The
TRIATEK FMS-1650L
Isolation Monitor
is an ultra-sensitive instrument used to control
and/or monitor air pressure in hospital rooms,
labs, and clean rooms. This unit is a precision
measuring system capable of measuring and
displaying air pressures down to 0.0001” WC.
It can be used to control pressures down to
0.001” WC. Features of the unit include:
•
Digital display of pressure with a
programmable descriptor
•
Full color touch screen
•
audible and visual alarm annunciation
•
Four relay outputs for transmitting alarm
conditions to a remote location such as a
central monitoring station
•
Auxiliary analog inputs for use with
optional sensors
•
Analog outputs used in control
applications
•
Password protection of programmed
setup
•
Optional keylock switch for isolation
select protection
•
Optional LON communications.
The FMS-1650L is equipped with a full color
touch screen display and can be wiped clean
using a soft cloth without the use of harsh
chemicals. No decontamination requirements
are required for the proper operation of this
product.
There are three background screen colors
to indicate “
Normal
” when pressure is within
defined limits, “
Caution
” when pressure
is nearing an out-of-limits condition, and
“
Alarm
” when pressure is outside defined
acceptable limits. The pressure ranges for
these conditions are easily set by the user for
the specific installation when necessary. The
background screen colors provide overview of
room pressure conditions at a glance.
Alarm Conditions
can be defined by the
user, in terms of desired pressure settings for
the room being monitored. When an alarm
condition occurs, it can be annunciated in
three user-definable ways: 1) on the display,
2) with an audible alarm, and 3) transmitted
via contacts to a remote monitoring station
and over network. The alarm can be set to
automatically reset when the unit has sensed
that the room pressure has returned to proper
limits, or it may be set to remain on until
manually reset. In either case, the attendant
can mute the audible alarm by touching the
OK
button on the alarm popup.
The FMS-1650L provides four
Relay
outputs that can be used for remote alarm
annunciation or pilot control functions. The
operation of each output can be configured by
the user to define the exact room air pressure
values above and below which the output will
operate. Delay times before activation can be
specified to minimize nuisance activation.
In many installations, it is important to have
other room variables such as temperature or
relative humidity to be displayed along with
room pressure.
The FMS-1650L provides for this by means
of
Additional Analog Inputs
which can be
configured for 4-20 ma current or for voltage
input signals. The input can be scaled as
needed to display correct values, and a
suitable descriptor can be applied.
The FMS-1650L provides
Analog Outputs
which can be set up for voltage. It can be
programmed to be proportional output (AO-2,
AO-3 or AO-4) for providing a linear signal
to an automation system, or programmed
for PID floating point output (AO-1) for direct
control of damper actuators, speed drives,
etc.
The user can set up multiple access level
passwords to protect against unauthorized or
casual access to the FMS-1650L programmed
variables.
Room pressure selection of
Positive
,
Negative
, or
No Isolation
is set using the
user menu or an optional
Keylock Switch
.
A
LON Communications Interface
enables
the unit to communicate room status
information to the building automation system.
GENERAL
Overview