background image

13

9. DC Input Terminals (All models):

The terminals’ lug screws secure the wires leading from 

your external battery or battery system. Your battery or battery system must provide your 
APS with proper DC voltage and your equipment with an adequate amp hour capacity. See 
Battery Selection section, pg. 8 for more information.

10. AC Receptacles: NEMA 5-15R (Corded models only):

These receptacles allow you to

connect equipment that would normally be plugged into a utility outlet. They feature ground
fault indicator switches that trip when the receptacles are in danger of short circuiting. If the
switches trip, press to reset them when the short circuit situation is remedied.

11. AC Input Line Cord: NEMA 5-15P fixed (Corded models only):

This cord should be

plugged into a 120V, 60 Hz, dedicated 15 Amp AC utility outlet. DO NOT plug the cord into 
the APS’s AC receptacles.

12. Hardwire AC Input/Output Terminal Strip (Hardwire models only):

Use the lug screws 

on these terminals to secure hardwire connections for AC input and output. See pages 10 &
36 for wiring instructions.

13. Resettable Circuit Breakers (All models):

These circuit breakers protect your APS against 

damage due to input or output overload. If a breaker trips, remove some of the load on the
APS to prevent overload, then wait 1 minute to allow components to cool before resetting
the circuit breaker.

14. Remote Module Connector (All models):

The front panel of all models has an RJ 45

receptacle for use with the optional remote module. (Module is included with all VR models.)
See the installation instructions packed with the remote module.

15. Load Sense Potentiometer (All models):

In order to save battery power, the APS’s inverter

automatically shuts off when no load is connected. When the unit detects a load, it 
automatically turns the inverter on. Users may choose the minimum load the APS will detect 
by adjusting the Load Sense Potentiometer. Using a small tool, turn the potentiometer clockwise
to lower the minimum load that will be detected, causing the inverter to turn on for smaller 
loads. When the potentiometer is turned fully clockwise, the inverter will operate even when
there is no load. Turn the potentiometer counterclockwise to increase the minimum load that
will be detected, causing the inverter to stay off until the new minimum load is reached.
The factory setting for the potentiometer is fully clockwise, but in areas with frequent power
interruptions, the potentiometer should be adjusted counterclockwise until the inverter is 
only in operation when the APS’s load is in use. 

Switches, Indicator Lights & Other Features

continued

Other Features

200110086 120V APS MV-cabinetEn-Sp 93-2006.qxd  1/4/02  10:38 AM  Page 13

Содержание APS POWERVERTER

Страница 1: ...onnection 5 Features 11 Maintenance and Service 14 PowerVerter is a registered trademark of Tripp Lite All rights reserved APS PowerVerter Alternative Power Sources 120V 60 Hz Voltage and Frequency Co...

Страница 2: ...rload Protection If you overload your APS it will automatically protect itself and your valuable batteries from damage Fast Load Switching Your APS provides an uninterruptible power supply If AC power...

Страница 3: ...keep your equipment running through brownouts and overvoltages without draining battery power Load Sharing Select models only Select APS models can be set to limit their own charging functions so they...

Страница 4: ...ell ventilated Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC input terminals Do not short or br...

Страница 5: ...ttery Point DIP Switch 2 Group A Voltage Switch Position 145V Up 135V Down Select Low AC Voltage Switch To Battery Point DIP Switches 4 Group A 3 Group A Voltage Switch Postion 105V 4 Up 3 Up 95V 4 Up...

Страница 6: ...the sum of their AC load and charger power within their circuit breakers rating This charger limiting function has four settings allowing you to choose less charger limiting for APS configurations wit...

Страница 7: ...APS2012 only DIP Switch 4 Group B To prevent overheating smaller batteries the charger on these UPS systems is initially set to deliver only a fraction of its maximum power rating to connected batter...

Страница 8: ...e Actual Amp Hour capacities are less when batteries are discharged at faster rates batteries discharged in 55 minutes provide only about 50 of their listed Amp Hour ratings while batteries discharged...

Страница 9: ...ut for brief periods of time Wiring should be configured to handle this brief high current draw Though your APS is a high efficiency converter of electricity its rated output capacity is limited by th...

Страница 10: ...ckouts adding strain reliefs if desired 3 Connect both input and output ground wires to the ground green terminal 4 Connect the incoming hot wire to the input hot brown terminal 5 Connect the incoming...

Страница 11: ...switches indicator lights and other features 1 Operating Mode Switch All models This switch selects the APS operating mode either AUTO REMOTE OFF or CHARGE ONLY See Set Operating Mode Switch pg 11 to...

Страница 12: ...this happens turn Operating Mode Switch OFF Remove the overload and let the unit cool You may then turn the APS ON after it cools 7 CUT BOOST VR models only These lights will turn ON whenever your AP...

Страница 13: ...APS to prevent overload then wait 1 minute to allow components to cool before resetting the circuit breaker 14 Remote Module Connector All models The front panel of all models has an RJ 45 receptacle...

Страница 14: ...e accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment which has been damaged by accident negligence or misap...

Страница 15: ...PS OFF Wait 1 minute and switch to AUTO REMOTE If automatic shutdown occurs call Tripp Lite Customer Service All APS Indicator Lights are This is normal if the APS is set OFF AC input absent to CHARGE...

Страница 16: ...ceptance Volts VDC Selectable 14 4 V 14 2 V Wet Gel Float Volts VDC w gel 13 3 V 13 6 V Input Voltage AC 120 V Input Current AC 1 4 A LINE VAC OPERATION Minimum Input AC Volts Selectable 75 85 95 or 1...

Страница 17: ...ODELS Cont APS2424 APSVR3636 Weight 41 0 lbs 56 9 lbs INVERTER Continuous power 20 C 2400 W 3600 W Surge power 5 seconds 4800 W 7200 W Efficiency Full Load 89 88 Minimum DC Fuse Rating 300A 300A DC In...

Страница 18: ...s 29 Mantenimiento y Servicio 32 Copyright 2001 Tripp Lite Propiedad Literaria de Tripp Lite 2001 Reservados todos los derechos APS PowerVerter Fuentes Alternativas de Energ a 120V 60 Hz Con Voltaje y...

Страница 19: ...as y a s misma con tra da os Cambio R pido de Carga El sistema APS brinda alimentaci n el ctrica ininterrumpida Si se pierde el suministro de corriente alterna de la red el APS conmutar en 6 milisegu...

Страница 20: ...ndo dicho voltaje para mantener sus equipos en operaci n durante ca das y subidas de voltaje sin desgastar las bater as Compartici n de Carga Modelos selectos solamente Algunos modelos APS pueden ser...

Страница 21: ...terminales entre s con ning n objeto Esto puede producir serias lesiones corporales o da os a objetos Precauciones Sobre la Conexi n de Equipos No utilice los Sistemas APS de Tripp Lite en aplicacione...

Страница 22: ...Voltaje de CA para el Cambio a Bater a Interruptor DIP No 2 Grupo A Voltaje Posici n del Interruptor 145V Arriba 135V Abajo Seleccione el Punto Bajo de Voltaje de CA para el Cambio a Bater a Interrupt...

Страница 23: ...or de circuitos Esta funci n de limitaci n del cargador tiene cuatro posiciones para permitirle escoger una menor limitaci n del cargador para configuraciones de sistemas APS con fusibles de mayor cap...

Страница 24: ...4 y APS2012 nicamente Interruptor DIP 4 Grupo B Para evitar el calentamiento excesivo de bater as de menor tama o el cargador incluido con estos No breaks Sistemas UPS viene limitado de f brica para s...

Страница 25: ...n Amperios Hora 4 La capacidad de bater as en Amperios Hora se indica usualmente para una intensidad de descarga de 20 horas La capacidad actual en Amperios Hora es menor cuando la bater a se descarga...

Страница 26: ...tale una caja de fusibles y un fusible aceptado por UL a una distancia no mayor de 18 pulgadas 46 cent metros de la bater a El ndice de capacidad del fusible debe ser igual o mayor al ndice M nimo de...

Страница 27: ...as del veh culo a 12 V para los sistemas APS de 12 V de entrada nominal de corriente directa etc Ver especificaciones Hay dos maneras principales de efectuar la conexi n a las bater as del veh culo U...

Страница 28: ...uipos 2 Enhebre sus alambres a trav s de los sujetacables y a trav s de la perforaci n para este prop sito 3 Conecte los alambres de conexi n a tierra de la entrada y la salida a la terminal de conexi...

Страница 29: ...otras caracter sticas 1 Interruptor Operating Mode Modo de operaci n Este interruptor selecciona el modo de operaci n del sistema APS AUTO REMOTE autom tico remoto OFF apagado CHARGE ONLY recarga sola...

Страница 30: ...ecarga o sobrecalentamiento Si esto sucediera apague OFF el Interruptor Operating Mode modo de operaci n Disminuya la carga conectada Permita que se enfr e la unidad y encienda ON nuevamente el sistem...

Страница 31: ...ulo de Control Remoto Todos los modelos El panel frontal de todos los modelos incluye un conector tipo RJ45 para utilizarlo con el m dulo opcional de control remoto Este m dulo se incluye con los mode...

Страница 32: ...a sola discreci n de Tripp Lite los productos defectuosos Para obtener servicio bajo esta garant a usted debe obtener un n mero de Autorizaci n de Devoluci n de Material RMA de Tripp Lite o de uno de...

Страница 33: ...o da ado cableado Falla en el cargador del sistema APS Apague el APS Espere 1 minuto y coloque el interruptor en la posici n AUTO REMOTE Si se apaga autom ticamente llame al Servicios a Clientes de Tr...

Страница 34: ...able 2 pies Aceptaci n de Voltios de CD Programable 14 4 14 2 V H meda Gel Flotador Voltios de CD con bater a de gel 13 3 V 13 6 V Voltaje de Entrada de CA 120 V Corriente de Entrada de CA 1 4 A OPERA...

Страница 35: ...eso 18 5 Kg 25 6 Kg INVERSOR Energ a continua a 20 C 2400 Vatios 3600 Vatios Energ a de sobretensiones transitorias 5 segundos 4800 Vatios 7200 Vatios Eficiencia Carga Completa 89 88 Indice M nimo de...

Страница 36: ...3 4 is the output hot black 3 5 is the input output ground tie point 3 6 is the input neutral blue and 3 7 is the input hot brown Refi rase a la secci n Conexiones El ctricas Directas al Circuito p g...

Страница 37: ...specs Refi rase a la secci n Conexi n de Bater as p gina 26 5 1 representa el fusible X El Voltaje Nominal de Entrada del Inversor del APS Vea las especificaciones See Battery Connection Pg 9 6 1 is...

Страница 38: ...Connection See Pg 9 8 1 is the alternator 8 2 is a battery isolator 8 3 is the vehicle battery ground 8 4 is an auxiliary vehicle battery 8 5 is the vehicle battery 8 6 is the fuse Conexi n Avanzada d...

Страница 39: ...s 3 Grupo B de Interruptores DIP Modelos selectos nicamente 4 LINE L nea Todos los modelos 5 INV Inversor Todos los modelos 6 LOAD Carga Conectada 8 BATTERY HI MED LO Carga de Bater as Alta Media Baja...

Страница 40: ...ruptores DIP Todos los modelos 3 Grupo B de Interruptores DIP Modelos selectos nicamente 4 LINE L nea Todos los modelos 5 INV Inversor Todos los modelos 6 LOAD Carga Conectada Todos los modelos 7 CUT...

Отзывы: