Product manual basicDIM DGC | 07-2018 | 1.9 | en
Installation
c
9 / 48
...
I
NOTICE
Installation
basicDIM DGC can be operated without sensor. For this, the motion sensor must be deactivated with the
masterCONFIGURATOR software.
_
DSI/DALI is not SELV. The installation instructions for mains voltage therefore apply.
_
The maximum cable length between the external switch and basicDIM DGC is 100 m.
_
The maximum cable length between the sensor and basicDIM DGC is 10 m.
_
A synchronous operation of DALI and DSI ballasts at the same control gear is not possible.
_
The output channels (for a cable cross-section of 1,5 m ) must not be exceeded 100 m.
2
_
If CH2 is used as link line, the maximum cable length must not exceed 100 m (at 1.5 mm ).
2
_
Any number of push to make switches may be connected in parallel to the inputs.
_
Do not connect standard switches to the input.
_
Please ensure that the detection range of the sensor lies in the lighting area of the controlled luminaires.
_
Heaters, fans, printers and copiers located in the detection zone may cause incorrect presence detection.
_
To avoid false readings, the sensor should be installed so there is no direct light from the lamp in the detection zone.
_
Sensor wires must be routed separately from the lamp wires and mains cables otherwise the lighting control system may
malfunction. If separate routing is not possible (for reasons of space) shielded lamp wires and mains cables must be used.
_