background image

www.tridonic.com

8

Subject to change without notice. Information provided without guarantee.

Data sheet 04/22-EM115-12

Emergency lighting units

EM LED Light Engines

6. Functions

6.2 Testing

Commissioning test

A full commissioning test is carried out automatically after permanent con-
nection of the supply for 5 days. The easy commissioning feature will set the 
initial test day and time to ensure random testing of units.

Functional test

Functional tests are carried out for 5 seconds on a weekly basis under the  
control of the Micro controller. Initiation and timing of these tests is set dur-
ing the commissioning of the luminaire.

Duration test

A full duration test is carried out yearly to check the capacity of the batteries.

For a full description of commissioning and test features please refer to  
application notes.

Test switch

Test switch is integrated in the bezel. This can be used to to:
•  Initiate a 5 seconds function test: 

press 200 ms < T <  1 s

•  Execute function test as long as switch pressed:  press > 1 s
•  Reset selftest timer (adjust local timing): 

press > 10 s

To initiate a test use a suitable tool, refer to drawing below.

Note: Press test switch carefully to avoid damaging it.

Timer reset functionality

The timer for function and duration test can be set to a particular time of the 
day by either pressing the test switch for longer than 10 seconds or cycling 
the unswitched line supply 5 times within 1 minute. The timer adjustment 
will enable the test start time to be defined manually at time in day when the 
timer was reset. It will also disable the adaptive test algorithm thereby forc-
ing the unit to perform the test at the same time rather than it being defined 
by the adaptive algorithm. This function will only work provided the interval 
time is greater than zero (automatic test mode enabled). The delay timer 

6.1 Status indication

System status is indicated by a bi-colour LED. The indication LED is integra-
ted in the bezel.

LED indiction

Status

Comment

Permanent green

System OK

AC mode

Fast flashing green
(0,1 sec on – 0,1 sec off)

Function test 

underway

Slow flashing green
(1 sec on – 1 sec off)

Duration test 

underway

Red LED on

Load failure

Open circuit / Short circuit / LED failure

Slow flashing red
(1 sec on – 1 sec off)

Battery failure

Battery failed the duration test or function 
test / Battery is defect or deep discharged / 
Incorrect battery voltage / Battery is outside of 
its temperature range for charging (0 – 60 °C)

Fast flashing red
(0,1 sec on – 0,1 sec off)

Charging failure Incorrect charging current

Double pulsing green

Inhibit mode

Switching into inhibit mode via controller

Green and red off

DC mode

Battery operation (emergency mode)

value set when the unit was commissioned will be reloaded in order to ran-
domise the tests between adjacent units.

Rest mode

Rest mode can be initiated by applying a short pulse of between 9.5 V

DC

 and  

22.5 V

DC

 in amplitude for a period of between 150 ms and 1.0 s. This should 

be applied to terminals marked Rest after the mains supply has been discon-
nected and whilst the module is in emergency operation. Terminals are not 
sensitive to polarity.
After a mains reset the EM R2A ST exits the rest mode. The EM R2A ST sup-
ports the re-light function.

Pulse/Mode

Standby

Emergency

Rest

150 – 1,000 ms

Inhibit

Rest

1,001 – 2,000 ms

Cancel inhibit

re-light

6.3 Technical data batteries

Accu Lithium Iron Phosphate 

International designation 

IFpR 19/66

Battery  voltage/cell 

3.2 V

Single cell dimensions
  Diameter 

18 mm

  Height 

65 mm

Capacity two cell pack 

3.0 Ah

Max. short term temperature (reduced lifetime) 

70 °C

Max. number discharge cycles 

50 cycles total

Packing quantity 

1 pc. per carton

Comply with UN 38.3 and IEC 62133 (safety testing) protected against over 
charge, over discharge, charging at excessive temperatures, short-circuit and 
over current.

For battery data see separate data sheet.

1.5 mm

Test Switch

Status LED

Содержание EM ready2apply SELFTEST 2 W SM

Страница 1: ...pot illumination Emergency lighting with self test function BESA compatible mounting Properties Output power 1 5 W Very low stand by power loss Non maintained variants 1 or 3 h rated duration separate variants Simple connection of Lithium Iron Phosphate battery with plug in system White or black housing color options Back box in two different heights available for rear and side entry 5 years guara...

Страница 2: ...e Mac Adams 3 Colour rendering index CRI 80 Lifetime up to 50 000 h EM ready2apply SELFTEST 2 W SM EM ready2apply 30 6 123 123 123 52 85 123 32 85 3 1 0 3 18 7 0 3 1 6 0 3 ø 4 1 0 3 ø 4 1 0 3 18 7 0 3 35 0 3 1 6 0 3 Ordering data Type2 Article number Colour Design Rated duration Number of cells Packaging carton Packaging pallet Weight per pc EM R2A ST NM 112 SM 89800790 White low 1 h 2 1 pc s 400 ...

Страница 3: ... R2A ST NM 132 SMh 2 3 h 20 mA 10 mA 2 5 W 0 6 W 0 50c EM R2A ST NM 112 SM B 2 1 h 20 mA 10 mA 2 5 W 0 6 W 0 50c EM R2A ST NM 132 SM B 2 3 h 20 mA 10 mA 2 5 W 0 6 W 0 50c EM R2A ST NM 112 SMh B 1 h 20 mA 10 mA 2 5 W 0 6 W 0 50c EM R2A ST NM 132 SMh B 2 3 h 20 mA 10 mA 2 5 W 0 6 W 0 50c Emergency operation EM R2A ST NM 112 SM 2 1 h 126 mA 12 V 1 50 W EM R2A ST NM 132 SM 2 3 h 126 mA 12 V 1 50 W EM ...

Страница 4: ... year design life up to 40 C ambient temperature 3 years guarantee Properties Certified quality manufacturer Charge efficiency 90 Low self discharge Simple connection with plug in system Protection and monitoring circuit built into battery sleeve Deep discharge protection Suitable for emergency lighting equipment as per IEC 60598 2 22 Lithium Iron Phosphate Battery pack 3 0 Ah Batteries ACCES SORI...

Страница 5: ...sphere with corrosive gas Disconnect batteries before store or delivery Avoid storage of discharged batteries 3 Installation Wiring 3 1 Lens assembly Wear gloves when mounting the lens Take care of the mounting direction of the escape route lens Use screwdriver for replacing removing lens 1 2 Push lens clips with screwdriver via openings on both sides 3 Remove lens Expected lifetime Type ta 25 C 3...

Страница 6: ... drill out Screw holes for BESA and general mounting are oval shape to allow adjust ment and are pre drilled to simplify the final installation 3 4 Wiring type and cross section Wiring Mains N L blue brown Rest orange orange Cable low smoke halogen free 8 1 mm wire preparation 0 5 2 5 mm2 The installation of the luminaire has to be done by a qualified person 4 Mechanical data 4 1 Housing propertie...

Страница 7: ...e 290 mA 0 mA Discharge current at 3 2 V nominal 625 mA 1 Automatic recharge when battery voltage falls below 3 4 V Charger off 0 mA when battery voltage exceeds 3 6 V Note Battery protected against operation at excessive temperatures charging stopped when battery cell temperature 0 C or 60 C 5 4 Battery charge regime discharge EM R2A ST 2 W SM 1 3 h Type EM R2A ST 2 W SM Article no 89800790 93 89...

Страница 8: ...atus indication System status is indicated by a bi colour LED The indication LED is integra ted in the bezel LED indiction Status Comment Permanent green System OK AC mode Fast flashing green 0 1 sec on 0 1 sec off Function test underway Slow flashing green 1 sec on 1 sec off Duration test underway Red LED on Load failure Open circuit Short circuit LED failure Slow flashing red 1 sec on 1 sec off ...

Страница 9: ...ative intensity Iv Iv max Max spacing for 1 0 lux1 Height Centre to end2 Centre to centre3 Trans Axial Trans Axial 2 5 m 4 75 m 2 75 m 11 65 m 6 55 m 3 0 m 4 80 m 2 95 m 12 75 m 7 20 m 3 5 m 5 05 m 1 50 m 13 45 m 6 85 m 4 0 m 5 20 m 1 65 m 13 60 m 6 50 m 5 0 m 5 50 m 1 80 m 14 30 m 4 35 m 6 0 m 5 70 m 1 90 m 15 05 m 4 85 m 7 0 m 5 75 m 1 90 m 15 60 m 5 15 m 8 0 m 5 65 m 1 85 m 16 05 m 5 35 m All v...

Отзывы: