As delivered, TRIDENT H contains the following two standards:
1) A standard with the thresholds of the EN50160 LV standard.
Standard Name
: EN-50160
Voltage Transformers TP
: 1V / 1V.
Current Transformateurs TC
For TRIDENT H/I : 500 A / 5 A.
For TRIDENT H/V : 100 A/ 1V.
Voltage measurement type
: simple.
Nominale voltage primary
: 240V.
Suscribed primary current
: 400A.
Duration of mesurement integration
: 10 mn.
Harmonic numbers for memorisation
: 3 - 5 - 7.
reference for the THD :
fundamental Voltage.
reference for the harmonic voltage rate:
nominal Voltage.
reference for the TDD :
Subscript Current.
Reference for the current harmonic rate:
subscript current.
THD threshold
: 8%
TDD threshold
: 0%
The threshold of 0% invalidates all the processing concerning possible out-of-limits.
Thresholds for voltage harmonic rates
Odd harmonics
Maximum rate
Even harmonics
Maximum rate
3
5%
2
2%
5
6%
4
1%
7
5%
6...24
0.5%
9
1.5%
11
3.5%
13
3%
15
0.5%
17
2%
19
1.5%
21
0.5%
23
1.5%
25
1.5%
Thresholds for current harmonic rates:
these are all zero, (no processing of current out-of-
limits).