Expandable runtime with optional BP48V60RT3U external battery packs
Half/full load runtime of 27/10 minutes with internal batteries
Includes 11 output receptacles (2 L6-20, 1 L6-30 & 8 NEMA 5-15/20R)
Ships with installed L6-30P input plug, supports user supplied 50A replacement plug or hardwire input
Integrated 8 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices
3 stage metered LEDs offer current monitoring and battery charge level
Mains power and voltage regulation LEDs offer at-a-glance power status information
Front panel switches support self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch racks
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required
Supports 2 post rackmount installation with optional 2POSTRMKIT accessory
Supports upright tower placement with optional 2-9USTAND accessory
Specifications
OUTPUT
Output Volt Amp Capacity
(VA)
5000
Output kVA capacity (kVA)
5
Output Watt Capacity
(watts)
3750
Output kW capacity
3.8
Output power factor
0.8
Nominal Output
Voltage(s) Supported
120V; 208V
Frequency compatibility
60 Hz
Output voltage regulation
(line mode)
208 & 120V (+/- 10%)
Output voltage regulation
(Battery mode)
+/- 5%
Built-in UPS output
receptacles
8 5-15/20R outlet(s); 2 L6-20R outlet(s); 1 L6-30R outlet(s)
Built-in controllable
switched load banks
Eight switchable single-outlet 5-15/20R load banks
Output circuit breaker
20A double pole breaker supports L6-20R outlets, 20A branch rated breaker (x2) supports 4 5-15/20R outlets
each, L6-30R outlet is unbreakered
Output AC waveform (AC
mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current (at
maximum load)
27A
Nominal Input Voltage(s)
Supported
208V AC
UPS input connection type
L6-30P
UPS Input cord length (ft.)
10
UPS Input cord length (m)
3