![Tripp Lite SmartOnline 3-Phase UPS Systems SU20KX Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/tripp-lite/smartonline-3-phase-ups-systems-su20kx/smartonline-3-phase-ups-systems-su20kx_owners-manual_1167810021.webp)
21
1
5
9
3
7
11
2
6
10
4
8
12
13
14
7 – Wiring
(continued)
7-8 AC Input/Output Wiring (Parallel UPS – Single Input)
Parallel Redundancy Warnings:
The total input cable length must be equal to the total
•
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).
Parallel redundancy only supports 2 UPS systems (1+1
•
redundancy ). Do not attempt to link more than two UPS
systems via parallel redundancy.
The UPS systems must have the same rating and capacity
•
for parallel redundancy installation. Attempting to link
dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Follow the steps in
•
Section 7-7
, wiring the UPS systems as shown
in the diagram.
Connect the included parallel redundancy cable
•
A
to the parallel
redundancy port
B
of each UPS system.
7-9 AC Input/Output Wiring (Parallel UPS – Dual Inputs)
Parallel Redundancy Warnings:
The total input cable length must be equal to the total
•
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).
Parallel redundancy only supports 2 UPS systems (1+1
•
redundancy ). Do not attempt to link more than two UPS
systems via parallel redundancy.
The UPS systems must have the same rating and capacity
•
for parallel redundancy installation. Attempting to
link dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Follow the steps in
•
Section 7-7
, wiring the UPS systems as shown
in the diagram.
Connect the included parallel redundancy cable
•
A
to the parallel
redundancy port
B
of each UPS system.
1
1
2
2
2
2
1
1
B
B
A
B
B
A
200706017 93-2688 SU manual 4C.indd 21
200706017 93-2688 SU manual 4C.indd 21
11/29/2007 2:02:42 PM
11/29/2007 2:02:42 PM