Tridonic 89800643 Скачать руководство пользователя страница 2

www.tridonic.com

2

Subject to change without notice. Information provided without guarantee.

Data sheet 11/20-EM111-1

Emergency lighting units

EM converterLED

 

   

 

     

 

 

 

Technical data

Rated supply voltage

220 – 240 V

AC voltage range

198 – 264 V

Mains frequency

50 / 60 Hz

LED module forward voltage range

48 – 250 V

Output current

see chapter 5.3

Starting time

< 0.5 s from detection of emergency 
event

Overvoltage protection

320 V (for 48 h)

U-OUT (including open- / short-circuit and 
double load)

300 V

Max. open circuit voltage

300 V

Ambient temperature range ta

-25 ... +55 °C

Max. casing temperature tc

80 °C

Mains voltage changeover threshold

according to EN 60598-2-22

Mains surge capability (between L – N)

1 kV

Mains surge capability (between L/N – PE) 2 kV
Type of protection

IP20

Integrated DALI bus power supply IPS

50 mA

Functional test

Weekly 5s test

Duration test

Yearly 1 h / 2 h / 3 h test

Life-time

up to 100,000 h

Dimensions LxWxH

179 x 30 x 21 mm

EM converterLED PRO NF MH/LiFePO4 250 V

Powered DALI PRO NFC series

 

30

21

30

179

169.2

Position A
   3 h

No duration 
link    2 h

Position B
   1 h

Note: LED Driver supplied with duration link in 3 hours position. Duration link must be set 
before battery and mains connection.

Ordering data

Type

1

Article 

number

Rated 

duration

Packaging, 
carton

Packaging, 
pallet

Weight 
per pc.

EM converterLED PRO 303 MH/LiFePO4 250V

 

89800643

1/2/3 h 10 pc(s).

1,600 pc(s). 0.075 kg

EM converterLED PRO 304 MH/LiFePO4 250V 89800644

1/2/3 h 10 pc(s).

1,600 pc(s). 0.075 kg

EM converterLED PRO 305 MH/LiFePO4 250V

89800645

1/2/3 h 10 pc(s).

1,600 pc(s). 0.075 kg

Test switch EM3

 

A

CCES

-

SORIES

 

Ordering data

Type

Article number

Packaging, 
bag

Packaging,
carton

Weight 
per pc.

Test switch EM 3

 

89899956

25 pc(s).

200 pc(s).

0.013 kg

Status indication bi-colour LED

 

A

CCES

-

SORIES

 

Specific technical data

Type

Battery 

technology

Rated 

duration

Typ. λ  

(at 230 V, 

50 Hz)

Typ. output 

power 

P emergency

Mains current in charging operation

Rated power in charging operation

Initial charge

3

Fast recharge

3

Trickle charge

23

Initial charge

3

Fast recharge

3

Trickle charge

23

EM converterLED PRO 303  
MH/LiFePO4 250V

 

NiMH

1 h

0.6C

2.5 W

17 mA

20 mA

17 / 12 mA

2.3 W

2.8 W

2.3 / 1.6 W

2 h

0.6C

2.5 W

24 mA

25 mA

20 / 12 mA

3.2 W

3.4 W

2.7 / 1.6 W

3 h

0.6C

2.5 W

24 mA

25 mA

20 / 12 mA

3.2 W

3.4 W

2.7 / 1.6 W

LiFePO

4

1 h

0.6C

2.5 W

22 mA

22 mA

22 / 12 mA

3.0 W

3.0 W

3.0 / 1.6 W

2 h

0.6C

2.5 W

27 mA

27 mA

27 / 12 mA

4.0 W

4.0 W

4.0 / 1.6 W

3 h

0.6C

2.5 W

27 mA

27 mA

27 / 12 mA

4.0 W

4.0 W

4.0 / 1.6 W

EM converterLED PRO 304  
MH/LiFePO4 250V

 

NiMH

1 h

0.6C

3.5 W

18 mA

22 mA

18 / 12 mA

2.5 W

3.1 W

2.5 / 1.6 W

2 h

0.6C

3.5 W

26 mA

27 mA

22 / 12 mA

3.8 W

4.1 W

3.0 / 1.6 W

3 h

0.6C

3.5 W

26 mA

27 mA

22 / 12 mA

3.8 W

4.1 W

3.0 / 1.6 W

LiFePO

4

1 h

0.6C

3.5 W

22 mA

22 mA

22 / 12 mA

3.0 W

3.0 W

3.0 / 1.6 W

2 h

0.6C

3.5 W

27 mA

27 mA

27 / 12 mA

4.0 W

4.0 W

4.0 / 1.6 W

3 h

0.6C

3.5 W

27 mA

27 mA

27 / 12 mA

4.0 W

4.0 W

4.0 / 1.6 W

EM converterLED PRO 305  
MH/LiFePO4 250V

NiMH

1 h

0.6C

4.5 W

20 mA

24 mA

20 / 12 mA

2.8 W

3.5 W

2.8 / 1.6 W

2 h

0.6C

4.5 W

28 mA

30 mA

24 / 12 mA

4.4 W

4.7 W

3.3 / 1.6 W

3 h

0.6C

4.5 W

28 mA

30 mA

24 / 12 mA

4.4 W

4.7 W

3.3 / 1.6 W

LiFePO

4

1 h

0.6C

4.5 W

22 mA

22 mA

22 / 12 mA

3.0 W

3.0 W

3.0 / 1.6 W

2 h

0.6C

4.5 W

27 mA

27 mA

27 / 12 mA

4.0 W

4.0 W

4.0 / 1.6 W

3 h

0.6C

4.5 W

27 mA

27 mA

27 / 12 mA

4.0 W

4.0 W

4.0 / 1.6 W

EM = Emergency

2

 

In case of NiMH batteries: Intermittent charge is used. Value 1 is for 4 min. charge on / Value 2 is for 16 min. charge off. In case of LiFePO

batteries voltage dependent constant current charging is used. Value 1 is 

for charge on / Value 2 is for charge off

3

 

Integrated DALI bus power supply is switched OFF. With the Integrated DALI bus power supply switched ON and fully loaded the input power and current is increased by 1 W and 6 mA in any charging mode.

Содержание 89800643

Страница 1: ...ayed power switching for the LED Driver Constant power output Two colour status display LED Black Box data recording Interfaces DALI interface for controlled testing and monitoring Near field communication NFC Battery management NiMH LiFePO4 Intelligent charge system Deep discharge protection Polarity reversal protection for battery via polarized connector plug Automatic detection of the connected...

Страница 2: ...rgency Mains current in charging operation Rated power in charging operation Initial charge3 Fast recharge3 Trickle charge23 Initial charge3 Fast recharge3 Trickle charge23 EM converterLED PRO 303 MH LiFePO4 250V NiMH 1 h 0 6C 2 5 W 17 mA 20 mA 17 12 mA 2 3 W 2 8 W 2 3 1 6 W 2 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W 3 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W LiFePO4 ...

Страница 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Страница 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Страница 5: ...lure rate of 0 2 per 1000 operating hours Expected life time with LiFePO4 batteries DALI power supply off Type ta 40 C 45 C 50 C 55 C EM converterLED PRO 303 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 304 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 305 MH LiFePO4 250V tc 6...

Страница 6: ...Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear LED Module Emergency LED Module LED Module LED control gear max 150 W in operation DALI bus Integrated power supply Battery Neutral Bat P O Lout Lin N DA DA L L N EM ConverterLED PRO Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched...

Страница 7: ...ect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4 Direct connection NiMH Connection with extension cable When using an EM converterLED in combination with a NiMH battery order the CONNECTION CABLE NiMH 500mm seperately LiFePO4 Connection with extension cable Battery 300 EM converterLED Battery 500 300 EM converterLED Battery 500 300 EM converterLED Neutr...

Страница 8: ...al and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the EMC performance of the luminaire 3 6 Maximum lead length LED 3 m 6 m loop 1 Status indication LED 1 m Batteries 0 8 m 1 Note The...

Страница 9: ... converterLED PRO MH LiFePO4 250V 90 130 130 130 180 260 260 260 3 6 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver ...

Страница 10: ... battery discharge current tolerance EM converterLED PRO 304 MH LiFePO4 250V Article number 89800644 NiMH battery 4 8 V battery voltage 810 870 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 1 285 1 375 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 305 MH LiFePO4 250V Article number 89800645 NiMH battery 6 0 V b...

Страница 11: ...ure Battery failed the duration test or function test Battery is defect or deep discharged Incorrect battery voltage Fast flashing red 0 1 sec on 0 1 sec off Charging failure Incorrect charging current Double pulsing green Inhibit mode Switching into inhibit mode via controller Binary transmission of address via green red LED Address identification During address identification mode Green and red ...

Страница 12: ... set by the DALI controller This is the delay time bet ween return of the mains supply and the end of the emergency operation The default prolong time is set as 0 minutes as specified within the DALI standard Indicator LED will stay off for the duration of the prolong time Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is ...

Страница 13: ... battery will be charged below 0 9 V The EM converterLED will indicate a battery fault The emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions EM converterLED PRO 1 2 3 h Type EM converterLED PRO 303 MH LiFePO4 250V EM converterLED PRO 304 MH LiFePO4 250V EM converterLED PRO 305 MH LiFePO4 250V Article no 898006...

Страница 14: ...ycles per year plus 30 cycles during comissioning Max storage time 12 months at 5 C to 25 C 8 4 Accu LiFePO4 Capacity 1 5 Ah International designation IFpR 19 66 Battery voltage cell 3 2 V Cell type 18650 Case temperature range to ensure 4 years design life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number disch...

Страница 15: ...operation The Black Box can be read out with the masterCONFIGURATOR and deviceANALYSER via DALI and NFC In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no battery is not connected1 4 Connect new battery 5 Connect main...

Отзывы: