SLM
102 – Operational Manual
TRINITY
[24]
2. Set all the Event parameters such as same steps of Relays before .
Selecting Baud Rate for RS485 Port and Changing Password
Baud Rate
In case of RS485 connection, the baud rate is settable to either 9600 or 19200 for the
speed of downloading. User can download live data to a host using software utility.
Password
The numerical password used can be changed according to user’s desire from 0 to
9. In case, the PASSWORD is not desired, set zero only for all four digits. In the
PASSWORD prompt, just press
key only to enter into Programming Mode!
To set Baud Rate and password change, proceed the following instruction
1. In the previous programmable parameter display, press
key till the next
display enters such as shown below.
2. In the above first row, Baud Rate displays along with character ‘
B
’ blinking
that shows the parameter is selected. Press
key that will start blinking digit
(i.e., 9). Set Baud Rate by pressing
and
keys and press
key to
confirm the setting so that the blinking character will also return.
3.
Press
key to enter into next row, PASSWORD that character ‘
P
’ will also
blink. Now, press
key that will start blinking first digit ‘0’ and set by
pressing
key only and then, press
key to shift to next digit and set by
pressing
key only. Similay, Set for rest digits also. If any set digit is
supposed to change again, press
key several times to return onto the
desired digit.
Setting IP Address