background image

2

1. Introduction

2. Installation and Setup

  1.1 Product Features

  2.1 System Requirements

  2.2 Communications Setup

  1.2 Package Contents

The RELAYIOCARD is a programmable UPS management device featuring:

6 programmable relay output contacts

• 

Configurable normal open or normal close for each relay contact

• 

Configurable UPS shutdown delay time

• 

Configurable input signal to shutdown UPS or test battery

• 

The RELAYIOCARD allows you to:

Monitor UPS status and events

• 

Perform remote system shutdowns and battery tests

• 

The RELAYIOCARD supports all Tripp Lite SmartOnline™ UPS Systems and select SmartPro™ UPS Systems, including SMART1050SLT, 
SMART1500SLT, SMART2200RMXL2U, SMX1050SLT, SMX1500SLT, SMART3000SLT, SMART2200SLT, SM2200RMNAFTA, SMART2600RM2U, 
SMART3000RM2U, SMART1500CRMXL, SMART1500SLTXL, SMART750XLa, SMX3000XLRT2U and SMX2200XLRT2U. Supported systems must 
run a UPS protocol of 3008 or above. 

To determine your UPS protocol:

Open Tripp Lite PowerAlert software.

1. 

Click on the “Misc” button on the main screen of the PowerAlert console.

2. 

View the protocol variable.

3. 

Connect Tx to pin2, Rx to pin 3 and GND-C to pin5 of RS-232 DBP port.

1. 

In the Windows environment, launch the Hyper Terminal program, then open the specified COM port.

2. 

Set the following properties – Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.

3. 

This Package Contains:

RELAYIOCARD

• 

Configuration Cable

• 

Faceplates

• 

Owner’s Manual

• 

PROGRAMMABLE RELAY I/O CARD 

USER MANUAL 

PRESENTATION                                                   

FEATURES 

This relay I/O card is an UPS management 

product with 6 relay output contacts for monitoring 

the status and 1 input contact as a shutdown UPS 

or a battery test command. 

Features:

z

  Monitor UPS events. 

z

  6 programmable relay output contacts. 

z

  Configurable normal open or normal close for 

each relay contact. 

z

  Configurable UPS shutdown delay time. 

z

  Configurable input signal as shutdown UPS or 

battery test. 

z

  Has the ability to protect up to 6 computers 

unattended shutdown gracefully. 

TECHNICAL SPECIFICATION                                                                                                                                                           

TECHNICAL SPECIFICATION 

Size

130 x 60 mm

Weight 

200 g

Operating Temperature 

0 ~ 40

q

 C

Operating Humidity 

10 ~ 80 %

Power Input 

8 ~ 20V DC

Power Consumption 

1.2 Watts 

OUTPUT CONTACT RATING 

Maximum 

DC Voltage  DC Current 

Relay 

R1~R6

24 V 

1A

INPUT RATING 

Maximum 

DC Voltage  DC Current 

Input 

24 V 

10 mA 

APPLICATION EXAMPLE                                                                                                                                                                   

In this case we’ll use the default settings, please 

set SW1 and SW2 to the OFF position. Apply 

12VDC to 

Common

 contact and connect the 

lamps to 

R1~R6

 terminals. Install a push button 

from the Common contact to the input terminal. 

Press the button for at least 3 seconds to 

shutdown the UPS remotely. 

Common

GND-R

R1

R2

R3

R4

R5

Input

+12V

Summary Alarm

Power Fail

Battery Low

On Bypass

Overload

Shutdown UPS

R6

Over Temperature

INTERNAL CIRCUIT                                                                                                                       

R1

R2

R3

R4

R5

Common

GND-R

Input

+5V

CPU Pin

R6

OUTLINE 

GND-R

Common

R1

R2

R3

R4

R5

R6

Input

Tx

Rx

GND-C

SW1

SW2

I/O PINOUT 

GND-R

: Ground for relays 

Common

: 12~24VDC 

Default Alarm Event

R1

Summary Alarm 

R2

Power Fail 

R3

Battery Low 

R4

On Bypass 

R5

Overload

R6

Over Temperature 

Input

: Remote shutdown or battery test 

Tx

: Transmit to PC, connect to sub9-pin2 

Rx

: Receive from PC, connect to sub9-pin3 

GND-C

: Ground for configuration Tx and Rx pins

OFF 

(Default)

ON

SW1

Normal open   

for default settings

Normal close   

for default settings 

SW2

Default settings 

Customized settings

PROGRAMMABLE CONTACTS                               

                                             

COMMUNICATION SETUP 

1.  Connect 

Tx

 to pin2, 

Rx

 to pin3 and 

GND-C

 to 

pin5 of PC RS232 port. 

2.  In the Windows environment, launch the 

Hyper- Terminal program then open the 

specified COM port. 

3.  Set the following properties: 

 

Baud rate: 

2400

, Data Bits: 

8

, Parity: 

None

 

Stop Bit: 

1

, Flow Control: 

None

CONFIGURATION 

1.  Press <Enter> to get the main menu of the 

programmable relay card. 


_8365HOD\&DUG_

)LUPZDUH9HUVLRQ5HOD\&DUG9
>@&XVWRPL]H2XWSXW5HOD\
>@&RQILJXUH,QSXW6LJQDO
>@&XVWRPL]H1RUPDO2SHQRU1RUPDO&ORVH
>@4XLW

3OHDVH(QWHU<RXU&KRLFH !

2.  Press ‘1’ to configure the alarm event for 

R1

~

R6

.

Contacts 

R1

~

R6

 can be configured for 

different power events. 


_&XVWRPL]H2XWSXW5HOD\_

5HOD\6HOHFWHG(YHQW
>@5HOD\6XPPDU\$ODUP
>@5HOD\3RZHU)DLO
>@5HOD\%DWWHU\/RZ
>@5HOD\2Q%\SDVV
>@5HOD\2YHUORDG
>@5HOD\2YHU7HPSHUDWXUH
>@%DFN7R3UHYLRXV0HQX

3OHDVH(QWHU<RXU&KRLFH !

 

Once the configuration is complete 

SW2

MUST be switched to the ON position to apply 

the new settings, switch 

SW2

 back to the OFF 

position to reset to the default settings. 

3.    Press ‘2’ to configure the 

Input

 signal. 


_&RQILJXUH,QSXW6LJQDO_

>@$FWDV6KXWGRZQRU7HVW6KXWGRZQ
>@,QSXW6LJQDO&RQILUP6HFRQGV
>@'HOD\%HIRUH6KXWGRZQ6HFRQGV
>@%DFN7R3UHYLRXV0HQX

3OHDVH(QWHU<RXU&KRLFH !

In this menu, the input signal can be redefined 

as shutdown UPS or battery test signal. 

Meanwhile, the UPS shutdown delay time is 

also adjustable to a maximum of 9999 

seconds.

4.    Press ‘3’ to configure the normal open or 

normal close for each relay. 


_&XVWRPL]H2XWSXW5HOD\_

5HOD\6HOHFWHG(YHQW
>@5HOD\1RUPDO&ORVH
>@5HOD\ 1RUPDO2SHQ
>@5HOD\ 1RUPDO&ORVH
>@5HOD\1RUPDO2SHQ
>@5HOD\1RUPDO&ORVH
>@5HOD\1RUPDO2SHQ
>@%DFN7R3UHYLRXV0HQX

3OHDVH(QWHU<RXU&KRLFH !

Once the configuration is complete 

SW2

MUST be switched to the ON position to apply 

the new settings. Switch 

SW2

 back to the 

OFF position to reset to the default settings.   

5.  Press ‘0’ to quit this configuration session. 

The system would prompt you to save or not. 

Press ‘Y’ to save your settings, ‘N’ to ignore. 

POWER OPTION IN WIN 2000/XP         

This relay card has the ability to provide UPS 

signals for Windows NT4/2000/XP/2003. First 

connect the RS232 port on the PC to the relay 

card as shown: 

Then open the power option from control panel 

and click on the UPS tab to setup the signals 

polarity, select 

Positive

 for Power Fail, Low 

Battery and UPS 

Shutdown. 

Since the 

R1

~

R6

contacts are 

programmable, 

the output 

contacts can be 

configured for 3 

computers with 2 

signals (power fail 

and low battery) or 

6 computers with 

one signal (power 

fail or low battery).   

Note: All of the computers must have the same 

earth ground potential. Connect all of the 

computers input power to the same UPS. 

Common

GND-R

R1

R2

R3

R4

R5

Input

Power Fail

R6

Battery Low

RTS pin7

GND pin5

CTS pin8

DCD pin1

DTR pin4

Shutdown UPS

200805102   93-2815.indd   2

7/15/2008   9:19:00 AM

All manuals and user guides at all-guides.com

Содержание RELAYIOCARD

Страница 1: ...oduct Features 1 2 Package Contents 2 Installation and Setup 2 1 System Requirements 2 2 Communications Setup 2 3 Configuration 3 Specifications 4 Warranty Warranty Registration Espa ol Fran ais Use o...

Страница 2: ...In the Windows environment launch the Hyper Terminal program then open the specified COM port 2 Set the following properties Baud rate 2400 Data Bits 8 Parity None Stop Bit 1 Flow Control None 3 This...

Страница 3: ...5HOD 6HOHFWHG YHQW 5HOD 6XPPDU ODUP 5HOD 3RZHU DLO 5HOD DWWHU RZ 5HOD 2Q SDVV 5HOD 2YHUORDG 5HOD 2YHU 7HPSHUDWXUH DFN 7R 3UHYLRXV 0HQX 3OHDVH QWHU RXU KRLFH Once the configuration is complete SW2 MUS...

Страница 4: ...push button from the Common contact to the input terminal Press the button for at least 3 seconds to shutdown the UPS remotely Common GND R R1 R2 R3 R4 R5 Input 12V Summary Alarm Power Fail Battery Lo...

Страница 5: ...2 Contenidos del Embalaje 2 Instalaci n y Configuraci n 2 1 Requisitos del Sistema 2 2 Configuraci n de Comunicaciones 2 3 Configuraci n 3 Especificaciones English Franc s No se recomienda el uso de e...

Страница 6: ...a pin 3 y GND C a pin5 del puerto de RS 232 DBP 1 En el entorno de Windows abra el programa Hyper Terminal luego abra el puerto COM especificado 2 Ajuste las siguiente propiedades velocidad en baudios...

Страница 7: ...LE CONTACTS OMMUNICATION SETUP Connect Tx to pin2 Rx to pin3 and GND C to _ XVWRPL H 2XWSXW 5HOD _ 5HOD 6HOHFWHG YHQW 5HOD 6XPPDU ODUP 5HOD 3RZHU DLO 5HOD DWWHU RZ 5HOD 2Q SDVV 5HOD 2YHUORDG 5HOD 2YHU...

Страница 8: ...HQ DFN 7R 3UHYLRXV 0HQX PRESENTATION FEATURES This relay I O card is an UPS management product with 6 relay output contacts for monitoring the status and 1 input contact as a shutdown UPS or a battery...

Страница 9: ...2 Installation et configuration 1 2 1 Configuration requise 1 2 2 Configuration des communications 1 2 3 Configuration 1 3 Sp cifications 1 English Espa ol L utilisation de cet appareil dans des appli...

Страница 10: ...ctez Tx pin 2 Rx pin 3 et GND C pin 5 du port RS232 de votre PC 1 Dans l environnement Windows lancez le programme Hyper Terminal puis ouvrez le port COM sp cifi 2 R glez les propri t s suivantes Baud...

Страница 11: ...settings ROGRAMMABLE CONTACTS OMMUNICATION SETUP Connect Tx to pin2 Rx to pin3 and GND C to _ XVWRPL H 2XWSXW 5HOD _ 5HOD 6HOHFWHG YHQW 5HOD 6XPPDU ODUP 5HOD 3RZHU DLO 5HOD DWWHU RZ 5HOD 2Q SDVV 5HOD...

Страница 12: ...UPS management product with 6 relay output contacts for monitoring the status and 1 input contact as a shutdown UPS or a battery test command Features z Monitor UPS events z 6 programmable relay outp...

Отзывы: