JumpStart Operation
System Operation
6.2.9 Zone Trouble
Each Zone has a Trouble LED (see Figure 6.1). The Zone's Trouble LED will blink when the specific SLC issues occur (such as, a missing
device or double address). If you press the Silence Key, it will cause the Zone Trouble LED to be on solid. Once the Zone Trouble is cor-
rected, the LED will turn off.
Figure 6.1 LED Operations
6.3 JumpStart Operation
The JumpStart feature will attempt to do the following:
•
Locate all SLC Mini-Monitor devices installed in the System.
•
Indicate all devices found on the TR-FFT and all TR-24Z-EXT Active LEDs.
•
Allow the user to accept the configuration.
•
Repeat the JumpStart.
•
Allow the configuration to be discarded.
To perform the TR-FFT JumpStart, do the following steps.
1.
Press and hold the JumpStart button for two seconds.
2.
The TR-FFT will search for the installed SLC devices and activate the Active LED’s of all zone/point addresses found.
3.
When the JumpStart is complete, the first four status LEDs will blink.
4.
The user can now press the Accept key causing the TR-FFT to save the configuration and restart.
5.
The user presses the JumpStart key again to repeat the SLC search process.
6.
If the user does not press the Accept key within one minute after the JumpStart is complete, its configuration will be discarded and the
TR-FFT will be restarted.
Answer LED
Active
(green)
Trouble
(amber)