The 

TRIATEK FMS-1650L

 Isolation Monitor 

is an ultra-sensitive instrument used to control 

and/or monitor air pressure in hospital rooms, 

labs, and clean rooms. This unit is a precision 

measuring system capable of measuring and 

displaying air pressures down to 0.0001” WC. 

It can be used to control pressures down to 

0.001” WC. Features of the unit include:

• 

Digital display of pressure with a  

programmable descriptor

• 

Full color touch screen

• 

audible and visual alarm annunciation

• 

Four relay outputs for transmitting alarm  

conditions to a remote location such as a  

central monitoring station

• 

Auxiliary analog inputs for use with  

optional sensors

• 

Analog outputs used in control 

applications

• 

Password protection of programmed 

setup

• 

Optional keylock switch for isolation 

select protection

• 

Optional LON communications.

 

The FMS-1650L is equipped with a full color 

touch screen display and can be wiped clean 

using a soft cloth without the use of harsh 

chemicals. No decontamination requirements 

are required for the proper operation of this 

product.

There are three background screen colors 

to indicate “

Normal

” when pressure is within 

defined limits, “

Caution

” when pressure 

is nearing an out-of-limits condition, and 

Alarm

” when pressure is outside defined 

acceptable limits. The pressure ranges for 

these conditions are easily set by the user for 

the specific installation when necessary. The 

background screen colors provide overview of 

room pressure conditions at a glance.

Alarm Conditions

 can be defined by the 

user, in terms of desired pressure settings for 

the room being monitored. When an alarm 

condition occurs, it can be annunciated in 

three user-definable ways: 1) on the display, 

2) with an audible alarm, and 3) transmitted 

via contacts to a remote monitoring station 

and over network. The alarm can be set to 

automatically reset  when the unit has sensed 

that the room pressure has returned to proper 

limits, or it may be set to remain on until 

manually reset. In either case, the attendant 

can mute the audible alarm by touching the 

OK

 button on the alarm popup.

The FMS-1650L provides four 

Relay

 

outputs that can be used for remote alarm 

annunciation or pilot control functions. The 

operation of each output can be configured by 

the user to define the exact room air pressure 

values above and below which the output will 

operate. Delay times before activation can be 

specified to minimize nuisance activation.

In many installations, it is important to have 

other room variables such as temperature or 

relative humidity to be displayed along with 

room pressure. 

The FMS-1650L provides for this by means 

of  

Additional Analog Inputs

 which can be 

configured for 4-20 ma current or for voltage 

input signals. The input can be scaled as 

needed to display correct values, and a 

suitable descriptor can be applied.

The FMS-1650L provides 

Analog Outputs

 

which can be set up for voltage. It can be 

programmed to be proportional output (AO-2, 

AO-3 or AO-4) for providing a linear signal 

to an automation system, or programmed 

for PID floating point output (AO-1) for direct 

control of damper actuators, speed drives, 

etc.

The user can set up multiple access level 

passwords to protect against unauthorized or 

casual access to the FMS-1650L programmed 

variables.

Room pressure selection of 

Positive

Negative

, or 

No Isolation

 is set using the 

user menu or an optional 

Keylock Switch

LON Communications Interface

 enables 

the unit to communicate room status 

information to the building automation system.

GENERAL

Overview

TRIATEK reserves the right to change product specifications without notice.

Содержание FMS-1650L

Страница 1: ...FMS 1650L Installation Manual Version 04 02 17 TRIATEK FMS 1650L The Next Generation in Critical Airflow Controls ...

Страница 2: ...preserve the accuracy of the calibration the remote sensor module MUST be installed no more than 10 feet from the FMS 1650L controller module using the supplied interface cable Failure to do so could result in inaccurate differential pressure readings The display module may be located up to 4000 feet from the FMS 1650L controller module Distance not to exceed 4000 feet Distance not to exceed 10 fe...

Страница 3: ...ld void your warranty Wiring diagrams can also be found at www triatek com Under no circumstances should a single transformer be split between actuator and controller Doing so will damage the actuator the transformer the controller or all units A single 120 24V 30Va transformer is required for the controller and a separate 120 24V 20Va transformer is required for the actuator CORRECT TRIATEK reser...

Страница 4: ...t 14 Analog Input to 2 Remote Pressure Sensors 0 10V Out 15 Analog Input to 2 Remote Pressure Sensors 4 20mA Out 16 Adding Input to Temperature Sensor 17 Digital Input to Door Switch 18 Digital Input to Flow Switch 19 Digital Input to Occupancy Sensor 20 Relay Output to Alarm 21 Relay Output to Warning 22 Relay Output 1 23 Relay Output 2 24 Power 25 Isolated Power Supply 26 COMMUNICATIONS Wiring 2...

Страница 5: ...t to change product specifications without notice INSTALLATION MANUAL Table of Contents MODULE SETTINGS Configuring Display Module Settings 34 35 CLEANING THE DISPLAY Cleaning the FMS 1650L 36 TRIATEK reserves the right to change product specifications without notice ...

Страница 6: ...24 Vac 60 50 Hz step down isolation transformer provided Communications LonWorks FTT 10A peer to peer network Two Wire Twisted Pair FTT 10A signaling Recommended Cable Type Level IV 22AWG Unshielded Plenum UL Type CMP Windy City 105540 Connet Air W22IP 2001 Metro Wire MWC 1000 Level IV 22AWG Shielded Plenum UL Type CMP Windy City 106500 Connet Air W22IP 2002 Metro Wire MWC 1002 Touch Screen User I...

Страница 7: ...ng 4 1 W x 6 H x 1 85 D Environmental Operating Temperature 32 to 125 F Operating Operating Humidity 10 95 RH Non condensing Venturi Valve Order Separately Diameter 6 8 10 12 14 16 O D CFM Range 30 2400 Materials Aluminum Stainless Steel Heresite Coating Sound Insulation Optional Actuation Electronic or Pneumatic Part Number Guide GENERAL TRIATEK reserves the right to change product specifications...

Страница 8: ...red When an alarm condition occurs it can be annunciated in three user definable ways 1 on the display 2 with an audible alarm and 3 transmitted via contacts to a remote monitoring station and over network The alarm can be set to automatically reset when the unit has sensed that the room pressure has returned to proper limits or it may be set to remain on until manually reset In either case the at...

Страница 9: ...e right to change product specifications without notice 4 3 5 3 4 3 4 PWR LED GND V MOUNTING WIRING TRIATEK reserves the right to change product specifications without notice Right Side View Left Angle Side View Control Unit Adapter Inside Control Unit Recommended Cable Type Belden 1325A ...

Страница 10: ...ecifications without notice 5 MOUNTING WIRING TRIATEK reserves the right to change product specifications without notice FMS Display Mounting Hole Pattern The FMS 1650L display backplate may be mounted directly to a standard single gang wall box using the two slots along the centerline Use the backplate as a template to mark the mounting holes and the cable access hole at the center of the backpla...

Страница 11: ...tinuous improvement TRIATEK reserves the right to change product specifications without notice 6 MOUNTING WIRING TRIATEK reserves the right to change product specifications without notice TRIATEK reserves the right to change product specifications without notice ...

Страница 12: ...nock out the back and one bottom knock out then with the signal wire pulled through the bottom hole into the box Mount the enclosure box in the opening provided and secure with screw and anchors Seal around the edges of the box with UL Classified Fire Sealant 5 Push a length of flow tube through the back hole on through the 7 16 hole in the opposite wall 6 Attach the flow tube to the sensor port t...

Страница 13: ... Plate Stainless Steel Flow Tube Mounting Plate Gasket Thin Silicone Caulking apply around tube and between stainless steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1650L Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To FMS 1650L Controller Wall Section cutaw...

Страница 14: ...OOM CORRIDOR Stainless Steel Mounting Plate Gasket Louvered Cover Plate Stainless Steel Flow Tube Mounting Plate Gasket Thin Silicone Caulking apply around tube and between stainless steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1650L Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as pos...

Страница 15: ... 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor Remote Sensor Transmitter GND Io Vin The electrical connections to the FMS 1650L are made via a convenient removable terminal block as shown below All wiring should conform to th...

Страница 16: ...ss the sta tus and the configuration of the unit Also used by configuration software to configure unit Analog Output Unit has 4 Analog Outputs which can be configured for 0 5 VDC or 0 10VDC Analog Input Unit has 4 Analog Inputs which can be configured for 4 20 mA 0 5VDC or 0 10VDC Power The FMS 1650L Series can be powered by either 24 VAC or 24 VDC A 120 VAC to 24 VAC Step Down Isolation Transform...

Страница 17: ...Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor CONNECTIONS FOR POWERED OUTPUT Air Control Modulator Optional External Transmitter Power Supply 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 AI 4 JP7 1 2 3 4 Analog Input 4 20mA JP6 AI 1 AI 2 AI 3 AI 4 Analog Input JP6 0 5v JP5 AO 1 AO 2 AO 3 AO 4 Analog...

Страница 18: ...H WP 1 SHLD NETWRK I NT 2 NT 1 PWR Vse 1 SW1 LED1 JP2 LED LED2 1 4 Tx LED3 LED4 Rx SW1 LED1 D D D JP3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 JP2 FL FL LED2 1 LED3 E E E LED4 E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 IN Pressure Sensor 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 AI 4 JP7 1 2 3 4 Analog Inpu...

Страница 19: ...ld Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor Remote Pressure Sensor Io Vin GND 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 AI 4 JP7 1 2 3 4 Analog Input 4 20mA JP6 AI 1 AI 2 AI 3 AI 4 Analog Input JP6 0 5v JP5 AO 1 AO 2 AO 3 AO 4 Analog O...

Страница 20: ... 1 1 1 1 1 1 1 1 1 1 1 1 1 1 INT NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor T Pressure Sensor 1 IN IN Pressure Sensor 2 0 10V OUT 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 AI 4 JP7 1 2 3 4 Analog In...

Страница 21: ...ring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and From Unit Between Room and Corridor Remote Pressure Sensor 1 Remote Pressure Sensor 2 GND Io Vin GND Io Vin 4 20mA OUT 0 5v JP7 Jumper Setting AI 1 AI 2 AI 3 AI 4 1 2 3 4 JUMPER ON Analog Input 0 10v JP7 AI 1 AI 2 AI 3 AI 4 JP7 1 2 3 4 Analog Input 4 20mA JP6 AI 1 AI 2 AI 3 AI 4 Analog Input JP6 0 5v JP5 AO 1 AO 2 AO 3 AO 4...

Страница 22: ...PIN 3 and jumper OFF JP7 PIN 3 AO 1 can be set to 0 10v jumper ON JP5 PIN 1 AO 2 0 5v can be set to 0 5v jumper OFF JP5 PIN 2 JUMPER OFF 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 AO 1 AO 2 AO 3 AO 4 AI AI AI AI GND GND 10v V ANALOG I 1 2 3 EXT SNSR 5v GND GND GND GND AUX PWR OUTPU ANALOG OUT RNG 4 1 2 3 Ain 4 Aout JP4 2 JP5 4 RNG 1 mA 3 JP7 Ain JP6 1 1 1 NT 1 NT 2 NETWRK OUT DI DI DI GND GND GND PH1 PH2 VS ...

Страница 23: ... 2 3 EXT SNS SELEC INT SNS SRVC EXT SRVC SNSR FLASH WP 5v GND GND GND GND 1 SHLD NETWRK I NT 2 NT 1 AUX PWR OUTPU PWR ANALOG OUT 1 SW1 RNG 4 1 2 3 LED1 JP2 LED Ain 4 Aout LED2 1 JP4 2 JP5 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain JP6 Rx SW1 LED1 D D D JP3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 JP2 FL FL LED2 1 1 LED3 E E E LED4 E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1...

Страница 24: ...ND GND GND GND SHLD NETWRK I NT 2 NT 1 AUX PWR OUTPU PWR ANALOG OUT SW1 RNG 4 1 2 3 LED1 JP2 LED Ain 4 Aout LED2 1 JP4 2 JP5 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain JP6 Rx 1 1 SW1 LED1 D D D JP3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 JP2 FL FL LED2 1 1 LED3 E E E LED4 E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NC No Connection to Field Wir Field Wiring w space for N...

Страница 25: ...P 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT Vsel 1 SW1 RNG 4 1 2 3 1 LED1 1 JP2 LED Ain 4 Aout LED2 1 JP4 1 2 JP5 1 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain 1 1 JP6 Rx SW1 LED1 1 JP3 1 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow To and Fro...

Страница 26: ... DI_3 1 2 3 EXT SNSR SELECT INT SNSR G 5v V DI SRVC EXT SRVC SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT Vsel 1 SW1 RNG 4 1 2 3 1 LED1 1 JP2 LED Ain 4 Aout LED2 1 JP4 1 2 JP5 1 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain 1 1 JP6 Rx SW1 LED1 1 JP3 1 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring ...

Страница 27: ...SELECT INT SNSR G 5v V DI SRVC EXT SRVC SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT Vsel 1 SW1 RNG 4 1 2 3 1 LED1 1 JP2 LED Ain 4 Aout LED2 1 JP4 1 2 JP5 1 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain 1 1 JP6 Rx SW1 LED1 1 JP3 1 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring...

Страница 28: ...UTS SHLD DI_3 1 2 3 EXT SNSR SELECT INT SNSR G 5v V DI SRVC EXT SRVC SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT Vsel 1 SW1 RNG 4 1 2 3 1 LED1 1 JP2 LED Ain 4 Aout LED2 1 JP4 1 2 JP5 1 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain 1 1 JP6 Rx SW1 LED1 1 JP3 1 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal...

Страница 29: ...I SRVC EXT SRVC SNSR FLASH_WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT Vsel 1 SW1 RNG 4 1 2 3 1 LED1 1 JP2 LED Ain 4 Aout LED2 1 JP4 1 2 JP5 1 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain 1 1 JP6 Rx SW1 LED1 1 JP3 1 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Des...

Страница 30: ... continuous improvement TRIATEK reserves the right to change product specifications without notice Mounting Wiring Power FMS 1650L 25 TRIATEK reserves the right to change product specifications without notice ...

Страница 31: ...solation Transformer provided with FMS 1650L Blue 24 VAC 30Va connected to Power on the FMS Only Class 2 wiring in this compartment 24 VAC 60 Hz Note This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker This circuit breaker should be mounted in an approved electrical enclosure located...

Страница 32: ..._WP 5v GND GND GND GND 1 SHLD NETWRK IN NT_2 NT_1 AUX PWR OUTPUT PWR ANALOG OUT Vsel 1 SW1 RNG 4 1 2 3 1 LED1 1 JP2 LED Ain 4 Aout LED2 1 JP4 1 2 JP5 1 4 RNG 1 Tx mA 3 LED3 LED4 JP7 Ain 1 1 JP6 Rx SW1 LED1 1 JP3 1 1JP2 LED2 1 1 1 1 1 LED3 LED4 1 1 FMS FMS NC No Connection to Field Wiring Field Wiring w space for Number Internal Wiring Screw Terminal Wiring Guide Legend Symbol Description Air Flow ...

Страница 33: ...ions cable Conductor discontinui ties produced by such connections may gener ate RFI or other electromagnetic interference on the communications circuit 3 Do not use wire nut devices for connecting communications cable 4 Do not route any part of the communications cable through conduit junction boxes or other devices containing AC electrical wiring 5 Do not strap communications cable to any condui...

Страница 34: ... Programming Notes FMS 1650L Due to continuous improvement TRIATEK reserves the right to change product specifications without notice 29 Due to continuous improvement TRIATEK reserves the right to change product specifications without notice TRIATEK reserves the right to change product specifications without notice ...

Страница 35: ...as been installed Current differential pressure reading in selected engineering units default is WC Current time and date Figure 2 The main screen of the FMS 1650L displays the differential pressure room status temperature and humidity if so equipped along with the time and date along the bottom of the screen As mentioned earlier the background color of the main display screen will be blue while s...

Страница 36: ... specified in sequence for either occupied or unoccupied modes These limits should be specified to set the differential pressure range which should be considered normal as well as the range which indicates a warning condition and the range which is considered critical and indicates an alarm condition Set Target Setpoints If this FMS 1650L is being used for monitoring only and does not control an e...

Страница 37: ...ry default back door password that will provide unrestricted access to the user menu system Please consult the factory for more information regarding this password Figure 5 This menu provides options for managing the system passwords Changing Display Settings The FMS 1650L display screen can be customized very easily using options available under the Display Setup menu shown in Figure 6 The inform...

Страница 38: ... commissioning technician to view the real time conditions of all of the hardware resources as well as several system variables These include the analog inputs analog outputs and digital inputs Selecting the Real Time View option from the Diagnostics menu allows the user to view the real time conditions of any of the listed resources For example selecting the Analog Inputs option from the Real Tim...

Страница 39: ...Single ON Dual 2 Test Mode OFF Disabled ON Enabled 3 Product Type OFF FMS 1650L ON FMS 1650L 4 Operational Mode OFF Demo Mode ON Run Mode Pushbutton Switch SW1 Reset Button Pushbutton Switch SW2 Options Configuration Module Settings Configuring Display Module Settings Due to continuous improvement TRIATEK reserves the right to change product specifications without notice 34 FMS 1650L TRIATEK reser...

Страница 40: ... to continuous improvement TRIATEK reserves the right to change product specifications without notice 35 Due to continuous improvement TRIATEK reserves the right to change product specifications without notice FMS 1650L TRIATEK reserves the right to change product specifications without notice Module Settings ...

Страница 41: ...pyl alcohol or kerosene Touching the current name text brings up an alphanumeric keyboard to quickly change the name of the monitored room Touching anywhere else on the screen enters the Main Setup Menu if no password is stored Otherwise a password must be entered before the Main Setup Menu can be accessed Touching DATE brings up the Date Entry popup to quickly change the current displayed date To...

Страница 42: ... PI PI PIED ED ED E ED ED ED D ED ED E E ED ED ED ED ED ED ED ED ED E E E ED D ED S S S S S S S S Sa as as as as as s as as as as s as as a as as s as s a as as a a h h h h h h h h h h h h h h h h h h h h h h h h h h h h Po P Po Po P Po Po Po Po Po Po Po P Po P Po Po P Po Po Po P Po osi i si si s si si si si si si si i si i si si i si s si i s s s ti ti ti ti t t ti t ti ti ti t ti t ti ti t t t t...

Отзывы: