SU60K UPS System

PowerAlert Software and cabling

Parallel cable (for 1+1 operation)

Instruction manual and startup checklist

Warranty information

Features

N+1 configuration: three self-contained, redundant 20kVA power modules can be hot-swapped (with the load powered) if maintenance is

required

1+1 configuration: connect two SU60K models in parallel to provide fail-safe redundancy or to increase capacity

High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology create low input Total Harmonic

Distortion (THDi)

Extremely efficient operation (up to 96%) saves money by lowering electricity consumption

True on-line, double conversion UPS with IGBT technology provides pure, sine wave AC output at all times

Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time

Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems

60,000VA/48,000W power capacity with 3-phase, hardwire 120/208VAC input/output connections

Features a wide input voltage correction range: 94-150/163-260VAC

A stand-alone hardwired external battery module (Models BP480V26B and BP480V40C, available separately from Tripp Lite) is required for

operation and to provide battery backup support. Additional external battery modules can be connected for extended runtime.

Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed

Dynamic battery management screen optimizes battery function to lengthen service life and allows cold restart of UPS

Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single

server

Accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns, reboots and more

Emergency Power Off button turns UPS output OFF and disables Bypass output

Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities

Start-up service program

 is recommended to enhance the reliability of the installation

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

60000

Output kVA capacity
(kVA)

60

Output Watt
Capacity (watts)

48000

Output kW capacity

48

Output power factor

0.8

Crest Factor

3:1

Nominal Output
Voltage(s) Supported

120/208V; 3-Phase Wye

Frequency
compatibility

50 / 60 Hz

Output voltage
regulation (line
mode)

+/- 2%

Output voltage
regulation (Battery
mode)

+/- 2%

Built-in UPS output
receptacles

Hardwire