5. Operation Modes
Bypass Range Setup
BYPASS RANGE: Sets the allowable voltage deviation (in percentage %) from nominal input voltage
that is acceptable for the unit to go to bypass in a fault condition. If the voltage goes outside the
range, the unit will not go to bypass. If the unit is already in bypass, it will turn the output off. The
factory setting of 15% of 230V is compatible with the vast majority of networking equipment.
Bypass Range Table
5% to 15% = -5%, +5% to -15%, +15%
HI 1 = -20% to +15%
HI 2 = -25% to +15%
HI 3 = (120V to 226V)
Economy Mode Setup
ECONOMY MODE is a UPS setting that enables enhanced efficiency and reduced BTU output by
suspending double-conversion circuits whenever input power is already of sufficient quality to run
connected equipment. If enabled, the UPS will run in economy mode when the voltage is within
±10% of nominal. If the voltage goes beyond the ±10% range, the UPS returns to on-line mode.
Note:
Economy Mode is off by default.
Alarm Setup
The ALARM screen gives the user the ability to permanently enable or disable the UPS system’s
audible alarm in case of an alarm event. The factory default of ON is ideal for most applications.
Certain applications may require the alarm to be disabled, in which case the OFF option may be
selected.
Overload Alarm Setup
OVERLOAD ALARM refers to the point at which the UPS will sound its overload alarm. The factory
setting of 105% will provide adequate overload warnings for most applications, but alternative
values from 5% to the 105% default (in 5% intervals) are available for custom configurations.
5.7 External Battery Type Selection Mode
EXTERNAL BATTERY TYPE refers to the ability for the UPS to become aware of which external battery
pack is connected to the UPS. Setting the external battery configuration enhances the accuracy of
the MINUTES RUNTIME countdown during power failure conditions. To update the runtime, you must
use Tripp Lite’s EXTERNAL BATTERY CONFIGURATION TOOL software available for download at this
link: http://www.tripplite.com/bpconfig.
18-09-252-93358B.indb 17
1/9/2019 2:19:30 PM
Содержание SmartOnline SUINT1000XLCD
Страница 80: ...80 3 0 1 4 0 1 1 3 3 2 3 3 3 SETUP 1 0 1 2 3 5 6 3 3 1 2 3 1 2 3 18 09 252 93358B indb 80 1 9 2019 2 19 39 PM...
Страница 84: ...84 3 24 0 0 45 0 50 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 18 09 252 93358B indb 84 1 9 2019 2 19 40 PM...
Страница 87: ...87 5 5 6 3 1 2 3 4 5 6 1 3 2 0 1 3 0 1 4 0 1 5 3 6 2 18 09 252 93358B indb 87 1 9 2019 2 19 41 PM...