WIRING GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction and must not be of such length or wire 
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and 
accessory devices should be color coded to reduce the likelihood of wiring 
errors. Improper connections can prevent a system from responding properly 
in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm2) may be used with the base. The sounder 
base will be shipped with the screw terminals set for 14 AWG wiring. If 12 
AWG wire is to be used, back out the screws to allow the wire to fit beneath 
the clamping plates. For best system performance, the power (+ and -) wires 
and the communication circuit wires should be twisted pair or shielded cable 
installed in a separate grounded conduit to protect the communication loop 
from electrical interference.
Make wire connections by stripping about 

3

/

8

" (10 mm) of insulation from the 

end of the wire. Then, slide the bare end of the wire under the appropriate 
clamping plate (See Figure 1), and tighten the clamping plate screw. Do NOT 
loop the wire under the clamping plate. (See Figure 2.) The wiring diagram for 
a typical 2-wire intelligent system is shown in Figure 4.

CAUTION

For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire under 
terminals. Break wire run as shown in Figure 2 to provide monitoring of connections.

FIGURE 1. 

FIGURE 2.

1

1

22

33

44

55

66

C0471-08  

C0473-00

TR-B200S-LF-WH/TR-B200S-LF-IV TERMINALS

No. Function
1.

Not Used

2.

Positive (+) Comm. Line In and Out

3.

Negative (-) Comm. Line In and Out

4.

External Supply Positive (+)

5.

External Supply Negative (-)

6.

Remote Annunciator

FIGURE 3. MOUNTING

C0891-09

MOUNTING

Mount the TR-B200S-LF-WH/TR-B200S-LF-IV mounting plate directly to an 
electrical box. The plate will mount directly to 4" (10.2cm) square (with and 
without plaster ring), 4" (10.2cm) octagon, 3½" (8.9 cm) octagon, single gang 
or double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3.  To mount the sounder base, hook the tab on the sounder base to the groove

on the mounting plate.

4.  Then, swing the sounder base into position to engage the pins on the

product with the terminals on the mounting plate.

5. Secure the sounder base by tightening the mounting screws.
6.  Install a compatible smoke sensor as described in the installation manual

for the sensor.

CAUTION

Do not over tighten mounting plate screws; this may cause mounting plate 
to flex.

TAMPER RESISTANT FEATURE

NOTE: Do not use the tamper-resist feature if the removal tool is to be used. 
This detector base includes a tamper-resist feature that prevents its removal 
from the base without the use of a tool. To activate this feature, break the tab 
from the detector base as shown in Figure 7A. Then, install the detector. To 
remove the detector from the base once the tamper-resist feature has been ac-
tivated, insert a small-bladed screwdriver into the slot from the top and press 
down on the lever. (See Figure 7B). This allows the detector to be rotated 
counterclockwise for removal. The tamper-resist feature can be defeated by 
breaking and removing the plastic lever from the base. However, this prevents 
the feature from being used again.

TESTING AND MAINTENANCE

Sensors and bases must be tested after installation and as an integral part of 
a periodic maintenance program. Test the TR-B200S-LF-WH/TR-B200S-LF-IV 
as follows: 
NOTE: Before testing, notify the proper authorities that the smoke sensor 
system is undergoing maintenance and, therefore, will be temporarily out of 
service. Disable the system undergoing maintenance to prevent unwanted 
alarms.
1.  Via the FACP, command the individual TR-B200S-LF-WH/TR-B200S-LF-IV

to activate using the associated sensor address. That sounder base should
sound in approximately five seconds.

2.  Via the FACP, command all TR-B200S-LF-WH/TR-B200S-LF-IV low fre-

quency sounder bases to activate using group communication to all associ-
ated addresses. All devices on the loop should sound, and if a temporal
tone is commanded, the tones can be synchronized to each other.

NOTE: Synchronization requires a power supply capable of producing the Sys-
tem Sensor synchronization pulses or a synchronization module.
When performing maintenance on connected smoke sensors, carefully note 
the location and address of each removed sensor. When re-installed, the 
TR-B200S-LF-WH/TR-B200S-LF-IV will confirm that address of the sensor 
matches the address stored in the sounder base memory. If there is a mis-
match, this will be communicated to the FACP and the sounder base can be 
commanded to chirp at regular intervals until the correct head is installed.
If a replacement head is installed or address changes are required, 
the mismatch may be resolved at the panel by commanding the 
TR-B200S-LF-WH/TR-B200S-LF-IV low frequency sounder base to re-enter its 
address learning mode and adopting the address of the new sensor.

I56-4151TRG-005 

4/22/2021

Содержание TR-B200S-LF-WH

Страница 1: ...setting 15 mA maximum 33 0 VDC 90 mA maximum 24 0 VDC 20 mA maximum 24 0 VDC 140 mA maximum 16 0 VDC 25 mA maximum 16 0 VDC SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum base only refer to applicable sensor specification Sound Output High Volume Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone L...

Страница 2: ...6 Install a compatible smoke sensor as described in the installation manual for the sensor CAUTION Do not over tighten mounting plate screws this may cause mounting plate to flex TAMPER RESISTANT FEATURE NOTE Do not use the tamper resist feature if the removal tool is to be used This detector base includes a tamper resist feature that prevents its removal from the base without the use of a tool To...

Страница 3: ...AC OPTIONAL REMOTE ANNUNCIATOR MODEL TR RA100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTIONAL ...

Страница 4: ...90 02 NOTE Wiring shown for System Sensor MDL Series Sync Module For additional wiring configurations see your sync module manual FACP 1 EOL 1 HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF NAC 1 B B NAC 2 B B NAC 3 B B TO NEXT DEVICE OR EOL 1 TO NEXT DEVICE OR EOL 1 2 CLASS B ZONES MASTER SOUNDER BASE SOUNDER BASE OPTIONAL Triga is a trademark...

Отзывы: