background image

12

Electricals

Electrical Requirements:

The Comfort-D is equipped with an appliance cord and may be plugged directly 

into a 120 volt, 15 amp household type convenience outlet�  If used in a wet area 

such as an indoor pool, spa room, or an area prone to flooding (basement or 

crawlspace), a ground fault interrupter protected circuit is required. In all cases 

local codes precede over all installation and wiring recommendations� 

If a remote wall mounted Humidistat is utilized, install the Humidistat control in a 

central area of the structure where it will sense the relative humidity of the struc-

ture accurately� Do not install the control where it may not accurately sense the 

relative humidity: near HVAC supply registers, near exterior doors, or near a pool 

or spa�  Do not install the control in an area not served by the Comfort-D�  The in-

staller must supply the wiring between the Comfort-D and the Humidistat control� 

Be sure to safely route the control wiring to prevent damage during installation� 

Be careful not to cross the wires when connecting the Comfort-D and the control, 

or damage to the transformer may result�

When a remote Humidistat is utilized, set the unit mounted humidistat to the 

“OFF” position. 

Consult the electrical schematic in this manual or on the access panel of the 

Comfort-D before making the control connections�

Condensate Removal:

Condensate drains by gravity, via the ¾” PVC drain outlet located at two loca

-

tions, front side and back side�  Use of both is not required�  As shipped the rear 

drain is plugged, and may be removed and placed into the front drain outlet if the 

rear outlet is used�  Also included with the unit is the condensate drain trap�  This 

trap must be used to allow the unit to drain properly during operation and prevent 

air from being drawn from the area where the unit is located�  A condensate pump 

kit (by others) may be required if a lift is necessary to dispose of the condensate.  

If a condensate pump is used, the condensate trap is still necessary and must be 

installed between the unit and pump�  When the condensate drain is located in, 

or passes through, a non-conditioned space, the condensate piping should be in-

sulated to prevent sweating, which may cause damage�  Double trapping should 

be avoided and will cause drainage problems if encountered�

Condensate

Содержание Comfort-D75

Страница 1: ...16 Whole House Central Dehumidifier Comfort D TM Models D75 and D95 266314 301 05 12 Please complete the following on the day of the installation Homeowner to retain for their future informational pur...

Страница 2: ...the entire home s air can a balance between humidity levels temperature comfort and energy costs be optimized Introduction Contents The following items should be included with your Trion Comfort D De...

Страница 3: ...Service Access Adjustable Legs 1 4 1 Low Voltage Terminal Strip Humidistat Blower Control TOP VIEW FRONT VIEW RIGHT SIDE LEFT SIDE BACK VIEW D E Dimension Table Comfort D75 Comfort D95 A 27 25 inch 2...

Страница 4: ...5 x14 25 Filter Dims LxWxH 11 75 x11 75 x2 00 13 75 x13 75 x2 00 Filter Efficiency MERV 11 MERV 11 Compressor Size 5 8 HP 3 4 HP Fan Motor Size 90 W 115 W Airflow 0 0 inch H2O esp 280 CFM 375 CFM Airf...

Страница 5: ...n pan MUST be placed under the unit if installed above a living area or above an area where water leakage could cause damage see local codes for other requirements 6 DO NOT position the Comfort D dire...

Страница 6: ...the return ducting is adequate tap into the existing return duct system near the return air grill Duct the supply of the Comfort D System to the return ducting of the existing HVAC system The fan int...

Страница 7: ...tions return ducting is not necessary Supply duct ing is recommended to enhance the performance of the system a minimum length of supply duct 3 to 6 will aid in air distribution If the area s being se...

Страница 8: ...de of the system For returns less than 10 feet in length an 8 D75 or 10 D95 round or equal may be utilized Multiple returns are acceptable The supply air outlet and the return air inlet are located on...

Страница 9: ...G R W Y Existing Field Supplied Control Wiring Typ Field Supplied Control Wiring DisconnectExisting Control Wiring From Fan G Control Terminal Reconnectto Blue Wire From Comfort D ConnectBrown Wire F...

Страница 10: ...Interlock C R D G Terminal on existing Thermostat G Terminal on Furnace or Air Handler 24V Hot R Terminal on Furnace or Air Handler Low Voltage Terminal R C H D G Remove Existing Wire Betw een T stat...

Страница 11: ...ifier Blower InterLock Connections Low Voltage Fa n Co il Air Ha n d le r Co n tr o l Th e r m o sta t Typ G R W Y G R W Y Existin g Fie ld Su p p lie d Co n tr o l Wir in g Typ Fie ld Su p p lie d Co...

Страница 12: ...he Comfort D and the control or damage to the transformer may result When a remote Humidistat is utilized set the unit mounted humidistat to the OFF position Consult the electrical schematic in this m...

Страница 13: ...dity control unit will operate the compressor and circulation fan when the dehumidification system is activated working only when there is a call or demand for dehumidification Remote Humidity Control...

Страница 14: ...e the loading and correct replacement intervals Your installation contractor should be contacted for assistance To access the air filter remove the filter access panel from the Front or Back side of t...

Страница 15: ...citor 7 266314 042 266314 043 Fan Run Capacitor 8 N A N A Drain Plug 3 4 MNPT 9 266314 051 266314 051 Curtis Terminal Block 10 266314 061 266314 061 Leveling Mount Foot Base 11 N A N A Evaporated Coil...

Страница 16: ...service dealer or contractor in your area or contact Trion IAQ 101 McNeill Road Sanford NC 27330 WARRANTY LIMITATIONS 1 This warranty is void if the covered equipment is removed from the original ins...

Отзывы: