TRIGA TR-HRL Скачать руководство пользователя страница 2

I56-5844TRG-002 

2/1/2021

TABLE 3. HORN CURRENT DRAW (mA) 

Pos

Tone

Volume

8-17.5

Volts

16-33 Volts

DC

DC

FWR

1

Temporal

High

39

44

54

2

Temporal

Low

28

32

54

3

Non-Temporal

High

43

47

54

4

Non-Temporal

Low

29

32

54

5

3.1 KHz Temporal

High

39

41

54

6

3.1 KHz Temporal

Low

29

32

54

7

3.1 KHz Non-Temporal

High

42

43

54

8

3.1 KHz Non-Temporal

Low

28

29

54

9

Coded

High

43

47

54

10

3.1 KHz Coded

High

42

43

54

TABLE 4. HORN SOUND OUTPUT (dBA) 

Pos

Tone

Volume

8-17.5

Volts

16-33 Volts

DC

DC

FWR

1

Temporal

High

84

89

89

2

Temporal

Low

75

83

83

3

Non-Temporal

High

85

90

90

4

Non-Temporal

Low

76

84

84

5

3.1 KHz Temporal

High

83

88

88

6

3.1 KHz Temporal

Low

76

82

82

7

3.1 KHz Non-Temporal

High

84

89

89

8

3.1 KHz Non-Temporal

Low

77

83

83

9

Coded

High

85

90

90

10

3.1 KHz Coded

High

84

89

89

TABLE 5. CHIME CURRENT DRAW (mA) 

Pos

Tone

Volume

8-17.5

Volts

16-33 Volts

DC

DC

FWR

1

1 second chime

High

5

8

9

2

1 second chime

Low

5

8

9

3

¼ second chime

High

6

10

10

4

¼ second chime

Low

5

9

9

5

Temporal 3 chime

High

7

10

10

6

Temporal 3 chime

Low

6

9

9

7

5 second whoop

High

12

15

16

8

5 second whoop

Low

7

10

11

9

1 chime (coded)

High

12

15

16

10

NOT TO BE USED

TABLE 6. CHIME SOUND OUTPUT (dBA) 

Pos

Tone

Volume

8-17.5

Volts

16-33 Volts

DC

DC

FWR

1

1 second chime

High

61

62

62

2

1 second chime

Low

56

55

55

3

¼ second chime

High

67

70

70

4

¼ second chime

Low

61

61

61

5

Temporal 3 chime

High

64

66

66

6

Temporal 3 chime

Low

59

60

60

7

5 second whoop

High

76

78

78

8

5 second whoop

Low

62

64

64

9

1 chime (coded)

High

76

78

78

10

NOT TO BE USED

To select the tone, turn the rotary switch on the back of the product to the 
desired setting. (See Figure 1.) 

FIGURE 1. AUDIO SETTINGS 

A0473-00

Available horn settings can be found in Table 1. Available chime settings can 
be found in Table 2. Tones listed as coded are intended to be used with coded 
power supplies. 

TABLE 1. HORN TONES

Pos

Tone 

Volume Setting

Temporal

High

2

Temporal

Low

3

Non-Temporal

High

4

Non-Temporal

Low

5

3.1 KHz Temporal

High

6

3.1 KHz Temporal

Low

7

3.1 KHz Non-Temporal

High

8

3.1 KHz Non-Temporal

Low

9

Coded

High

10

3.1 KHz Coded

High

TABLE 2. CHIME TONES

Pos

Tone 

Volume Setting

1 second chime

High

2

1 second chime

Low

3

¼ second chime

High

4

¼ second chime

Low

5

Temporal chime

High

6

Temporal chime

Low

7

5 second whoop

High

8

5 second whoop

Low

9

1 chime (coded)

High

10

NOT TO BE USED

CURRENT DRAW AND AUDIBILITY RATINGS

For the horn, the current draw for each setting is listed in Table 3 and the au-
dibility ratings can be found in Table 4. For chime, the current draw for each 
setting is listed in Table 5 and the audibility ratings can be found in Table 6. 
Tones listed as coded are intended to be used with coded power supplies. 

Содержание TR-HRL

Страница 1: ... panel manufacturer or power supply for more information These wall horns and chimes come enabled with System Sensor synchro nization protocol which requires connections to a power supply capable of generating the System Sensor synchronization pulses a FACP NAC output configured to System Sensor synchronization protocol or the use of MDL 3 module to generate the synchronization protocol FIRE ALARM...

Страница 2: ... chime High 61 62 62 2 1 second chime Low 56 55 55 3 second chime High 67 70 70 4 second chime Low 61 61 61 5 Temporal 3 chime High 64 66 66 6 Temporal 3 chime Low 59 60 60 7 5 second whoop High 76 78 78 8 5 second whoop Low 62 64 64 9 1 chime coded High 76 78 78 10 NOT TO BE USED To select the tone turn the rotary switch on the back of the product to the desired setting See Figure 1 FIGURE 1 AUDI...

Страница 3: ...of its published specifications Improper connections can prevent the system from alerting occupants in the event of an emergency Wire sizes up to 12 AWG 2 5 mm may be used with the mounting plate The mounting plate ships with the terminals set for 12 AWG wiring Make wire connections by stripping about 3 8 of insulation from the end of the wire Then slide the bare end of the wire under the appropri...

Страница 4: ...is equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The horn or chime will not wo...