Status LED and Audible Alarm Notifications
The status LED and audible alarm report UPS off/on status, battery mode operation, low battery condition and UPS fault.
See chart for a complete description.
LED Alarm
UPS Status
Off
The mains is normal and UPS is operating normally.
Sounding every 10 seconds
Power failure occurs and UPS is in battery mode.
Sounding every second
Low battery.
Off
UPS is off.
Continuously sounding
UPS fault, the LED will be Off.
LED On
LED Off
LED Flashing
Problem
Possible Cause
Solutions
LED not lit.
The UPS is not on.
Press the power switch again to turn on the UPS.
Battery voltage is too low.
Charge the battery at least 6 hours.
Battery fault.
Replace the battery.
The UPS stays in battery mode.
Power cord loose.
Re-plug the power cord.
The UPS continuously beeps.
UPS may have been damaged. Shut down UPS and disconnect all loads on UPS,
then restart it. If the issue persists please contact
a qualified professional for maintenance.
Backup power time is too short.
Battery voltage is too low.
Charge the battery at least 6 hours.
Overload.
Remove some unnecessary loads. Before recon-
necting equipment, please verify that the load
matches the UPS capability specified in the specs.
Battery defect.
Replace the battery.