Operation

TempStatus

Description

Address

Value

Unit

TempStatus Byte 1, 2

0x0476

Low: Byte 1, Hi: Byte 2

TempStatus Byte 3, 4

0x0477

Low: Byte 3, Hi: Byte 4

TempStatus Byte 5, 6

0x0478

Low: Byte 5, Hi: Byte 6

TempStatus Byte 7, 8

0x0479

Low: Byte 7, Hi: Byte 8

TempStatus Byte 9, 10

0x047A

Low: Byte 9, Hi: Byte 10

TempStatus Byte 11, 12

0x047B

Low: Byte 12, Hi: Byte 12

TempStatus Byte 13, 14

0x047C

Low: Byte 13, Hi: Byte 14

TempStatus Byte 15, 16

0x047D

Low: Byte 15, Hi: Byte 16

TempStatus Byte 17, 18

0x047E

Low: Byte 17, Hi: Byte18

TempStatus Byte 19, 20

0x047F

Low: Byte 19, Hi: Byte 20

Reserved

0x0480

Reserved

0x0481

Temp Byte 1 (Lo):   R Phase Inverter Temperature
Temp Byte 2 (Hi): 

B0: Temperature Warning (>=75C)

 

 

B1: High Temperature Shutdown  

 

   (>=85C)

 

 

B2: Inverter Voltage Too Low

 

 

B3: Inverter Voltage Too High

 

 

B4: Overload Warning

 

 

B5: Overload Shutdown

 

 

B6: Inverter Fuse Fail Shutdown

 

 

B7: Inverter PCB Communication  

 

   Abnormal

Temp Byte 3 (Lo): 

S Phase Inverter Temperature

Temp Byte 4 (Hi): 

B0: Temperature Warning (>=75C)

 

 

B1: High Temperature Shutdown  

 

   (>=85C)

 

 

B2: Inverter Voltage Too Low

 

 

B3: Inverter Voltage Too High

 

 

B4: Overload Warning

 

 

B5: Overload Shutdown

 

 

B6: Inverter Fail Shutdown

 

 

B7: Parallel Communication Abnormal

Temp Byte 5 (Lo): 

T Phase Inverter Temperature

Temp Byte 6 (Hi): 

B0: Temperature Warning (>=75C)

 

 

B1: High Temperature Shutdown  

 

   (>=85C)

 

 

B2: Inverter Voltage Too Low

 

 

B3: Inverter Voltage Too High

 

 

B4: Overload Warning

 

 

B5: Overload Shutdown

 

 

B6: Inverter Freq Abnormal Shutdown

 

 

B7: Parallel Communication Fail

Temp Byte 7 (Lo): 

B3..B0: The Summary of UPS Run at  

 

 

 

Inverter Test Mode

 

 

B7..B4: The Summary of UPS at 

 

 

 

Inverter Mode

Temp Byte 8 (Hi): 

B0: Power Fail

 

 

B1: EPO Happened

 

 

B2: MB_ON (To Bypass)

 

 

B3: Low Battery Warning

 

 

B4: Battery Low Shutdown

 

 

B5: Master UPS (Output Synch)

 

 

B6: Inverter DC Bus Abnormal Shutdown

 

 

B7: Short Circuit Shutdown

Temp Byte 9 (Lo):   Heatsink Temperature
Temp Byte 10 (Hi):  B0: Bypass Voltage Over
 

 

B1: Bypass Voltage Under

 

 

B2: Bypass Freq Abnormal

 

 

B3: Bypass Phase Abnormal

 

 

B4: Rectifier Voltage Over

 

 

B5: Rectifier Voltage Under

 

 

B6: Rectifier Freq Abnormal

 

 

B7: Rectifier Phase Abnormal

Temp Byte 11 (Lo):   Ambient Temperature
Temp Byte 12 (Hi):   B0: Bypass Voltage Over
 

 

B1: Bypass Voltage Under

 

 

B2: SSW at Bypass Side

 

 

B3: SSW at Inverter Side

 

 

B4: Rectifier Voltage Over

 

 

B5: Rectifier Voltage Under

 

 

B6: Rectifier Input Over Current

 

 

B7: Rectifier Input Current Unbalanced

Temp Byte 13 (Lo):   Battery Temperature
Temp Byte 14 (Hi):   B0: Bypass Voltage Over
 

 

B1: Bypass Voltage Under

 

 

B2: Low Battery Shutdown

 

 

B3: Low Battery Warning

 

 

B4: Rectifier Voltage Over

 

 

B5: Rectifier Voltage Under

 

 

B6: Rectifier Fail

 

 

B7: DC Bus Over Voltage

Содержание MODBUSCARD

Страница 1: ...ght 2018 Tripp Lite All rights reserved PROTECT YOUR INVESTMENT Register your product for quicker service and ultimate peace of mind You could also win an ISOBAR6ULTRA surge protector a 100 value www...

Страница 2: ...Single Registers Provides communication through RS 232 RS 485 or RS 422 interfaces Simultaneous communication through RS 232 and RS 485 or RS 232 and RS 422 connection interfaces A MODBUS Device ID C...

Страница 3: ...Note The communication methods chosen must have its configuration dip switches set prior to installing the MODBUSCARD into the UPS systems accessory slot Device ID Configuration Every MODBUS device n...

Страница 4: ...GND Function Switch Value ON OFF SW 1 SW 2 OFF OFF MODBUS OFF ON ON MODBUS ON Baud Rate SW2 1 SW2 2 OFF OFF 2400 Default ON OFF 4800 OFF ON 9600 ON ON 19200 Parity Check SW2 3 OFF Disable Parity Check...

Страница 5: ...efault ON OFF 4800 OFF ON 9600 ON ON 19200 Parity Check SW3 3 OFF Disable Parity Check Default ON Enable Parity Check SW3 4 OFF Even Parity Default ON Odd Parity Protocol SW3 5 SW3 6 OFF OFF MODBUS Pr...

Страница 6: ...PC request Discrete Inputs Range 0x0100 0x012F Read Function 0x02 The Read Discrete Inputs function code is used to read 1 2000 contiguous status of Discrete Inputs in a remote device The starting add...

Страница 7: ...s STS Over Alarm Bypass STS Fault 0x012C OK Bypass STS Fault Reserved 0x012D Reserved 0x012E Reserved 0x012F Note Your UPS may not support all fields Coils Range 0x0200 0x020F Read Function 0x01 Write...

Страница 8: ...nsfer Voltage 0x0304 0 999 Voltage High Transfer Voltage 0x0305 0 999 Voltage Voltage Sensitivity 0x0306 0 Normal 1 Reduced 2 Low Last Battery Replace Date Year 0x0307 0 9999 Last Battery Replace Date...

Страница 9: ...tage High Tx Voltage Point 0x0409 0 999 Voltage Low Tx Voltage Upper Bound 0x040A 0 999 Voltage Low Tx Voltage Lower Bound 0x040B 0 999 Voltage High Tx Voltage Upper Bound 0x040C 0 999 Voltage High Tx...

Страница 10: ...ve Battery Temp 0x042B 0 999 Degrees Celsius Negative Battery Level 0x042C 0 999 Reserved 0x042D Reserved 0x042E Reserved 0x042F Input Status Description Address Value Unit Input Number Lines 0x0430 0...

Страница 11: ...x0450 0 999 Output Voltage 12 0x0451 0 9999 0 1 Voltage Output Voltage 23 0x0452 0 9999 0 1 Voltage Output Voltage 31 0x0453 0 9999 0 1 Voltage Reserved 0x0454 Reserved 0x0455 Bypass Status Descriptio...

Страница 12: ...Temperature 0x0469 0 999 Degrees Celsius Humidity 0x046A 0 999 Relay 1 0x046B 0 Off 1 On Relay 2 0x046C 0 Off 1 On Relay 3 0x046D 0 Off 1 On Relay 4 0x046E 0 Off 1 On Reserved 0x046F Reserved 0x0470 S...

Страница 13: ...emp Byte 5 Lo T Phase Inverter Temperature Temp Byte 6 Hi B0 Temperature Warning 75C B1 High Temperature Shutdown 85C B2 Inverter Voltage Too Low B3 Inverter Voltage Too High B4 Overload Warning B5 Ov...

Страница 14: ...Temp Byte 19 Reserved Temp Byte 20 Hi B5 Ambiance Over Temperature B7 Auxiliary Power Fail Note Currently TempStatus is not supported by UPS Operation Parallel Master ID Description Address Value Uni...

Страница 15: ...1 4 PFC Status 0 1 0x0493 Lo Status 0 Hi Status 1 Power Module ID 0x0494 PFC Status 0 1 0x0495 Power Module ID 0x0496 PFC Status 0 1 0x0497 Power Module ID 0x0498 PFC Status 0 1 0x0499 Reserved 0x049...

Страница 16: ...erter Voltage Abnormal B8 Inverter Circuit General Fault B9 DC Bus Over Voltage Shutdown B10 Inverter Overload B11 B12 Inner Communication Loss includes the communication to system or other modules B1...

Страница 17: ...0x04BD 0 9999 0 1 Voltage Power Module ID 0x04BE 1 4 Temperature PFC 0x04BF 0 9999 0 1 Voltage Temperature TBD 0x04C0 0 9999 0 1 Voltage Temperature INV 0x04C1 0 9999 0 1 Voltage Temperature INV R 0x0...

Страница 18: ...ule ID 0x04E2 1 4 Inverter Voltage R 0x04E3 0 9999 0 1 Voltage Inverter Voltage S 0x04E4 0 9999 0 1 Voltage Inverter Voltage T 0x04E5 0 9999 0 1 Voltage Power Module ID 0x04E6 1 4 Inverter Voltage R 0...

Страница 19: ...Byte 7 Model Byte 8 9 0x0507 Lo Byte 8 Hi Byte 9 Model Byte 10 11 0x0508 Lo Byte 10 Hi Byte 11 Model Byte 12 13 0x0509 Lo Byte 12 Hi Byte 13 Model Byte 14 15 0x050A Lo Byte 14 Hi Byte 15 Reserved 0x05...

Страница 20: ...ts and you may have other rights which vary from jurisdiction to jurisdiction WARNING The individual user should take care to determine prior to use whether this device is suitable adequate or safe fo...

Отзывы: