Nominal Input
Voltage(s) Supported
120V AC
UPS input
connection type
5-15P
UPS Input cord
length (ft.)
10 ft.
UPS Input cord
length (m)
3.05
Recommended
Electrical Service
120V 15A
Voltage
compatibility (VAC)
120
BATTERY
Full load runtime
(minutes)
5 min. (1200w)
Half load runtime
(minutes)
18 min. (600w)
Expandable battery
runtime
Supports extended runtime with optional external battery pack
BP48V24-2U
(limit 1) and
BP48V60RT-3U
(multi-pack
compatible)
External battery
pack compatibility
BP48V24-2U
(limit 1);
BP48V60RT-3U
(multi-pack compatible)
DC system voltage
(VDC)
48
Battery recharge
rate (included
batteries)
Less than 6 hours from 10% to 80%
Replacement battery
cartridge (internal
UPS battery
replacement)
RBC94-2U
Battery Access
Hot-swap battery replacement supported via front access panel
Typical battery
lifespan
3-6 years, depending on usage
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion power conditioning maintains output within 2% of 100/110/120 volts at all times
Overvoltage
correction
Maintains output of selected n/-2% during overvoltages to 138V AC
Undervoltage
correction
2% output voltage regulation during undervoltages to 80
Severe undervoltage
correction
Maintains output within 2% of nominal during undervoltages to 65 (under 70% load only)
LEDS ALARMS & SWITCHES
LED Indicators
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in
rack/tower formats
Alarms
Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 sec. on / 0.5 sec. off),
low battery warning (1.25 sec. on / 0.5 sec. off), overload (sounds continuously), UPS fault (4.2 sec. on / 1 sec. off),
input voltage out of frequency (2.1 sec. on / 0.14 sec. off) and high input voltage (2.1 sec. on 0.07 sec. off)