13
Place the UPS System in Bypass Mode or completely turn it off,
depending on preference. (See section 5.4,
Operation of Manual
Bypass Switch
, or 4.2,
Turning the UPS Off
.)
1
Remove battery access panel, located on the FRONT of the UPS
system.
2
2
Disconnect the
RED
and
BLACK
cables attached to each internal
battery pack.
3
3
Remove the battery cartridge fuses from each fuse block.
Save the fuses.
4
4
Disconnect the
BLUE
and
WHITE
jumper cables attached to each
fuse block.
5
5
CAUTION!
When disconnecting the jumper cables, pull
them straight away from the fuse block with
even force. Do not wiggle them side-to-side,
as this may damage the connector.