background image

1

5

9

3

7

11

2

6

10

4

8

12

13

14

1

2

3

5

4

A

Output

Manual 

Bypass

Bypass 

Input

Main 

Input

Q2

Q4

Output

Output

Manual 

Bypass

Manual 

Bypass

Bypass 

Input

Bypass 

Input

Main 

Input

Main 

Input

Q3

Q1

A

32

9 – Start-Up, Shutdown and Bypass 

(continued)

9-11 Switching from Manual Bypass to Normal Mode (Parallel UPS)

If the UPS systems have external battery cabinets connected, 

• 

switch off the external battery cabinet circuit breaker switch 

A

 

of each battery pack. On the SU20KX or SU40KX, turn OFF the 
battery breaker on the back of the UPS.

Switch on the bypass input circuit breaker switch 

• 

Q2

 and the 

output circuit breaker switch 

Q4

 of each UPS system.

Confirm that both UPS systems are shut down, then switch off 

• 

the manual bypass input circuit breaker switch 

Q3

 of each UPS 

system. The LCD screen will read “ON AUTO BYPASS”.

Switch on the main input circuit breaker switch 

• 

Q1

 of each UPS 

system.

Press the ON button 

• 

A

 of the first UPS systems for 3 seconds 

(until you hear a beep), then release the button. Press the ON 
button for the second UPS system for 3 seconds (until you hear 
a beep), then release the button. When the inverter of each UPS 
system is operating normally, they will switch to online (normal) 
mode at the same time.

1

2

3

4

5

Содержание SmartOnline SU20KX

Страница 1: ...p Lite to activate your warranty 1 SmartOnline 3 Phase UPS Systems Models SU20KX SU40KX SU60KX SU80KX Input Output 220 380V 230 400V or 240 415V AC 3O 4 wire ground Not suitable for mobile application...

Страница 2: ...S 25 9 3 Normal Start Up Procedure Single UPS 25 9 4 Battery Start Up Procedure Single UPS 26 9 5 Manual Bypass Procedure Single UPS 27 9 6 Shutdown Procedure Single UPS 27 9 7 Preliminary Checklist P...

Страница 3: ...undancy SU40KX SU60KX and SU80KX Built in parallel or hot standby redundancy 1 1 capability for increased capacity or fault tolerance Up to 80kVA capacity in a compact footprint up to 160kVA in parall...

Страница 4: ...djustments within the final installation area only The casters are not designed for moving the UPS system over longer distances The casters are not designed to provide long term support for the UPS sy...

Страница 5: ...attery supply is connected Service and repair should be performed by trained personnel only while the UPS system is turned off or placed into bypass mode Disconnect internal batteries if present befor...

Страница 6: ...conds to turn the UPS system s inverter ON OFF Button Press and hold this button for 3 seconds to turn the UPS system s inverter OFF If the UPS system is in online normal mode it will switch to auto b...

Страница 7: ...ied electrician See Section 6 Internal Battery Connection for more information Output Circuit Breaker Switch Q4 Controls AC output power Manual Bypass Circuit Breaker Switch Q3 Controls AC input power...

Страница 8: ...nitoring of operating and power conditions Parallel Configuration Port This DB9 port connects the UPS system to another UPS system of identical type and capacity for use in a parallel redundancy 1 1 c...

Страница 9: ...em if it has been damaged or mishandled Confirm that the shipping container is upright and use a screwdriver to remove its top panel front panel and back panel Also remove the plastic wrap and interio...

Страница 10: ...e with the UPS system s input requirements See the Section 12 Specifications for more information about input requirements and floor loading requirements The UPS system must be installed in a clean se...

Страница 11: ...alified service personnel only following all the precautions listed in this manual and adhering to local electrical codes Read Section 2 Important Safety Instructions before proceeding Internal batter...

Страница 12: ...1 2 6 10 4 8 12 13 14 UPS System Battery Back Connector UPS System Battery Back Connector Fuse Block Bracket 12 6 Internal Battery Connection continued SU40KX shown 6 1 Internal Battery Wiring Diagram...

Страница 13: ...f the UPS system Remove the battery access bezels located on the front of the UPS system Remove the battery cartridge fuses from each fuse block Disconnect the blue and white jumper cables attached to...

Страница 14: ...ed until all the battery strings have been inserted into the empty battery slots Note Depending on the model of the UPS system some battery compartment slots may remain empty Reconnect the fuse block...

Страница 15: ...ermining the possible causes of the incorrect voltage reading before proceeding Connect the black cable for each internal battery pack to the nearest black connector located inside the UPS system s ba...

Страница 16: ...l connection to an IT power distribution system that requires neutral isolation upon disconnect the disconnect device must be a four pole device and must disconnect all line conductors and the neutral...

Страница 17: ...ass Input External Battery Connection External Battery Cabinet Breaker Switch 17 7 Wiring continued SU80KX and BP480V40C shown for illustration only consult the battery cabinet s documentation for exa...

Страница 18: ...ound 4 wire ground 250A 70 mm2 SU40KX 220 380V 230 400V 220 380V 230 400V 125A 50 mm2 or 240 415V AC 3O or 240 415V AC 3O 75A 25 mm2 160A 70 mm2 4 wire ground 4 wire ground 250A 70 mm2 SU60KX 220 380V...

Страница 19: ...ive neutral N and negative external battery connection terminals of the UPS system See Section 7 3 and the external battery cabinet s documentation for terminal block diagrams See Section 7 4 for wiri...

Страница 20: ...at the main input circuit breaker switch Q1 and the bypass input circuit breaker switch Q2 are both off Second confirm that the manual bypass circuit breaker switch Q3 is off Third confirm that the ou...

Страница 21: ...7 wiring the UPS systems as shown in the diagram Connect the included parallel UPS cable A to the parallel port B of each UPS system 7 9 AC Input Output Wiring Parallel UPS Dual Input Sources Paralle...

Страница 22: ...the operation of connected equipment 8 3 Auto Bypass Mode Single UPS If the inverter malfunctions due to excessive temperature overload output short circuit abnormal voltage or battery problems the in...

Страница 23: ...connected equipment load is supported by the remaining UPS system If the total load exceeds the capacity of the remaining UPS system it will switch to auto bypass mode 8 6 Battery Backup Mode Paralle...

Страница 24: ...to manual bypass mode for a single UPS system Section 8 4 except with parallel 1 1 UPS systems Note Both UPS systems must be switched into manual bypass mode 8 9 Hot Standby Mode Parallel UPS For add...

Страница 25: ...ton OFF Button EPO Emergency Power Off Button Main Input Circuit Breaker Switch Bypass Input Circuit Breaker Switch Manual Bypass Circuit Breaker Switch Output Circuit Breaker Switch 9 2 Preliminary C...

Страница 26: ...Press the ON button A for 3 seconds until you hear a beep then release the button The inverter will activate and synchronize with the bypass source then automatically switch from auto bypass reserve m...

Страница 27: ...elsewhere Turn ON the MANUAL BYPASS circuit breaker Q3 The LCD will display Load Unprotected On Manual Bypass and you will hear an audible alarm Turn OFF the OUTPUT circuit breaker Q4 Turn OFF the BY...

Страница 28: ...on the display and audible beeping If an alarm is present press the UP or DOWN arrows to display the active alarm Correct the action as required 10 Scroll through the Measure Menu and confirm all inpu...

Страница 29: ...breaker switch Q2 of each UPS system After a brief initialization process the LCD screen will show ON AUTO BYPASS and the BYPASS LED will illuminate Switch on the main input circuit breaker switch Q1...

Страница 30: ...too large to be handled by a single UPS system both UPS systems will shut down their inverters and switch to bypass mode and their LCD screens will read ON AUTO BYPASS For the UPS system you wish to...

Страница 31: ...s mode and their LCD screens will read ON AUTO BYPASS Repeat step 1 for the second UPS system you wish to shut down Switch off the main input circuit breaker switch Q1 of each UPS system Confirm that...

Страница 32: ...back of the UPS Switch on the bypass input circuit breaker switch Q2 and the output circuit breaker switch Q4 of each UPS system Confirm that both UPS systems are shut down then switch off the manual...

Страница 33: ...s LCD Status Display Multi language display ESC Escape Button Escape Page Up Scroll Buttons and Scroll cursor Up or Down Enter Button Confirm settings ON Button Press and hold for 3 seconds to start u...

Страница 34: ...stem starts up and completes the self test the LCD status screen will show the default display The default display includes a status message and diagram that shows the operational status of the UPS sy...

Страница 35: ...ntinued 10 3 1 Status Display continued The loads are supplied by bypass source due to initial startup of the UPS The UPS is starting up by battery power The UPS system is in auto bypass mode Connecte...

Страница 36: ...splay continued The UPS system is operating in online normal mode Connected equipment loads will receive battery backup power if the mains utility or generator power source fails The UPS is in battery...

Страница 37: ...ystem is in manual bypass mode in order to allow qualified service personnel to perform maintenance or repair on the UPS system Connected equipment loads will lose power if the bypass power source fai...

Страница 38: ...iguration continued 10 4 Main Menu continued UPS System Measure Menu 1 Press the enter button to select MEASURE from the main menu 2 Use the scroll buttons or to scroll through the available data scre...

Страница 39: ...OR Qualified service personnel User The authorization is only to check the parameter but not to configure The password consists of 4 numerals Press the scroll down button or the scroll up button to se...

Страница 40: ...assword is wrong press to reselect 10 5 1 Bypass Setup Enter the UPS system setup menu Use the scroll buttons to move the cursor to BYPASS SETUP then press the enter button From the VOLTAGE RANGE scre...

Страница 41: ...s frequency range and press the enter button to confirm the setting Press ESC to return to the UPS SETUP menu 10 5 2 Output Setup Use or to select OUTPUT SETUP then press to confirm 3 All parameters i...

Страница 42: ...rformance From the FREQUENCY screen use the scroll buttons to select the desired setting and press the enter button to confirm the setting Note The output frequency setting is only used when the UPS s...

Страница 43: ...e or to select the desired number of modules for redundancy usually one for redundancy then press to confirm This feature allows the user to determine an acceptable power output limit to guarantee a r...

Страница 44: ...g For example SU40KX and BP480V26B 58 AH 9 9 40 BAT STRINGS If only internal batteries are used enter the number of strings For example SU40KX has two internal battery strings so enter 2 If both inter...

Страница 45: ...the enter button to confirm the settings Battery Next Replace Date Use or to set the next replace date then press to confirm When the selected date is reached the UPS will alarm and a message will be...

Страница 46: ...al power module multiplied by the number of modules For example the SU60KX has three internal power modules so its charger current range is 2 15 amps Set the charger current value based on the size of...

Страница 47: ...allel group setting tells the UPS that it is operating in parallel Group 1 is the default setting See Section 7 Wiring for wiring considerations Note Possible settings are 1 or 2 Parallel ID Identifie...

Страница 48: ...o confirm Use or to select the desired item then press to confirm Battery Auto Test Use or to select the desired item then press to confirm Allows for scheduling of a battery test frequency for the du...

Страница 49: ...word will be needed Force Boost Charge Press to execute FORCE BOOST CHARGE Enables activating the boost charge which is at a voltage of 20 higher than the nominal setting Warning Boosting battery char...

Страница 50: ...assword to confirm the operation Press ESC to return to the UPS SETUP menu 10 5 7 Local Setup Use or to select LOCAL SETUP then press to confirm Use or to select the desired item then press to confirm...

Страница 51: ...rmat Use or to change the date format then press to confirm This item is user accessible From the SERIAL COM ID screen use the scroll buttons to select the desired serial port ID and press the enter b...

Страница 52: ...e settings Note The administrator password should be used by qualified service personnel only User Password The password consists of 4 digits From the PASSWORD CHANGE screen use the scroll buttons and...

Страница 53: ...number of the UPS unit Use or to select the desired item then press to confirm Firmware Version Use or to select the F W version item then press to confirm The display will show the firmware version o...

Страница 54: ...ess to confirm The ADVANCED item includes clear statistics clear event log firmware upgrade and other status monitor for service This item is only accessible for administrator The Password will be req...

Страница 55: ...sets Input Contact A Pin 1 2 Rated for 12V DC minimum 0 1A nominal Input Contact B Pin 3 4 Rated for 12V DC minimum 0 1A nominal See Section 11 5 P3 External Battery Cabinet Temperature 1 Temperature...

Страница 56: ...iary Dry Contact Input Circuit Diagram The auxiliary dry contact input connections P2 allow the UPS system to receive external signals These contacts are normally open External contacts rated for 12V...

Страница 57: ...allel redundancy installation the parallel communication is not normal Output overload warning shutdown The load exceeds the capacity of the UPS system Power module fault shutdown The UPS system has s...

Страница 58: ...etwork RS 232 signals and operations include load level battery status battery level operation mode AC input voltage AC output voltage AC input frequency internal temperature set shut down delay time...

Страница 59: ...Input Output Bypass Inverter Frequency Loading Battery Voltage UPS abnormal messages with intelligent self diagnosis Interface Standard RS 232 Dry Contact Optional SNMPWEBCARD Others Parallel Redunda...

Страница 60: ...product should prove defective in material or workmanship within that period Seller will repair or replace the product in its sole discretion Service under this Warranty includes parts and Tripp Lite...

Отзывы: