30
HPP5500
series
bIAS 25
BIAS value when valve position is at 25%
bIAS 75
BIAS value when valve position is at 75%
0Y 0d
Total used time duration. If a unit was used less than 1 minute, the
time will not accumulate.
FULL_OP
Time elapsed for valve to fully open
FULL_CL
Time elapsed for valve to fully close.
VM NOR
Type of valve stroke on LCD. (in percentage or in value)
Erro
Error code or warning message.
VALUE I
Current I value
ABS
Absolute resistance value.
7. Error and Warning Code
7.1 Error
code
Error Code
Code Description and Cause
Action
MT ERR L
Positioner
is
improperly
installed.
Positioner is not parallel to the
ground at 50% point. Lever is at
lower position than actual 50% point.
Re-install
the
positioner.
Ensure the feedback lever does
not touch the lever stopper at 0%
and 100%.
MT ERR H
Positioner
is
improperly
installed.
Positioner is not parallel to the
ground at 50% point. Lever is at
higher position than actual 50%
point.
Re-install
the
positioner.
Ensure the feedback leer does
not touch the lever stopper at 0%
and 100%.
CHK AIR
Valve does not operate when
positioner receive “Full Open” signal
during the auto calibration.
Check
supply
pressure
level.
RNG ERR
Operating angle is too small due to
improper positioner installation.
Adjust bracket so the positioner
can be mounted closer to
actuator.
C
Error of 10% or more persists more than 1
minute.
No valve movement.
High level of valve friction
Changes in setting pressure of actuator.
Perform
BIAS
calibration.
Check setting pressure of actuator.
Содержание Optimux HPP5500 Series
Страница 1: ...SMART POSITIONER PRODUCT MANUAL HPP5500 SERIES VERSION 1 00 ...
Страница 6: ...6 HPP5500 series 2 4 Product Number HPP5500 series can be used for direct mounting application ...
Страница 9: ...9 HPP5500 series 2 7 Product Dimension 2 7 1 HPP5500L 2 7 2 HPP5500R 2 7 2 1 HPP5500R standard ...
Страница 32: ...32 HPP5500 series 8 Main Software Map ...