Cooling method
Fan
Installed whole system
dimensions in secondary
form factor (height x
width x depth / cm)
44.45 x 8.89 x 34.29
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature
Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
34.3
Battery mode BTU / hr.
(full load)
463.6
COMMUNICATIONS
Communications
interface
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port
description
Supports detailed monitoring of UPS and site power conditions
PowerAlert software
Included
Communications cable
USB and DB9 cabling included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
2-4 milliseconds
Low voltage transfer to
battery power (setpoint)
75
High voltage transfer to
battery power (setpoint)
147
SPECIAL FEATURES
Grounding lug
Back panel grounding lug
Cold Start (startup in
battery mode during a
power failure)
Cold-start operation supported
High availability UPS
features
Hot swappable batteries
Green & high efficiency
features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B
(EMI); ROHS (Restriction of Hazardous Substances)
WARRANTY
Product Warranty Period
(Worldwide)
2-year limited warranty