Operation
Installation
The MODBUSCARD should be installed in the accessory slot of a compatible SmartOnline UPS system.
Note:
Prior to installing the card into the UPS, all configuration switches should be set to the values required by the UPS and your PC
communication ports.
1. Remove the screws securing the blank cover plate from the UPS and set them aside.
2. Detach the communication terminal connector from the MODBUSCARD.
3. Slide the configured MODBUSCARD into the UPS accessory slot
4. With the screws that were removed in step 1, attach the compatible cover plate that came with MODBUSCARD to the
accessory slot mounting points.
5. Re-insert the wired terminal strip connector into the MODBUSCARD port.
6. The MODBUSCARD’s red LED will flash to indicate the UPS is connected and ready for communication.
7. The user will need to supply the means of communication on the PC side via RS-232, RS-422, or RS-485, as well as the
appropriate monitoring software.
LED Indicators
LED
Status
Description
RED
OFF
UPS disconnected
Flashing (1 second)
UPS connected
GREEN
Illuminated (0.2 seconds)
Receiving PC request
Discrete Inputs (Range 0x0100 - 0x012F, Read Function 0x02)
The Read Discrete Inputs function code is used to read 1-2000 contiguous status of Discrete Inputs in a remote device. The
starting address and number of inputs is specified by the request Protocol Data Unit. Addresses start at 0 and Discrete Inputs
numbered 1-16 would address as 0-15.
Description
Address
Value 0
Value 1
Alarm Temperature
0x0100
OK
Over Temperature
Alarm Input Bad
0x0101
OK
Input Bad
Alarm Output Bad
0x0102
OK
Output Bad
Alarm Overload
0x0103
OK
Overload
Alarm Bypass Bad
0x0104
OK
Bypass Bad
Alarm Output Off
0x0105
Output On
Output Off
Alarm UPS Shutdown
0x0106
OK
Shutdown
Alarm Charger Failure
0x0107
OK
Charger Failure
Alarm System Off
0x0108
System On
System Off
Alarm Fan Failure
0x0109
OK
Fan Failure
Alarm Fuse Failure
0x010A
OK
Fuse Failure
Alarm General Fault
0x010B
OK
General Fault
Alarm Awaiting Power
0x010C
OK
Awaiting Power
Alarm Shutdown Pending
0x010D
OK
Shutdown Pending
Alarm Shutdown Imminent
0x010E
OK
Shutdown Imminent
Buzzer Status
0x010F
Silence
Alarm
Economy Mode
0x0110
No
Yes
Alarm Inverter Bad
0x0111
OK
Inverter Bad
Emergency Power Off
0x0112
Off
On
Buzzer State
0x0113
Disable
Enable
Battery Ground Fault
0x0114
OK
Battery Ground Fault
Reserved
0x0115
Reserved
0x0116