240
15
DANGER!
BATTERY CARTRIDGE FUSES MUST BE INSERTED LAST DUE TO THE DANGER OF POTENTIAL
ARCING OF CONNECTORS.
FUSE REPLACEMENT
The fuses protect against short circuit damage. If a heavy overload or short circuit is encountered,
a fuse will blow. A battery pack with a blown fuse will not deliver any output voltage to the UPS
system.
DANGER!
The fuses must be replaced by a qualified electrician. To reduce the risk of fire, replace only with
fuses of the same type or rating (UL-recognized 30A 600VDC rated cartridge fuses).
Use a voltmeter (user-supplied) to test the voltage of the battery pack.
Observe proper polarity: connect the voltmeter's
BLACK
probe to the
battery pack's
BLACK
connector; connect the voltmeter's
RED
probe
to the battery pack's
RED
connector. To get a proper reading, make
sure the voltmeter's probes touch the metal contacts inside the battery
pack's connectors.
The battery pack's Acceptable DC Voltage Range
is between 220 and 280V DC.
If several attempts at voltmeter tests
yield results outside this range, contact Tripp Lite for assistance in
determining the possible causes of the incorrect voltage reading.
12
12
Connect the
BLUE
and
WHITE
jumper cables on each internal battery
pack to its corresponding fuse block. See printing next to fuse block to
locate the correct fuse block for each cable.
10
10
Insert the battery cartridge fuses into each fuse block. The fuses are
identical, and can be inserted into any of the blocks. Make sure that the
fuses are firmly snapped into place.
11
11
7. Adding or Replacing Internal Batteries
(continued)