FMS-2000M Lite
LIT-12013692
11
Use the rough-in box for new construction applications when the walls have not yet been installed.
Before you begin, make sure you have the following tools:
•
a drywall saw or an oscillating tool with a drywall saw blade
•
a drill and a 7/16 in. drill bit
•
a #2 Phillips head screwdriver
•
a 1/16 in. hex wrench
Note:
If you want to install the FMS-2000M Lite in a new construction application, attach the rough-in box before the walls are installed.
You can then attach the display once the walls are in place.
1.
Determine the location where you want to place the FMS-2000M Lite monitor. The default orientation is portrait, but you can also
choose to use landscape orientation.
2. Mount the rough-in box to the side of a stud
.
Make sure the front surface is flush, or slightly recessed, to fit with the drywall surface
that you install later.
3.
Pull the pre-wired 4-conductor interface cable and the RS-485 BACnet MS/TP wires through the opening in the rough-in box.
4. If the 2-conductor power cable terminates at the monitor, pull the 2-conductor power cable through the opening in the rough-in box.
5.
Install the drywall. Make sure that the mounting surface is flush with the finished surface of the drywall
, and the opening fits
precisely with the rough-in box.
6. Align the monitor’s mounting bracket to the four screw holes on the mounting tabs of the rough-in box. Use a #2 Phillips head
screwdriver to secure the bracket with the screws provided. Make sure the bracket is level.
Note:
To avoid warping the mounting bracket, do not over-tighten the screws.
7. Connect the wires to the back of the monitor. For more information, refer to Figure 11.
8. Align the two slots on the back of the monitor with the tabs on the bracket and swing the monitor towards the wall so that the single
tab on the bracket slots into the back of the monitor.
9.
Insert the set screw into the hole in the monitor’s housing when the monitor sits flush against the wall. Use a 1/16 in. hex wrench to
drive the screw into the monitor until it engages with the tab on the bracket.
After you mount the FMS-2000M Lite monitor, apply power to the monitor. The initial splash screen displays the Triatek logo and the
Safety Halo bezel lights up green to represent the current system status.
Installing the FMS-2000M Lite Thin Mount display for a new application
1.
58
3 in.
1.
66
2 in.
1.
59
6 in.
1.5 in.
3.18 in.
2.878 in.
3.
33
8 in.
4.
84
in.
1.
5 in.
0.728 in.
1.725 in.
0.728 in.
(84.785 mm)
(122.94 mm)
(40.208 mm)
(42.215 mm)
(40.538 mm)
(73.101 mm)
(80.77 mm)
(38.1 mm)
(18.491 mm)
(43.815 mm)
(18.491 mm)
(38.1 mm)