operations of your UPS, and no action is required on your part.

 BATTERY CHARGE: 

This multicolored light displays 7 separate UPS battery charge conditions. It will turn from red (low) to 

yellow (medium) to green (full) to show you the level of battery charge. If the light is constant, your UPS is in the 

ON

 or 

STANDBY

 mode, operating from line power, and the battery is charging. If the light is flashing, your UPS is in the 

INVERT 

mode, operating from battery, and the battery is discharging. If the light is flashing red, your UPS is in the 

INVERT

 mode 

and is nearly out of power: you should save files and shut down your equipment immediately.

 OUTPUT LOAD: 

This multicolored light shows how heavy your UPS’s load is. Steady green indicates a light load, steady 

yellow a medium load. When the light is red, your UPS is supporting a load above 85% of its capacity. If the red light begins 
flashing, then your UPS is severely overloaded. Immediately remove load from the UPS until the light stops flashing.

Содержание SmartPro SMART5000RT3U

Страница 1: ...icker service and ultimate peace of mind You could also win an ISOBAR6ULTRA surge protector a 100 value www tripplite com warranty 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2016 Tripp Lite All rights reserved SmartPro is a registered trademark of Tripp Lite Important Safety Instructions 2 Mounting 3 Connection 4 Basic Operation 6 Storage and Service 8 Product Regi...

Страница 2: ...itrous oxide Do not connect surge suppressors or extension cords to the output of your UPS This might overload the UPS and will void the surge suppressor and UPS warranties Battery Warnings Batteries can present a risk of electrical shock and burn from high short circuit current Observe proper precautions Do not dispose of the batteries in a fire Do not open the UPS or batteries Do not short or br...

Страница 3: ...e mounting rails permanently using the included screws and cup washers C as shown Place 6 screws total at the front and 4 screws total at the back Tighten all screws before proceeding Warning Do not attempt to install your equipment until you have inserted and tightened the required screws The plastic pegs will not support the weight of your equipment 3 Attach your equipment s mounting brackets to...

Страница 4: ...ut breaker to the ON position towards the left side of the rear panel 3 Plug your UPS s line cord into an electrical outlet Once your UPS is plugged in the UPS will enter STANDBY mode The fan will activate and the LED will begin flashing The UPS system s outlets will not be active until the UPS is turned ON Your UPS features a 30 amp plug However a trained technician may replace this plug with a u...

Страница 5: ...O plug is disconnected Connection Optional 1 2 3 2 USB Port Connection Using the USB cable provided connect a USB port from a computer to a USB port on your UPS On the computer install the Tripp Lite power protection software appropriate to its operating system A second USB computer may be connected to the second USB port if desired 3 EPO Port Connection Using the RJ11 cable provided connect the E...

Страница 6: ... may test its batteries by pressing the MUTE TEST button for two seconds The UPS will switch to INVERT mode for several seconds Normally the INVERT alarm four short beeps will sound indicating that the system is working properly If the OVERLOAD alarm short rapid beeps sounds reduce the load on the UPS If the LOW BATTERY alarm a constant beep sounds your UPS s batteries may need replacing your exte...

Страница 7: ...onnect the UPS to a DB9 port on any workstation or server Use with Tripp Lite cabling and PowerAlert Software to monitor and manage network power and automatically save open files and shut down equipment during a blackout see Connection The DB9 port labeled SNMP Config is also used while configuring Tripp Lite SNMP Adapters Smart USB Ports Your UPS features 2 USB ports that may be used to connect ...

Страница 8: ...ce it in the OFF mode by reversing the Connection procedure use the POWER button to place the UPS in STANDBY mode unplug the UPS set the double pole input breaker to the OFF position disconnect the external battery pack If you store your UPS for an extended period of time recharge the UPS batteries once every three months by following Steps 1 2 and 3 in the Connection section and allowing the UPS ...

Страница 9: ...rdance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The user must use shielded cables and connectors with this equipment Any changes or modifications to this equipment not expressly app...

Страница 10: ...l Módulo de Baterías AGBP4860Y3U No conveniente para los usos móviles 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 2016 Tripp Lite Todos los derechos reservados SmartPro es una marca registrada de Tripp Lite Importantes Instrucciones 11 de Seguridad Montaje 12 Conexión 13 Operación Básica 15 Almacenaje y Servicio 18 English 1 Français 19 ...

Страница 11: ...nsiones o cables de extensión a la salida de su UPS Esto puede sobrecargar al UPS y anulará las garantías del supresor de sobretensiones y del UPS Advertencias Sobre las Baterías Debido a que las baterías presentan un peligro de choque eléctrico y quemaduras por las altas corrientes de cortocircuito tome las precauciones adecuadas No deseche las baterías en un incinerador No abra las baterías No p...

Страница 12: ...permanentemente los entrepaños B a los rieles de instalación usando los tornillos y las arandelas de copa C como se muestra Coloque 6 tornillos en total en el frente y 4 tornillos en total en la parte posterior Apriete todos los tornillos antes de continuar Advertencia No intente instalar su equipo hasta que haya insertado y apretado los tornillos requeridos Las espigas de plástico no soportarán e...

Страница 13: ...O hacia el lado izquierdo del panel trasero 3 Enchufe el cable del sistema UPS a una toma eléctrica Una vez conectado el sistema UPS éste se encuentra en modo STANDBY reserva Se activa el ventilador y el LED empieza a parpadear Las tomas del sistema UPS no se activarán hasta encender el sistema Este sistema UPS cuenta con una clavija para 30 amp Sin embargo un técnico debidamente capacitado puede ...

Страница 14: ... con un puerto USB Con ayuda del cable USB proporcionado conecte un puerto USB de una computadora a un puerto USB de su sistema UPS Instale en la computadora el software de protección de energía de Tripp Lite que corresponda al sistema operativo Si así lo desea es posible conectar otra computadora al segundo puerto USB computer may be connected to the second USB port if desired 3 Conexión con un p...

Страница 15: ...tema emite sonidos rápidos y breves para avisarle de la necesidad de reducir la carga La tercera alarma es la de Low Battery batería baja Cuando el sistema UPS está en modo INVERT y las baterías están casi agotadas emite un sonido constante para advertirle de la necesidad de apagar todo el equipo que está conectado Para silenciar las alarmas INVERT u OVERLOAD oprima el botón MUTE TEST silenciar ap...

Страница 16: ...era conexiones USB en su sistema UPS para reiniciar de manera remota el equipo conectado encienda y apague el sistema UPS con ayuda del software PowerAlert de Tripp Lite Para encender y apagar de manera remota e individual el equipo conectado a algunos contactos se usa el software del sistema UPS Tripp Lite sin necesidad de interrumpir el suministro de energía al resto del equipo conectado a los o...

Страница 17: ...o de onda presentes en la entrada de CA Cuando se producen dichas distorsiones el sistema UPS normalmente hace un cambio para entregar una alimentación sinusoidal pura mediante sus baterías y durante todo el tiempo que permanezca la distorsión En el caso de regiones en las cuales el suministro de energía es deficiente o en aquellos casos en los que el sistema UPS se alimenta con un generador de re...

Страница 18: ...servicio técnico En este sencillo formulario en línea se le solicitarán los números de serie y modelo de la unidad junto con otra información general del comprador El número RMA y las instrucciones para el envío se le enviarán por correo electrónico La presente garantía no cubre ningún daño directo indirecto especial o consecuencial del producto que ocurra durante el envío a Tripp Lite o a un cent...

Страница 19: ... module de batteries AGBP4860Y3U Non approprié aux applications mobiles 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Tripp Lite 2016 Tous droits réservés SmartPro est une marque déposée de Tripp Lite Importantes consignes 20 de sécurités Montage 21 Connexion 22 Exploration de base 24 Entreposage et entretien 27 English 1 Español 10 ...

Страница 20: ... de l oxygène ou de l oxyde nitreux Ne pas brancher de parasurtenseurs ou de rallonges électriques à la sortie de l onduleur Cela risquerait de surcharger l onduleur et annulerait la garantie du parasurtenseur et de l onduleur Mises en garde relatives à la batterie Parce que les batteries présentent un risque de choc électrique et de courant de court circuit élevé prenez les précautions nécessaire...

Страница 21: ... rebord du support de chaque étagère doit être tourné vers l intérieur 2 Retenir les étagères B aux rails de montage de façon permanente en utilisant les vis et les rondelles à collerette incluses C tel qu illustré Placer 6 vis au total à l avant et 4 vis au total à l arrière Serrer toutes les vis avant de continuer Avertissement n essayez pas d installer l équipement avant d avoir inséré et serré...

Страница 22: ... alimentation de votre système UPS dans une prise de secteur Dès que votre système UPS est branché ce dernier se met en mode STANDBY attente Le ventilateur démarre et les voyants se mettent à clignoter Les prises du système UPS ne seront pas actives avant que ce dernier ne soit mis sous tension ON Votre système UPS est doté d une prise de courant de 30 ampères Toutefois un technicien qualifié peut...

Страница 23: ...Connexion du port USB En utilisant le câble USB fourni reliez le port USB de l ordinateur à celui de votre système UPS Installez dans l ordinateur le logiciel de protection de l alimentation électrique Tripp Lite adapté à son système d exploitation Un deuxième ordinateur peut être connecté au deuxième port USB du système UPS si désiré 3 Connexion du port d arrêt d urgence EPO En utilisant le câble...

Страница 24: ...tale du matériel branché dépasse la capacité de sortie de l unité La troisième l alarme de batterie faible émet un signal sonore en continu quand le système UPS est en mode INVERT et que ses batteries sont presque épuisées pour vous prévenir qu il faut éteindre le matériel branché Pour amortir les alarmes INVERT ou OVERLOAD appuyez sur le bouton MUTE TEST L alarme de batterie faible ne s arrête qu...

Страница 25: ...ie ou USB à votre système UPS vous pouvez réinitialiser à distance le matériel branché en utilisant le logiciel PowerAlert de Tripp Lite pour allumer ou éteindre votre unité Vous pouvez même sélectionner à distance les prises à mettre hors tension et en marche individuellement en utilisant le logiciel de système UPS Tripp Lite sans couper le courant au matériel branché aux autres prises Le système...

Страница 26: ...illes d une montre pour protéger le système UPS contre la distorsion de l onde d entrée c a Quand une telle distorsion se produit le système UPS basculera normalement vers l alimentation de batterie pour fournir une onde sinusoïdale pure tant que la distorsion persiste Dans les régions où l alimentation électrique du secteur est de mauvaise qualité ou si l alimentation du système UPS provient d un...

Страница 27: ...tour du produit De cet endroit vous pouvez demander un numéro d autorisation de retour de matériel RMA qui est exigé pour une réparation Ce formulaire en ligne simple vous demandera le numéro de modèle et le numéro de série de votre unité ainsi que d autres renseignements généraux concernant l acheteur Le numéro RMA ainsi que les instructions concernant le transport vous seront acheminées par cour...

Страница 28: ...28 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 15 12 016 93 2159_rev C ...

Отзывы: