background image

www.tridonic.com

3

Subject to change without notice. Information provided without guarantee.

Data sheet 10/20-EM090-8

Emergency lighting units

EM converterLED

 

Product description

•  Two-colour status display LED

•  Green: system OK, red: fault

•  Plug connection

 

Product description

•  For connection to the emergency lighting unit

•  For checking the device function

•  Plug connection

Test switch EM3

 

A

CCES

-

SORIES

 

Ordering data

Type

Article number

Packaging, 
bag

Packaging,
carton

Weight 
per pc.

Test switch EM 3

 

89899956

25 pc(s).

200 pc(s).

0.013 kg

Status indication bi-colour LED

 

A

CCES

-

SORIES

 

Ordering data

Type

Article number

Packaging, 
bag

Packaging, 
carton

Weight 
per pc.

LED EM 

bi-colour, 1.0 m CON

89800273

25 pc(s).

200 pc(s).

0.015 kg

LED EM 

bi-colour, high brightness HO 1.0 m CON

89800275

25 pc(s).

200 pc(s).

0.015 kg

LED EM 

bi-colour, 0.6 m CON

89800474

25 pc(s).

200 pc(s).

0.005 kg

LED EM 

bi-colour, high brightness HO 0.6 m CON

89800475

25 pc(s).

200 pc(s).

0.005 kg

LED EM 

bi-colour, 0.3 m CON

89800274

25 pc(s).

200 pc(s).

0.005 kg

LED EM 

bi-colour, high brightness HO 0.3 m CON

89800276

25 pc(s).

200 pc(s).

0.005 kg

Содержание 89800624

Страница 1: ...e changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Two colour status display LED Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by by 3 pole connector Automatic detection of the connected battery technology NiMH or LiFe...

Страница 2: ...h 10 pc s 1 600 pc s 0 07 kg Specific technical data Type Battery technology Rated duration Typ λ at 230 V 50 Hz Typ output power P emergency Mains current in charging operation Rated power in charging operation Initial charge Fast recharge Trickle charge2 Initial charge Fast recharge Trickle charge2 EM converterLED ST 202 MH LiFePO4 50V NiMH 1 h 0 65C 1 5 W 15 mA 16 mA 15 11 mA 1 9 W 2 2 W 1 9 1 ...

Страница 3: ...bag Packaging carton Weight per pc Test switch EM 3 89899956 25 pc s 200 pc s 0 013 kg Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Страница 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Страница 5: ... LED modules with a total forward voltage of 10 to 54 V can be connected to the EM converterLED These LED module s marked with Emer gency are operated in emergency mode from the associated battery In normal mains mode all LED modules are operated by the mains LED Driver Meaning of marking Double or reinforced insulation for built in electronic LED Drivers The control gear relies upon the luminaire...

Страница 6: ...r LED Not connected Not connected Control gear LED LED Control gear Battery Battery LED Module Emergency EM converterLED SELFTEST with one LED module for non maintained emergency operation EM converterLED SELFTEST with a standard LED Driver and one LED module for mains and emergency operation EM converterLED SELFTEST with a standard LED Driver and series operation of LED modules One LED module is ...

Страница 7: ...ol Un Switched Line Switched Line out EM ConverterLED SELFTEST One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery co...

Страница 8: ...nducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads to the LED module must not be exceeded...

Страница 9: ...EM converterLED ST MH LiFePO4 50V 90 130 130 130 180 260 260 260 10 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED REST Mains Switched Live Battery LED Test switch Indicator LED REST Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver i...

Страница 10: ...tery discharge current tolerance EM converterLED ST 203 MH LiFePO4 50V Article number 89800625 NiMH battery 3 6 V battery voltage 890 960 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 770 830 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED ST 204 MH LiFePO4 50V Article number 89800626 NiMH battery 4 8 V battery volta...

Страница 11: ...s commissioned will be reloaded in order to randomise the tests between adjacent units 5 4 LED Driver compatibility The EM converterLED emergency unit use 3 pole technology and is compa tible with most LED Drivers on the market however it is important to check that the rating of the LED Driver does not exceed the values specified below The max allowed output current rating of the associated LED Dr...

Страница 12: ...CON 28002327 side by side 2 x 1 Accu LiFePO42B CON 28002319 side by side 4 x 1 Accu LiFePO44B CON 28002323 side by side 5 x 1 Accu LiFePO45B CON 28002326 Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off the LED output If the Inhibit Mode has been ...

Страница 13: ... emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions EM converterLED ST 1 2 3 h LiFePO4 Type EM converterLED ST 202 MH LiFePO4 50V EM converterLED ST 203 MH LiFePO4 50V EM converterLED ST 204 MH LiFePO4 50V Article no 89800624 89800625 89800626 Duration 1 h 2 3 h 1 h 2 3 h 1 h 2 3 h Battery charge time Initial c...

Страница 14: ...cles EM converterLEDs are tested with 50 000 mains switching cycles of the associated LED driver 8 2 Battery replacement After a battery replacement and a subsequent full charge cycle 24 h a duration test is mandatory to prove that with the new battery the rated duration is achieved 8 3 Additional information Additional technical information at www tridonic com Technical Data Guarantee conditions ...

Отзывы: