INPUT

Rated input current (at
maximum load)

10.1A

Nominal Input Voltage(s)
Supported

120V AC

UPS input connection
type

5-15P

Input circuit breaker

15A

UPS Input cord length
(ft.)

10

UPS Input cord length
(m)

3

Recommended Electrical
Service

15A 120V

BATTERY

Full load runtime
(minutes)

7.5 min. (1000w)

Half load runtime
(minutes)

21 min. (500w)

Expandable battery
runtime

Extended runtime supported via optional external battery packs

External battery pack
compatibility

BP36V15-2U

 (limit 1); 

BP36V42-3U

 (multi-pack compatible)

DC system voltage (VDC)

36

Battery recharge rate
(included batteries)

Less than 4.5 hours from 10% to 90%

Replacement battery
cartridge (internal UPS
battery replacement)

RBC93-2U

Battery Access

Front panel battery access door

Battery replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147

Overvoltage correction

Input voltages between 128 and 147 are reduced by 12%

Undervoltage correction

Input voltages between 95 and 104 are boosted by 12%

Severe undervoltage
correction

Input voltages between 75 and 94 are boosted by 24%

LEDS ALARMS & SWITCHES

LED Indicators

5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status

Alarms

Audible alarm indicates power-failure, overload and low-battery conditions

Alarm cancel operation

Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation