background image

www.tridonic.com

11

Subject to change without notice. Information provided without guarantee.

Data sheet 11/20-EM111-1

Emergency lighting units

EM converterLED

7.4 Testing

DALI Control

A DALI command from a suitable control unit can be used to initiate func-
tion and duration tests at individually selected times. Status flags are set for 
report back and data logging of results.

When a DALI bus has not been connected or when a DALI bus is connected 
but the DALI default DELAY and INTERVAL times have not been re-set 
by sending appropriate DALI commands, then the EM converterLED PRO 
will conduct self-tests in accordance with the default times set within the 
EEPROM. 
These default times are factory pre-set, in accordance with the DALI stan-
dard EN 62386-202, to conduct an automatic function test every 7 days and 
a duration test every 52 weeks. Since the DELAY time is factory pre-set to 
Zero, all units are tested at the same time. Test times can be changed with a 
command over the DALI bus.

5.4 LED Driver compatibility

The EM converterLED emergency unit use 3 pole technology and is compa-
tible with most LED Drivers on the market, however it is important to check 
that the rating of the LED Driver does not exceed the values specified below:

•  The max. allowed output current rating of the associated LED Driver is  

2.4 A peak (current rating of switching relays of EM converterLED)

•  The max. allowed inrush current rating of the associated LED Driver is  

60 A peak for 1 ms or 84 A for 255 μs (inrush current rating of switching 
relay of EM converterLED)

•  The max. allowed output voltage (U-OUT) of the associated LED Driver 

applied to the EM converterLED output is 450V (voltage withstand  
between adjacent contact of the single switching relay of the    
EM converterLED)

•  The max. allowed LED load of the associated LED Driver is 150 W in  

operation. The load must be an LED module.

Check compatibility with the carried out function test (duration at least 5 
seconds) individually for each device.

7.3 Status indication

System status is indicated by a bi-colour LED and by a DALI status flag.

LED indication

Status

Comment

Permanent green

System OK

AC mode

Fast flashing green
(0,1 sec on – 0,1 sec off)

Function test 

underway

Slow flashing green
(1 sec on – 1 sec off)

Duration test 

underway

Red LED on

Load failure

Open circuit / Short circuit / LED failure

Slow flashing red
(1 sec on – 1 sec off)

Battery failure

Battery failed the duration test or function 
test / Battery is defect or deep discharged/ 
Incorrect battery voltage

Fast flashing red
(0,1 sec on – 0,1 sec off)

Charging failure Incorrect charging current

Double pulsing green

Inhibit mode

Switching into inhibit mode via controller

Binary transmission of address 
via green/red LED

Address

identification

During address identification mode

Green and red off

DC mode

Battery operation (emergency mode)

7. Functions

7.2 Duration link selection

Emergency lighting LED Driver supplied with duration link in 3 hours positi-
on (position A).

The position of the link will only be read on first power up. If it is changed  
afterwards both the battery and mains supply must be disconnected for 10 
seconds to enable the EM converterLED to read the new link position on  
reconnection of the battery and mains. It will lead to a false battery failure  
indication if the link is changed after installation without this reset.

2 hr

3 hr

No duration link

Position A

Duration

Link position

1 hr

Position B

6.2 Nearfield communication (NFC)

The NFC Interface allows wireless communication with the LED Driver in 
unpowered state. This interface offers the option to write configuration and 
to read configuration, errors and events via a suitable NFC antenna and the 
companionSUITE software. 
Place the NFC antenna directly on the LED Driver to guarantee a correct 
communication between the LED Driver and the NFC antenna. Any material 
placed between the LED Driver and the NFC antenna can cause a deteriora-
tion of the communication quality. We recommend the use of following NFC 
antennas: 
www.tridonic.com/nfc-readers.

NFC is complied with ISO/IEC 15963 standard.

After programming the device via NFC power up the device one time for one
second till the deviceANALYSER can read out the parameters.

7.1 Integrated DALI bus power supply voltage (IPS)

This feature can optionally be activated (by default it is disabled).

IPS = 50 mA and IPS_max = 250 mA.
The minimum guaranteed output current is 50 mA.
Imax = 250 mA
 
Note: The voltage drop in the DALI wires must not exceed 2 V.

No other DALI power supply is allowed to be connected in parallel.

If the IPS function is activated, do not integrate the Driver into an 
existing DALI network with active DALI bus power supply.

6. Interfaces / communication

6.1 Control input (DA+, DA–)

The DALI Interface allows communication with the Driver via a suitable DALI 
control unit. The DALI interface is not SELV. Install the control cable (DALI 
bus) in accordance to the requirements of low voltage installations.
DALI terminals are mains voltage proof.

Содержание 89800643

Страница 1: ...ayed power switching for the LED Driver Constant power output Two colour status display LED Black Box data recording Interfaces DALI interface for controlled testing and monitoring Near field communication NFC Battery management NiMH LiFePO4 Intelligent charge system Deep discharge protection Polarity reversal protection for battery via polarized connector plug Automatic detection of the connected...

Страница 2: ...rgency Mains current in charging operation Rated power in charging operation Initial charge3 Fast recharge3 Trickle charge23 Initial charge3 Fast recharge3 Trickle charge23 EM converterLED PRO 303 MH LiFePO4 250V NiMH 1 h 0 6C 2 5 W 17 mA 20 mA 17 12 mA 2 3 W 2 8 W 2 3 1 6 W 2 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W 3 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W LiFePO4 ...

Страница 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Страница 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Страница 5: ...lure rate of 0 2 per 1000 operating hours Expected life time with LiFePO4 batteries DALI power supply off Type ta 40 C 45 C 50 C 55 C EM converterLED PRO 303 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 304 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 305 MH LiFePO4 250V tc 6...

Страница 6: ...Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear LED Module Emergency LED Module LED Module LED control gear max 150 W in operation DALI bus Integrated power supply Battery Neutral Bat P O Lout Lin N DA DA L L N EM ConverterLED PRO Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched...

Страница 7: ...ect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4 Direct connection NiMH Connection with extension cable When using an EM converterLED in combination with a NiMH battery order the CONNECTION CABLE NiMH 500mm seperately LiFePO4 Connection with extension cable Battery 300 EM converterLED Battery 500 300 EM converterLED Battery 500 300 EM converterLED Neutr...

Страница 8: ...al and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the EMC performance of the luminaire 3 6 Maximum lead length LED 3 m 6 m loop 1 Status indication LED 1 m Batteries 0 8 m 1 Note The...

Страница 9: ... converterLED PRO MH LiFePO4 250V 90 130 130 130 180 260 260 260 3 6 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver ...

Страница 10: ... battery discharge current tolerance EM converterLED PRO 304 MH LiFePO4 250V Article number 89800644 NiMH battery 4 8 V battery voltage 810 870 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 1 285 1 375 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 305 MH LiFePO4 250V Article number 89800645 NiMH battery 6 0 V b...

Страница 11: ...ure Battery failed the duration test or function test Battery is defect or deep discharged Incorrect battery voltage Fast flashing red 0 1 sec on 0 1 sec off Charging failure Incorrect charging current Double pulsing green Inhibit mode Switching into inhibit mode via controller Binary transmission of address via green red LED Address identification During address identification mode Green and red ...

Страница 12: ... set by the DALI controller This is the delay time bet ween return of the mains supply and the end of the emergency operation The default prolong time is set as 0 minutes as specified within the DALI standard Indicator LED will stay off for the duration of the prolong time Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is ...

Страница 13: ... battery will be charged below 0 9 V The EM converterLED will indicate a battery fault The emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions EM converterLED PRO 1 2 3 h Type EM converterLED PRO 303 MH LiFePO4 250V EM converterLED PRO 304 MH LiFePO4 250V EM converterLED PRO 305 MH LiFePO4 250V Article no 898006...

Страница 14: ...ycles per year plus 30 cycles during comissioning Max storage time 12 months at 5 C to 25 C 8 4 Accu LiFePO4 Capacity 1 5 Ah International designation IFpR 19 66 Battery voltage cell 3 2 V Cell type 18650 Case temperature range to ensure 4 years design life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number disch...

Страница 15: ...operation The Black Box can be read out with the masterCONFIGURATOR and deviceANALYSER via DALI and NFC In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no battery is not connected1 4 Connect new battery 5 Connect main...

Отзывы: