For your safety
Read all instructions and mounting steps
carefully. Keep the instructions for maintenance
or disassembly work.
Explanation of the warning levels
Observe and follow the warnings.
Non-observance of the warnings may lead
to injuries or material damage!
WARNING!
Indicates dangers which
can result in serious and/or fatal
injuries.
CAUTION!
Indicates dangers which
can result in injuries or health hazards.
NOTICE.
Indicates dangers which
can result in material damage or
malfunctions.
TIP.
Indicates information containing
advice or a useful note.
Explanation of important symbols and
pictograms
Safety notes
Indicates professional personnel who
are trained and authorised to carry
out the electrical connection.
Indicates professional personnel who
are trained and authorised to carry
out the mounting.
WARNING!
Risk of electric shock!
Never work with voltage applied.
Important information on electronic control
gear units (ECG)
A neutral conductor interruption in the three-
phase circuit leads to overvoltage damage
in the lighting system. Only open the neutral
conductor isolating terminal in de-energised
state, and close the neutral conductor isolating
terminal before switching on again. Do not
exceed the maximum permissible ambient
temperature
t
a
of the luminaire.
Exceeding this limit reduces the service life
and in extreme cases there is a risk of premature
failure of the luminaire. Design connection
cables for the control inputs of DALI control
gear (1-10 V, DALI etc.) to be 230 V mains volt-
age-proof (basic insulation).
Disposal of waste electrical and electronic
equipment
Always collect and dispose of old
electrical and electronic equipment
separately at the end of its service
life. In case of doubt, seek information about
environmentally-compliant waste disposal
from your local district authority or special
waste disposal companies. Current information
on the energy efficiency class of the selected
product version can be found in the corre-
sponding data sheet for the luminaire. Instruc-
tions for replacing or removing the light source
in accordance with Regulation 2019/2020/EU
can be found at:
www.trilux.com/EcoDesign
Directive 2014/53/EU
Simplified EU Declaration of Conformity
according to the RED Directive if the luminaire
is equipped with a control gear unit with NFC
interface or a radio component:
TRILUX hereby declares that the following
radio system type complies with Directive
2014/53/EU:
The full text of the EU Declaration of Confor-
mity is available on the Internet at:
www.trilux.com/eu-conformity
LIVELINK
...
Important notes on control units
• Do not exceed the maximum permissible
ambient temperature ta of the control unit.
Exceeding this limit reduces the service
life, and in extreme cases there is a risk of
premature failure of the control unit.
• Lay out the connection cables for the control
inputs of DALI control gear 230 V mains
voltage-proof (basic insulation).
• A maximum of 64 DALI loads per DALI bus
are permitted.
• A maximum of 10 gateways can be connec-
ted in series.
Important notes for checking the installation
Check the installation before commissioning.
To check the installation the gateway features
a function for the broadcast identification of
all connected devices.
• Short key press (SW1 key): all devices flash
• Press the key again (SW1 key): all devices
stop flashing
Intended use
Intended for indoor use with a maximum ambi-
ent temperature of:
ta 40 °C
Safety class:
II
Protection rating:
IP20
NOTICE.
Operation permitted only
with all-pole protected supply. Com-
ply with DALI standard in accordance
with IEC 62386.
Important notes on resetting the gateway
• Long button press (approx. 10 s, button
SW1): settings reset, status LED goes out
briefly and then glows yellow for approx. 2 s.
This is followed by flashing red.
Important notes on the status LED
Each DALI channel has its own status LED.
• Status LED glows green: system is booting.
• Status LED glows continuously and flickers
occasionally: normal operation (gateway
communicating with devices and server).
• Status LED flickers continuously: high com-
munication load (e.g. active DALI scan)
• Status LED flashes (approx. every 0.5 s):
gateway is not connected to the server or
logged in.