OUTPUT

Output Volt Amp
Capacity (VA)

2200

Output kVA capacity
(kVA)

2.2

Output Watt Capacity
(watts)

1920

Output kW capacity

1.92

Output power factor

0.87

Output Capacity
Details

Output derates to 1600 watts in all external battery pack configurations

Nominal Output
Voltage(s) Supported

120V

Frequency
compatibility

60 Hz

Output voltage
regulation (line mode)

-14%, +6%

Output voltage
regulation (Battery
mode)

+/- 5%

Built-in UPS output
receptacles

4 5-15R outlet(s); 4 5-15/20R outlet(s)

Built-in controllable
switched load banks

Two switched single outlet load banks (1 5-15/20R & 1 5-15R)

Output AC waveform
(AC mode)

Pure Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

16.0A

Nominal Input
Voltage(s) Supported

120V AC

UPS input
connection type

5-20P

UPS Input cord
length (ft.)

10

UPS Input cord
length (m)

3

Recommended
Electrical Service

20A 120V

Содержание SmartPro SMART2200RMXL2U

Страница 1: ...ows and Mac OS X Network communications ports enable detailed monitoring of equipment load levels self test data and utility power conditions Includes PowerAlert monitoring software and complete cabling Switched output load banks enable scheduled and real time remote reboot and load shedding of select outlets Emergency Power Off EPO interface LCD display panel easily rotates for viewing in rackmou...

Страница 2: ... 1920 Output kW capacity 1 92 Output power factor 0 87 Output Capacity Details Output derates to 1600 watts in all external battery pack configurations Nominal Output Voltage s Supported 120V Frequency compatibility 60 Hz Output voltage regulation line mode 14 6 Output voltage regulation Battery mode 5 Built in UPS output receptacles 4 5 15R outlet s 4 5 15 20R outlet s Built in controllable switc...

Страница 3: ...pplies when input is between 127 and 145 Undervoltage correction Voltage boost of 12 applies when input voltage is between 96 and 108 Severe undervoltage correction Voltage boost of 24 applies when input voltage is between 83 and 95 LEDS ALARMS SWITCHES Front panel LCD display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data plus con...

Страница 4: ...ack Height 2U Secondary form factor Tower requires 2 9USTAND UPS Power Module weight lbs 57 6 UPS Power Module weight kg 26 2 UPS Shipping dimensions height x width x depth inches 9 1 x 22 44 x 24 2 UPS Shipping dimensions height x width x depth cm 23 x 57 x 61 5 Shipping weight lbs 68 8 Shipping weight kg 31 2 Cooling method Fan UPS housing material Steel ENVIRONMENTAL Operating Temperature Range...

Страница 5: ...tifications Tested to UL1778 USA Tested to CSA Canada Tested to NOM Mexico Meets FCC Part 15 Category A EMI ROHS Restriction of Hazardous Substances WARRANTY Product Warranty Period Worldwide 2 year warranty 3 year with registration Note registration is required for 3 year warranty Connected Equipment Insurance U S Canada Puerto Rico 250 000 Ultimate Lifetime Insurance Related Items Optional Produ...

Страница 6: ... L5 20P input with 5 20P adapter 1 PDUMNH20 Single Phase Monitored PDU 20A 120V 1U Horizontal Rackmount NEMA 5 15 20R outlets NEMA L5 20P input with 5 20P adapter 1 PDUMV20NET Single Phase Switched PDU 20A 120V 0U Vertical Rackmount NEMA 5 15 20R outlets NEMA L5 20P input with 5 20P adapter 1 PDUMH20AT Single Phase Auto Transfer Switch Metered PDU 20A 120V 1U Horizontal Rackmount 5 15 20R outlets ...

Отзывы: