background image

UPS / Power Module
weight (lbs)

43

UPS / Power Module
weight (kg)

19.5

Included battery
pack dimensions
(height x width x
depth / inches)

5.25 x 17.5 x 25

Included battery
pack dimensions
(height x width x
depth / cm)

13.3 x 44.4 x 63.5

Included battery
pack weight (lbs)

158.7

Included battery
pack weight (kg)

72

UPS Shipping
dimensions (height
x width x depth /
inches)

38.25 x 31.5 x 23

UPS Shipping
dimensions (height
x width x depth / cm)

97.2 x 80 x 58.4

Shipping weight (lbs)

327.6

Shipping weight (kg)

148.7

UPS housing
material

Steel

Cooling method

Fan

ENVIRONMENTAL

Operating
Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage
Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr.
(full load)

3415

AC economy mode
BTU / hr. (full load)

1275

AC economy mode
efficiency rating
(100% load)

96%

Operating Elevation
(ft)

0-3000m (0 to 10,000 ft.)

Audible Noise

60 dBA at front side 1 meter

Operating Elevation
(m)

0-3000 m

COMMUNICATIONS

Communications
interface

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Содержание SmartOnline SU10KRT3UHV

Страница 1: ...rial locations Package Includes SU10000RT3UPM 3U UPS power module BP240V10RT3U external battery pack SUPDMB710HW Detachable PDU with manual bypass switch Four post compatible rack rail kit 2 sets Towe...

Страница 2: ...er Off EPO via built in interface Included rail kit supports 6U 19 inch rackmount installation in 4 post racks Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks Front panel LEDs and...

Страница 3: ...Y Full load runtime minutes 4 3 min 9000w Half load runtime minutes 12 5 min 4500w Expandable battery runtime Supports extended runtime with optional external battery packs External battery pack compa...

Страница 4: ...swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantaneous EMI RFI AC noise suppression Yes PHYSICAL Installation form factors supported with included ac...

Страница 5: ...lbs 327 6 Shipping weight kg 148 7 UPS housing material Steel Cooling method Fan ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Ran...

Страница 6: ...ge varies beyond 10 with less than 1 millisecond transfer time between modes High availability UPS features Automatic inverter bypass Manual bypass switch Detachable hot swap PDU Hot swappable UPS pow...

Страница 7: ...eb or Telnet 1 SNMP Accessories SRSWITCH Magnetic Door Switch Kit for front and rear doors requires ENVIROSENSE 1 UPS Accessories MODBUSCARD For remote monitoring and control via MODBUS protocol 1 UPS...

Отзывы: