background image

Operating
Temperature
Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage
Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr.
(full load)

512

AC economy
mode BTU / hr.
(full load)

142

Battery mode BTU
/ hr. (full load)

813

AC economy
mode efficiency
rating (100% load)

97%

Audible Noise

< 50.5 dB at front side 1m

COMMUNICATIONS

Communications
interface

USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface

Network
monitoring port
description

Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications

PowerAlert
software

Included

Communications
cable

USB and DB9 cabling included

WatchDog
compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

Zero transfer time (0 ms.) in online, double-conversion and frequency regulation / conversion modes

Low voltage
transfer to battery
power (setpoint)

55V (33% load), 70V (70% load), 100V (100% load)

High voltage
transfer to battery
power (setpoint)

150

SPECIAL FEATURES

Cold Start (startup
in battery mode
during a power
failure)

Cold-start operation supported

High availability
UPS features

Automatic inverter bypass; Hot swappable batteries

Green & high
efficiency features

High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)

WARRANTY

Содержание SmartOnline SU1500XLCD

Страница 1: ...meters and line power status Included PowerAlert power management software supports an unlimited number of network UPS systems The SU1500XLCD also accepts an optional SNMPWEBCARD accessory that enables the UPS to operate as a managed device on the network It comes backed by a 2 year warranty and 250 000 of Ultimate Lifetime Insurance Package Includes SU1500XLCD SmartOnline Tower UPS System PowerAl...

Страница 2: ... provides surge protection for a standard phone or network connection cable not included EMI RFI Line Noise Filtering Various electrical and radio sources can cause disruptive interference on the AC line This line noise is a common cause of incremental hardware damage data corruption and audio video performance problems The SU1500XLCD incorporates technology that filters out disruptive line noise ...

Страница 3: ...ut frequency on startup Output matches input frequency when 5Hz of nominal Output is regulated to 0 05Hz when input frequency exceeds 5Hz of nominal UPS switches to battery mode when input frequency is below 40Hz or above 70Hz FREQUENCY REGULATION CONVERSION MODE Output is regulated to 0 05Hz of selected output frequency when input is 40 to 70Hz UPS switches to battery mode when input frequency is...

Страница 4: ...teries Less than 3 hours from 10 to 90 Replacement battery cartridge internal UPS battery replacement RBC48 SUTWR Battery Access Battery access door Battery replacement description Hot swappable user replaceable batteries VOLTAGE REGULATION Voltage regulation description Online double conversion power conditioning Overvoltage correction 2 output voltage regulation during overvoltages to 150 Underv...

Страница 5: ...ise suppression Yes PHYSICAL Installation form factors supported with included accessories Tower Primary form factor Tower UPS Power Module dimensions in primary form factor height x width x depth inches 10 2 x 9 x 19 5 UPS Power Module dimensions in primary form factor height x width x depth cm 25 9 x 22 9 x 49 5 UPS Power Module weight lbs 52 3 UPS Power Module weight kg 23 7 UPS Shipping dimens...

Страница 6: ...ommunications cable USB and DB9 cabling included WatchDog compatibility Supports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time Zero transfer time 0 ms in online double conversion and frequency regulation conversion modes Low voltage transfer to battery power setpoint 55V 33 load 70V 70 load 100V 100 load High voltage transfer to...

Страница 7: ...uires ENVIROSENSE 1 PDUB15 Single Phase Hot Swap PDU 15A 120V 2U Horizontal Rackmount 8 NEMA 5 15R outlets set of 2 NEMA 5 15P input plugs 1 PDUMH15AT Single Phase Auto Transfer Switch Metered PDU 15A 120V 1U Horizontal Rackmount 8 NEMA 5 15R outlets 2 NEMA 5 15P inputs 1 PDUMNV15 Single Phase Monitored PDU 15A 120V 0U Vertical Rackmount 16 NEMA 5 15R outlets NEMA 5 15P input plug 1 PDUMV15NET Sin...