10
Installation
Hardwire Input and Output Wiring Instructions (Optional with Select Models)
Note:
The tightening torque is 1 N•m (10 lb•in.).
CAUTION:
This type of connection must be performed by qualified professional electrical service personnel only. When making connections,
check that the mains power to the UPS is OFF. Connect the ground wires from the cables to the chassis ground lug. Always connect the
ground wire first.
Be sure to observe the Input Line Configuration, Breaker and wire AWG as outlined in the
UPS Input and Output Overview
table, detailed
in this section.
Note: Select models include an AC input cord with L6-30P plug. If this AC cord is to be used, the UPS input/output power capacity ratings will
change. See the UPS nameplate for more information.
1. Remove the access cover located on the right side of the Hardwire In/Out knockouts (shown below), to access the terminal block.
Note:
A label describing terminal connections can be found on the back of the access cover.
2. Remove the appropriate knockout sizes for the hardwire input and output connections.
3. Install and secure the included or user-provided strain relief connectors to the hardwire enclosure.
4. Pass the cable through the strain relief.
Note:
The Output strain relief is on top and the Input strain relief is on the bottom.
5. Install each wire to the terminal block, as indicated below. (See note below regarding tightening torque specifications.)
6. Tighten the strain relief.
Hardwire In/Out with Strain Relief
Input and Output Terminals
ACC SLOT
RS232
USB
EPO
Parallel Port
BP DETECT
REMOTE ON/OFF
L1
OUT
L2/N
OUT
L1
IN
L2/N
IN
GND
OFF
ON
VCC
X
GND
EPO
VCC
AC MAINS CONNECTIONS
GROUND
Note:
The tightening torque is 1 N•m (10 lb•in.). The
included ground lug needs to added to the ground stud as
shown. The ground wire for equipment should fit the #8 stud
with an outer diameter of 8.71 mm and an inner diameter of
4.3 mm.
Содержание SmartOnline AG-0358 Series
Страница 106: ...106 0 3 smart Tripp Lite BP192V12RT3US...
Страница 108: ...108 BP192V12RT3US 1 2 3 4 1 2 3 Smart Battery 4...
Страница 109: ...109 1 2 5 7 6 8 5 6 7 8 1...
Страница 110: ...E D G G F 1 2 3 4 A B B A C C 110 1 BP192V12RT3US 1 A B 6 5 e o a o 2 B C 2 4 2 4 c 3 D E F 4 G 5 8...
Страница 111: ...111 Tripp Lite 2 9USTAND SmartOnline Tripp Lite Smart Smart Smart Tripp Lite Smart 2U Tripp Lite 2POSTRMKITWM...
Страница 116: ...210 3000 3000 Escape Page Up Page Down Enter 210 3000 3000 210 3000 3000 0 3000 3000 116 Tripp Lite 5 4 2 0 5...
Страница 122: ...122 0 5 60 60 0 5 50 60 50 0 5 FREQUENCY CONVERSION FREQUENCY CONVERSION...
Страница 131: ...131 Tripp Lite Tripp Lite Tripp Lite Tripp Lite ECO Tripp Lite smart EPO NonSmart Non Smart Smart...
Страница 133: ...1 2 5 6 9 7 8 133 5 6 7 8 9 1...
Страница 134: ...1 5 3 134 tripplite com support 1 2 2 3 4 3 2 5 1...