www.tridonic.com
12
Subject to change without notice. Information provided without guarantee.
Data sheet 10/20-EM090-8
Emergency lighting units
EM converterLED
7. Battery data
7.1 Battery selection
EM converterLED ST, 1 / 2 / 3 h
Type
EM converterLED ST
202 MH/LiFePO4 50V
EM converterLED ST
203 MH/LiFePO4 50V
EM converterLED ST
204 MH/LiFePO4 50V
Article no.
89800624
89800625
89800626
Duration
1 h
2/3 h
1 h
2/3 h
1 h
2/3 h
Technology and
capacity
Design
Number
of cells
Type
Article no.
Assignable batteries
NiMH 4.0 Ah
LA cells
stick
1 x 2
Accu-NiMH 2A CON
28002316
•
stick
1 x 3
Accu-NiMH 3A CON
89800441
•
stick
1 x 4
Accu-NiMH 4A CON
89800442
•
stick + stick
2 + 2
Accu-NiMH 4C CON
89800438
•
LiFePO
4
1.5 Ah
18650 cells
stick
1 x 1
Accu-LiFePO4
1A CON
28002317
•
stick
1 x 2
Accu-LiFePO4
2A CON
28002318
•
•
•
stick
1 x 4
Accu-LiFePO4
4A CON 28002322
•
stick
1 x 5
Accu-LiFePO4
5A CON
28002325
•
stick + stick
2 + 2
Accu-LiFePO4
4C CON
28002324
•
stick + stick
3 + 2
Accu-LiFePO4
5C CON
28002327
•
side by side
2 x 1
Accu-LiFePO4
2B CON
28002319
•
•
•
side by side
4 x 1
Accu-LiFePO4
4B CON
28002323
•
side by side
5 x 1
Accu-LiFePO4
5B CON
28002326
•
Rest Mode / Inhibit Mode
Emergency operation is automatically started when the mains supply is
switched off. If the Rest Mode is activated, the discharging of the battery will
be minimized by switching off the LED output. If the Inhibit Mode has been
activated before the mains supply is switched off, Rest Mode will be automa-
tically activated if the mains supply is switched off within 15 minutes.
Rest Mode and Inhibit Mode can be initiated by applying a short pulse bet-
ween 9.5 and 22.5 V
DC
in amplitude for a period of 150 to 1,000 ms. This pulse
shall be applied to terminals marked Rest.
After a mains reset the EM converterLED exits the Rest Mode. Rest Mode
and Inhibit Mode can both be disabled by applying a voltage pulse of
1,000 to 2,000 ms to the terminals marked as Rest to send the RE-LIGHT/
RESET INHIBIT command.
The EM converterLED ST 202 does not support the Rest Mode / Inhibit
Mode.
Pulse/Mode
Standby
Emergency
Rest
150 – 1,000 ms
Inhibit
Rest
–
1,000 – 2,000 ms
Cancel inhibit
–
Re-light