Included battery pack weight (lbs)
158.7
Included battery pack weight (kg)
72
UPS Shipping dimensions (height x
width x depth / inches)
39.8 x 31.5 x 23
UPS Shipping dimensions (height x
width x depth / cm)
101 x 80 x 58.4
Shipping weight (lbs)
331
Shipping weight (kg)
150.3
Cooling method
Fan
UPS housing material
Steel
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full load)
2732
AC economy mode BTU / hr. (full
load)
1020
AC mode efficiency rating (100%
load)
91%
AC economy mode efficiency rating
(100% load)
96%
Operating Elevation (ft.)
0-3000m (0 to 10,000 ft.)
Audible Noise
60 dBA at front side 1 meter
Operating Elevation (m)
0-3000 m
COMMUNICATIONS
Communications interface
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports
PowerAlert software
Included
Communications cable
USB, DB9 serial and EPO cables included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Transfer time (economy mode)
8 ms. typical power failure response in optional economy mode
Low voltage transfer to battery
power (setpoint)
100V
5 / 7