background image

Comfort

BREEZE 

TM

 Model CB100

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

10

www.trioniaq.com

6.2 Control Board Faults & Reset

Faults are indicated by a red and green flashing LED located 

on the base of the unit in the lower left corner.  (See figure XX 

above).  There is a reset button on the control board that will 

reset the unit in the event of a fault.  Use the fault list below and 

the troubleshooting chart to diagnose the fault and correct any 

issues that may be present.

When the LED is glowing solid green, the unit is humidifying and 

operating normally.  The following list describes the faults that 

may occur and will be displayed by the LED’s.

1.  Rapid Red Blink = Terminals AP1 & AP2 for the air proving 

switch did not close.  The unit will not operate until airflow 

is present.

2.  Slow Red Blink = Once the solenoid valve is energized and 

humidification has begun, the controls must see a change 

in termperature or the unit will not be allowed to operate. 

This may be an indication of interupted water supply.

3.  Alternating Red/Green Blink = One of the thermistors has 

failed.

• 

If T1  has  failed  the  LED  will  blink  Green/Red/Red  with 

a two second delay.  The unit will not operate in this 

condition unless DIP switch #5 is turned ON and the reset 

button is pressed.

• 

If  T2  has  failed  the  LED  with  blink  Green/Green/Red 

with a two second delay.  The unit will not operate in this 

condition unless the T1 thermistor is relocated to act as 

T2 and DIP switch #5 is turned ON.  Using the override 

DIP switch is only recommended as a temporary solution 

until the failed thermistor can be replaced.

4.  Solid Red LED = This functions to remind the homeowner 

to replace the evaporator pad.  The unit will continue to 

operate and the LED may be cleared by pressing the reset 

button on the control board.

6.3 Motor Replacement 

1.  Follow steps 1-7 in the pad replacement section in order to 

separate the dome from the unit base.

2. 

Insert a flat-head screwdriver into the motor cover as shown 

in Figure 15.  Tilt the screwdriver up as shown in Figure 16.  

This willl release the motor cover and allow you to slide it off 

of the humidifier dome.

3. 

If you have a circuit board equipped unit (CB100S), unplug 

the motor cable from the circuit board.  If you have a unit not 

equipped with a circuit board, unplug the white connector to 

free the motor leads from the relay board.  The motor/dome 

will now be free from the base of the humidifier.

4. 

With  the  motor  cover  removed,  as  described  in  step  2, 

disconnect  the  quick-connects  from  the  black  and  white 

wires.  Also, remove the ground terminal from the motor by 

removing the ground screw.

5. 

Using  an  allen  wrench,  loosen  the  setscrew  on  the  fan 

impeller to remove it from the motor shaft.

6. 

Using  a  nutdriver,  remove  the  four  nuts  that  secure  the 

motor to the dome and remove the motor.  Take care not 

to misplace the nuts, washers, & grommets.   These will be 

used to mount the new motor.

7. 

Install the new motor to the dome using the nuts, washers, 

& grommets that you removed from the old motor.  Refer to  

Figure 17 to see installation order.

8. 

With  the  new  motor  mounted  to  the  dome,  connect  the 

ground wire to the motor and reconnect the quick-connect 

terminals on the black and white wires.

Figure 15

Figure 16

9. 

Replace the motor cover by sliding it onto the dome until it 

bottoms out.  Place the dome back on the base and secure 

it with the screw removed previously.  Refer to Figure 13.

10. 

Reconnect  the  motor  cable  that  was  disconnected  as 

described in step 3.

11.  Close the access door on the dome and replace the screw.  

Refer to Figure 12.

Содержание ComfortBREEZE CB10

Страница 1: ...Tr i o n w w w t r i o n i a q c o m ComfortBREEZE TM CB100 CB100S Flow Through Evaporative Humidifier READ AND SAVE THESE INSTRUCTIONS...

Страница 2: ...ecifications Table 4 3 3 What s in the Box 4 4 Installation 4 4 1 Clearances 4 4 2 Mounting 4 4 3 Plumbing 6 4 4 Electrical Wiring 7 4 4 1 Wiring CB100 without water saving controls 7 4 4 2 Wiring CB1...

Страница 3: ...ts or components and does not include the payment of the cost of labor charges to remove or replace such defective components or parts 7 Trion will not be responsible for loss of use of any product lo...

Страница 4: ...ed range of 30 40 relative humidity assures automatic humidity control during the heating season A lower setting may be necessary to prevent condensation on windows An electronic humidistat is supplie...

Страница 5: ...ded humidistat range is 30 40 relative humidity If condensation occurs on windows the humidistat setting must be lowered to prevent condensation damage DO NOT install the humidifier where freezing tem...

Страница 6: ...debris that may have accumulated in the line during the installation process Once this is complete close the saddle valve 3 Attach the line to the humidifier by simply pushing the line into the push t...

Страница 7: ...SOLENOID VALVE BLK WHT GRN MOTOR DUCT THERMISTOR UNIT THERMISTOR MANUAL HUMIDISTAT SWITCH AIR PROVING HUMIDISTAT ELECTRONIC OR TERMINALS SEE FROM SYSTEM WIRING NOTES LINE CORD 120 VAC TERMINALS SEE T...

Страница 8: ...A solid red LED Service indicator light may light up This will tell you that it is time to service your humidifier Please refer the following procedure DIP 4 Furnace Runs Fan Humidifier Runs Fan In mo...

Страница 9: ...ng from the motor to the circuit board if equipped or disconnect the 3 wire connector 7 Lift the entire dome from the base of the unit by pulling the bottom of the dome away from the base and then lif...

Страница 10: ...vaporator pad The unit will continue to operate and the LED may be cleared by pressing the reset button on the control board 6 3 Motor Replacement 1 Follow steps 1 7 in the pad replacement section in...

Страница 11: ...se is blown Replace circuit board Motor will not operate turn Motor internal thermal protective device is open Remove power and allow motor to cool Restart unit and ensure proper operation If motor wi...

Страница 12: ...ComfortBREEZE TM Model CB100 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 www trioniaq com 11 10 3 13 22 12 Figure 17...

Страница 13: ...ComfortBREEZE TM Model CB100 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 13 www trioniaq com 29 7 8 14 6 21 16 15 1 16 18 17 20 20 4 Figure 18...

Страница 14: ...ComfortBREEZE TM Model CB100 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 14 www trioniaq com 29 7 9 14 6 25 19 16 15 1 16 17 2 Figure 19...

Страница 15: ...OUD 1 1 11 266371 001 COMFORTBREEZE MOTOR MAIN DOME 1 1 12 265462 001 COMFORTBREEZE MOTOR CAP 1 1 13 265463 001 COMFORTBREEZE DOME ACCESS DOOR 1 1 14 265470 001 PAD EVAPORATOR 1 1 15 265471 001P PAINT...

Страница 16: ...Trion 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Trion 2015 All Rights Reserved Form No 265817 002 Rev 02 15...

Отзывы: