Tripp Lite HTR15-2U Скачать руководство пользователя страница 2

Instruction manual with warranty information

Features

HTR15-2U Pure Sine Wave UPS provides perfectly regulated sine wave output within 2% of 100/110/120V (user selectable) under all usage

conditions

1500VA/1200W power handling capacity compatible with control systems, high-definition sources, Audio/Video editing suites, digital

consoles, DVD/music/PCs/servers, RAIDs, media centers, PVRs/DVRs, boardrooms, digital processors/EFX, racks and other sensitive

electronics

Removes harmonic distortion, fast electrical impulses, frequency variations and other hard-to-solve power problems not addressed by other

UPS types

Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 100/110/120V (+/-2%) values

2 switchable load banks (2 outlets each) enable remote outlet management for load shedding or remote reboot of individual devices from

anywhere in the world

Single-line tel/DSL/Ethernet surge suppression

Internal battery set offers 18 min. runtime at half load (600W) and 8 min. at full load (1200W)

Optional BP48V60RT3U external battery pack increases runtime to 155 min. at half load (600W) and 72 minutes at full load (1200W);

multi-pack compatible

Optional BP48V24-2U external battery pack increases runtime to 75 min. at half load (600W) and 34 min. at full load (1200W); limit 1

Fault-tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure

and requires maintenance

Compact rackmount form factor installs in 2 rack spaces (2U) with a maximum installed depth of only 19 in.

Offers simultaneous monitoring by up to 3 directly connected devices through included USB, DB9 and SNMP* interfaces (*requires optional

SNMPWEBCARD), or the monitoring of any number of additional UPS systems over IP with included PowerAlert monitoring software

HID-compliant USB interface enables full integration with built-in power management and auto shutdown features of Windows, Mac OS X

and Linux

PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, pager and email

notification, event logging and running user-defined script commands

Front panel LEDs offer current monitoring and battery charge level information

UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required

$250,000 

Ultimate Lifetime Insurance

 (USA and Canada Only)

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

1500

Output Watt
Capacity (watts)

1200

Nominal Output
Voltage(s) Supported

100V; 110V; 120V

Frequency
compatibility

50/60 Hz (auto-selectable)

Frequency
compatibility details

Output frequency matches input nominal on startup

Output voltage
regulation (line
mode)

+/- 2%

Built-in UPS output
receptacles

6 5-15R outlet(s)

Built-in controllable
switched load banks

Two controllable 5-15R load banks (bank 1 - two outlets, bank 2 - four outlets)

INPUT

Rated input current
(at maximum load)

12A