Product manual basicDIM DGC | 07-2018 | 1.9 | en
Functions
c
22 / 48
5.1.19. Behaviour after return of power
The basicDIM DGC module features two different types of starting behaviour after mains failure.
Symbol
Description
Power ON behaviour OFF (luminaires remain switched off)
Power ON behaviour ON (the luminaires are switched on after return of power).
Default setting for all profiles!
5.1.20. Scenes
Up to 16 scenes can be saved on basicDIM DGC. It is possible to choose different values for CH1, CH2 and the relay.
To call up a scene, the basicDIM DGC must be integrated into a DALI line via DALI IN (wiring DALI). CH1 and CH2 are reacting
different to scene commands than the relay. Because of this, output channels and the relay must be considered separately.
Response of CH1/CH2 to scene commands
If a scene is called, the saved state after the scene command is decisive:
Important note:
If, for example, CH1 is programmed with 0 and CH2 with MASK, then the state of CH2 before the scene command is decisive:
Response of the relay to scene commands
The relay does not respond to scene commands, when it is in standby mode:
If the relay is programmed with MASK, then the state of the relay before the scene command is decisive, for example, if the relay is
programmed with MASK:
If one of the output channels (CH1/CH2) is programmed with a value > 0, the run-on time is started.
_
If both channels are programmed with a value = 0, the dead time is started
_
If CH2 was switched on before the scene command (value > 0), the run-on time is started.
_
If CH2 was switched off before the scene command (value = 0), the dead time is started.
_
If the relay is programmed with ON, the run-on time is started.
_
If the relay is programmed with Off, the dead time is started.
_
If the relay was switched off before the scene command, the dead time is started.
_
If the relay was switched on before the scene command, the run-on time is started.
_