background image

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

125A (per phase, online)

Nominal Input
Voltage(s) Supported

120V / 208V 3 phase wye

UPS input
connection type

Hardwire

UPS input
connection
description

120/208V (3-Phase, 4 Wire, wye)

Phase

3-Phase

BATTERY

Expandable battery
runtime

Battery set sold separate

External battery
pack compatibility

BP480V26B

BP480V40C

BP480V55

BP480V78

BP480V103

BP480V140

Expandable runtime
description

External battery pack wiring is contractor supplied

DC system voltage
(VDC)

+/- 240

Battery recharge
rate (included
batteries)

Less than 4 hours from 10% to 90%

Battery replacement
description

Hot-swappable, replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Online, double-conversion power conditioning

Overvoltage
correction

Maintains continuous operation without using battery power during overvoltages to 150 / 260 (3-Phase, 4-Wire, wye),
reducing output within 1% of nominal

Undervoltage
correction

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 94 / 163
(3-Phase, 4-Wire, wye)

LEDS ALARMS & SWITCHES

LED Indicators

4-LED Display: Displays normal AC input, on battery power, bypass input and fault conditions

Alarms

Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more

Alarm cancel
operation

Power-fail alarm can be silenced using alarm-cancel switch

Switches

ON button turns UPS's inverter ON. OFF button turns UPS's inverter OFF. LCD Display Control Buttons browses
through and selects items displayed on LCD screen. Emergency Power Off button turns UPS output OFF and
disables Bypass output. Manual Bypass breaker bypasses the UPS's inverter during maintenance.

SURGE / NOISE SUPPRESSION

UPS AC
suppression joule
rating

4675