BACnet OBJECTS
FMS-1650
-
68
-
The following table itemizes the list of points available for integration in a building management system (BMS). This table contains the objects for
open BACnet integration.
TRIATEK reserves the right to change product specifications without notice.
Object Instance
Functional Description
Read or Write
Analog Inputs
AI - 1
Analog Input 1 (default: Isolation Room Differential Pressure)
Read-Only
AI - 2
Analog Input 2 (default: Anteroom Differential Pressure)
Read-Only
AI - 3
Analog Input 3 (default: Isolation Room Humidity)
Read-Only
AI - 4
Analog Input 4 (default: Supply/Exhaust Duct Air Flow)
Read-Only
AI - 5
Thermistor Input 1 (default: Isolation Room Temperature)
Read-Only
AI - 6
Thermistor Input 2 (default: Duct Temperature)
Read-Only
Analog Outputs
AO - 1
Analog Output 1 (default: Isolation Room Damper Control)
Read-Only
AO - 2
Analog Output 2 (default: Anteroom Damper Control)
Read-Only
AO - 3
Analog Output 3 (spare control output)
Read-Only
AO - 4
Analog Output 4 (spare control output)
Read-Only
Binary Inputs
BI - 1
Digital Input 1 (default: Isolation Room Door Switch)
Read-Only
BI - 2
Digital Input 2 (default: Anteroom Door Switch)
Read-Only
BI - 3
Digital Input 3 (spare digital input)
Read-Only
BI - 4
Digital Input 4 (spare digital input)
Read-Only
Binary Outputs
BO - 1
Relay Output 1 (default: Primary Alarm Relay Output)
Read-Only
BO - 2
Relay Output 2 (default: Secondary Alarm Relay Output)
Read-Only
BO - 3
Relay Output 3 (spare relay output)
Read-Only
BO - 4
Relay Output 4 (spare relay output)
Read-Only
Analog Values
AV - 1
AI-1 Setpoint (Isolation Room Differential Pressure)
Read/Write
AV - 2
AI-2 Setpoint (Anteroom Differential Pressure)
Read/Write
AV - 3
AI-3 Setpoint (Isolation Room Humidity)
Read/Write
AV - 4
AI-4 Setpoint (Supply/Exhaust Duct Air Flow)
Read/Write
AV - 5
TI-1 Setpoint (Isolation Room Temperature)
Read/Write
AV - 6
TI-2 Setpoint
Read/Write
AV - 7
Air Change Rate based on Flow Input at AI-1
Read/Write
AV - 8
Air Change Rate based on Flow Input at AI-2
Read/Write
AV - 9
Air Change Rate based on Flow Input at AI-3
Read/Write
AV - 10
Air Change Rate based on Flow Input at AI-4
Read/Write
AV - 11
Alarm Relay 1 High Setpoint
Read/Write
AV - 12
Alarm Relay 1 Low Setpoint
Read/Write
AV - 13
Alarm Relay 2 High Setpoint
Read/Write
AV - 14
Alarm Relay 2 Low Setpoint
Read/Write
AV - 15
Alarm Relay 3 High Setpoint
Read/Write
AV - 16
Alarm Relay 3 Low Setpoint
Read/Write
AV - 17
Alarm Relay 4 High Setpoint
Read/Write
AV - 18
Alarm Relay 4 Low Setpoint
Read/Write
AV - 19
AI-1 Low Alarm Setpoint (low differential pressure alarm)
Read/Write
BACnet
®
Objects