background image

DC system voltage
(VDC)

48

Battery Access

User replaceable, hot swap battery replacement supported via front access panel

Full load runtime

Internal batteries — 5 min. /1 BP48V212U battery pack (1500VA) — 28 min.

Half load runtime

Internal batteries — 17 min. / 1 BP48V212U battery pack (750VA) — 74 min.

Battery Pack
Accessory
(optional)

BP48V212U (optional)

Typical battery
lifespan

3-6 years, depending on usage

Battery recharge
rate

2-4 hours to 90%

VOLTAGE REGULATION

Voltage regulation
description

On-line, double-conversion power conditioning maintains output within 2% of 120 volts at all times

Overvoltage
correction

Maintains output of 120V +/-2% without consuming battery power during overvoltages to 138V AC

Brownout
correction

Maintains output of 120V +/-2% during undervoltages to 80V AC

Severe brownout
correction

At load levels less than 70%, UPS maintains output of 120V +/-2% during undervoltages to 65V AC

LEDS ALARMS & SWITCHES

Alarms

Multi-function audible alarm offers notification of UPS start, backup operation, low battery warning, overload, UPS fault
and remote shutdown

Switches

Includes main power off/on switch, plus 1 switch to select battery charge / load level display

Front panel LEDs

6 LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red),
battery low (yellow) 
4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%)

SURGE / NOISE SUPPRESSION

UPS AC
suppression joule
rating

2440 joules

EMI / RFI AC noise
suppression

Yes

AC suppression
response time

Instantaneous

PHYSICAL

Shipping weight
(lbs)

63.8

Shipping weight
(kg)

29.0

Unit Dimensions
(HWD/in)

3.5 x 17.5 x 22

Unit Dimensions
(HWD/cm)

8.89 x 44.5 x 52.8

Unit weight (lbs)

49