background image

24

CHAPTER

 5

CHAPTER 5 - WATER HEATER MAINTENANCE

Water from opened drain valves, unions and 

other connections may be extremely hot. To 

avoid substantial property damage, serious 

injury, or death:

- Tighten all drain hose connections.

- Direct hot water away from all persons.

5.3.1  Draining Inner (Domestic Water) Tank.

There are 3 methods typically used in the drain-

ing of the inner tank. The first method outlined 

as Option 1 is to siphon the water out. This 

method is typically the easiest to perform, but 

may be lengthly in time to complete.

The second method, shown as Option 2, uses com-

pressed air. This method is more complicated how-

ever it is generally quicker in draining the tank. 

The final method, Option 3, use a pump to drain the 

tank. As with Option 2, Option 3 is generally more 

complicated, but is quicker in draining the tank.

Prior to draining the inner tank, ensure the fol-

lowing is completed:

•  The snap-set wiring connection at the wa-

ter heater is disconnected.

•  The DHW system supply isolation valve is 

closed.

•  The outer (boiler water) tank pressure is less 

than 15 psig

Reference domestic piping diagram, see  Fig. 2 

on page 7 thru  Fig. 4 on page 8.

Draining Inner Tank - Option 1

1.  Connect a hose to the domestic water drain valve 

at the cold water inlet. The hose should extend to a 

drain at floor level to allow siphoning of the domes-

tic inner tank.

2.  Open a hot water faucet at the highest point above 

the water heater.

3.  Open the domestic water drain valve to start the 

siphoning of the domestic inner tank.

 

WARNING

NOTICE

4.  When draining is complete, close the hot water fau-

cet and the domestic drain valve.

Draining Inner Tank - Option 2

1.  Connect a hose to the domestic water drain valve 

at the cold water inlet. Direct the hose to a proper 

drain/suitable place for drainage.

2.  Close the isolation valve on the DHW system hot 

outlet of the water heater.

3.  On the hot water outlet piping between the water 

heater and the isolation valve install a shrader (air 

tank) valve or some other fitting or means that al-

lows connection of an air hose from a compressor.

4.  Open the domestic water drain valve on the cold 

water inlet.

5.  Apply compressed air at a maximum regulated 

pressure of 40 psig. 

6.  When draining is complete, remove the air hose 

and fittings needed to connect the air hose.

7.  Close the domestic water drain valve on the cold 

water inlet and open the isolation valve on the hot 

water outlet.

Draining Inner Tank - Option 3

1.  Connect the suction side of the pump to the domestic 

water drain valve using a hose and/or piping fittings.

2.  Connect a hose to the discharge side of the pump. 

Direct the hose to a proper drain or a suitable place 

for drainage. 

3.  Open a hot water faucet at the highest point above 

the water heater. 

4.  Open the domestic water drain valve and start the 

pump to begin draining the inner tank. 

5.  When draining is complete stop the pump, close 

the hot water faucet and close the domestic drain 

valve. Remove the pump and all hoses and fittings.

5.3.2  Draining Outer (Boiler Water) Tank

1.  Disconnect snap set wiring connection at water 

heater.

2.  Close boiler water isolation valves between boiler 

and water heater.

3.  Connect hose to boiler water drain valve at water 

heater. Open and drain water to a safe place.

4.  To speed draining procedure, open manual air vent 

on top of tank.

5.  When draining is complete, close drain valve and 

close manual air vent.

BEST PRACTICE

Содержание SMART Series

Страница 1: ...pment must be filed immediately against the transportation company by the consignee Customer must register unit within sixty 60 days of installation in order to gain warranty coverage See Warranty Card for details Leave all documentation received with appliance with the owner for future reference Installation and service should only be performed by a qualified installer or service technician Insta...

Страница 2: ...INTENTIONALLY LEFT BLANK ...

Страница 3: ... Valve 4 2 2 1 Standard Installation 4 2 2 2 Commonwealth of Massachusetts Installation 4 2 3 Manual Air Vent 4 2 4 Thermal Expansion 4 2 5 Water Hammer 4 2 6 Vacuum Breaker 4 2 7 General Piping 4 2 8 Domestic Piping 4 2 9 Thermostatic Mixing Valve 5 2 10 Recirculation Piping 5 2 11 Multiple Water Heater Systems 5 2 12 Boiler Piping 6 CHAPTER 3 INSTALLATION WIRING 15 3 1 Wiring Requirements 15 3 2...

Страница 4: ...ce technician should include the following 23 5 1 2 Homeowner monthly maintenance to include 23 5 2 Filling Water Heater 23 5 3 Draining Water Heater 23 5 3 1 Draining Inner Domestic Water Tank 24 5 3 2 Draining Outer Boiler Water Tank 24 CHAPTER 6 REPLACEMENT PARTS 25 CHAPTER 7 WATER HEATER SPECIFICATIONS AND PERFORMANCES 26 ...

Страница 5: ... Series Water Heater System Boiler Piping Reverse Return Balanced Flow 13 Fig 14 Multiple SMART Series Water Heater System Boiler Piping Manifold 13 Fig 15 Snap Set Wiring 15 Fig 16 Typical 4 wire Zone Valve Zoning with Domestic Priority 16 Fig 17 Typical 3 wire Zone Valve Zoning with Domestic Priority 16 Fig 18 Typical 4 wire Zone Valve Zoning without Domestic Priority 17 Fig 19 Typical 3 wire Zo...

Страница 6: ...INTENTIONALLY LEFT BLANK ...

Страница 7: ...nance which are import ant to the equipment but not related to person al injury hazards Indicates recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equip ment DANGER WARNING CAUTION NOTICE BEST PRACTICE IMPORTANT SAFETY INFORMATION FOR THE HOMEOWNER AND THE INSTALLER DANGER Water temperatures over 125ºF can cause severe burnsi...

Страница 8: ... Protection must be taken against excessive temperature and pressure Installation of a Temperature Pressure T P relief valve is required Failure to comply with these instructions can result in minor property damage or injury CAUTION CAUTION In case of any anomaly please call your qualified service technician Make sure to reference the unit s model number and serial number from the rating label whe...

Страница 9: ... heat transfer medium is main tained less than the normal minimum operating pressure of the potable water system Exception Steam complying with section 1 above 3 The equipment is permanently labeled to indicate that only additives recognized as safe by the FDA shall be used in the heat transfer medium NOTICE Other heat exchanger designs may be permitted where approved by the Administrative Authori...

Страница 10: ... adequate drainage should be placed under the water heater The SMART Series Water Heaters are designed for vertical installation only BEST PRACTICE 1 5 Recommended Clearances Water heater should be installed to allow adequate clearance for servicing Zero clearance is permissible to any side of the SMART Series water heater that has no connection but infor mation labels may be hidden Also take into...

Страница 11: ...l T P relief valve in the Auxiliary connection located behind the air vent on the top of the water heater Refer to Fig 2 on page 7 or Install theT P relief valve in the run straight through leg of a tee located at the domestic hot water outlet when using the Auxiliary connection for a recircula tion return Refer to Fig 3 on page 7 2 1 2 CommonwealthofMassachusettsInstallation Follow this procedure...

Страница 12: ...CAUTION 2 5 Water Hammer Dishwashers clothes washers and fast closing positive shut off valves incorporated in the system all contrib ute to creating water shock Install a water hammer ar rester to prevent damage to pipes and appliances See device manufacturer s instructions for application and installation Water hammering within the domestic piping system can cause premature failure of the inner ...

Страница 13: ... Tube Draining Dip Tube Recommend ed Minimum Boiler Piping Domestic Water Inlet Outlet NPT Boiler Water Supply Return NPSC Auxiliary Connection NPSC Length Inches Diam eter Inches Length Inches Diameter Inches Diameter Inches SMART 30 3 4 1 3 4 34 3 4 34 3 4 1 SMART 40 3 4 1 3 4 43 3 4 43 3 4 1 SMART 50 3 4 1 1 4 3 4 25 3 4 52 3 4 1 SMART 60 3 4 1 1 4 3 4 34 3 4 62 3 4 1 1 4 SMART 80 1 1 2 1 1 2 1...

Страница 14: ... toxic having toxicity rating or class of 1 as listed in Clinical Toxicology of Commercial Prod ucts Antifreeze can only be used if the boiler water pressure relief valve is set to 30 psig or below NOTICE CAUTION If antifreeze is used in the boiler system local codes may require a backflow preventer on cold water supply line Use antifreeze specifically intended for hydronic heating systems Inhibit...

Страница 15: ...n valve 8 Thermal expansion tank potable 9 Recirculation dip tube 10 Thermostatic mixing valve Optional devices may be required by local codes Cold Water Inlet 6 1 12 min Heat Trap Loop Optional 12 min Heat Trap Loop Optional 1 5 5 1 8 7 4 10 M H C 7 Cold Water Inlet 6 1 Recirculating Loop 2 3 4 1 5 5 1 8 12 min Heat Trap Loop Optional 12 min Heat Trap Loop Optional 9 Fig 3 Standard Installation D...

Страница 16: ...Backflow preventer or pressure reducing valve 7 Drain valve 8 Thermal expansion tank potable Optional devices may be required by local codes 7 Cold Water Inlet 6 1 Recirculating Loop 2 3 4 1 5 5 1 8 12 min Heat Trap Loop Optional 12 min Heat Trap Loop Optional Fig 4 Optional Installation Domestic Piping with Recirculation SMART Series ...

Страница 17: ...pansion tank potable 9 Vacuum breaker 10 Mixing valve 11 Dip tube Draining per Chart 1 Optional devices may be required by local codes Fig 5 Drain Tube Assembly Commonwealth of Massachussets Fig 6 Commonwealth of Massachussets Domestic Piping SMART Series Cold Water Inlet 6 1 12 min Heat Trap Loop Optional 12 min Heat Trap Loop Optional 4 1 5 5 8 9 11 10 M H C 7 ...

Страница 18: ...Priority Valve normally open 2 Port Priority Valve normally close 1 6 5 Cold water inlet Fig 8 SMART System Piping with 2 Port Zone Valves Domestic Priority 1 Shut off valves 2 Circulator 3 Expansion tank 4 Drain valve 5 Feed valve 6 Air separator Fig 7 SMART System Piping with 3 Port Zone Valve Domestic Priority ...

Страница 19: ...ION PIPING 1 Shut off valves 2 Circulator 3 Flow check valve 4 Expansion tank 5 Drain valve 6 Feed valve 7 Air separator Fig 9 SMART System Piping with Zone Valves Non Domestic Priority Fig 10 SMART System Piping with Zone Circulators ...

Страница 20: ...t of the water heater system or at each hot water fixture Each tank should be piped with a drain as shown in Fig 2 on page 7 Recommended for applications in which there is a large water consump tion in short period of time A maximum of 3 water heaters may be piped in series Utilize the lead hot water outlet SMART tank thermostat to control system temperature Install automatic mixing valve at ei th...

Страница 21: ...ves 2 Circulator 3 Flow check valve 4 Expansion tank 5 Drain valve 6 Feed valve 7 Air separator Fig 13 Multiple SMART Series Water Heater System Boiler Piping Reverse Return Balanced Flow Fig 14 Multiple SMART Series Water Heater System Boiler Piping Manifold ...

Страница 22: ...INTENTIONALLY LEFT BLANK ...

Страница 23: ...to control component instructions packed with boiler for application information 4 An optional service switch may be installed in water heater electrical circuit This switch would only shut off the water heater not the home heating system Do not shut off water heater if there is a chance of freezing 5 All electrical contacts shown do not have power applied off the shelf condition See pages 15 to 1...

Страница 24: ... Thermostat Snap Set Water Heater Zone Boiler Thermostat Terminals High Voltage Low Voltage Boiler Low Voltage Priority Relay H N High Voltage 120 V A C 24 V A C Room Thermostat Zone 1 Additional zones Additional zones may be added as shown above Transformer Power Zone Valve Zone Valve 1 2 C Water Heater Thermostat Snap Set Water Heater Zone Isolation Relay Boiler Thermostat Terminals Use isolatio...

Страница 25: ...1 2 C Water Heater Thermostat Snap Set Water Heater Zone Boiler Thermostat Terminals High Voltage Low Voltage Boiler Low Voltage H N High Voltage 120 V A C 24 V A C Room Thermostat Room Thermostat Zone 1 Zone 2 Additional zones Additional zones may be added as shown above Transformer Power Zone Valve Zone Valve Zone Valve 1 2 C Water Heater Thermostat Snap Set Water Heater Zone Isolation Relay Boi...

Страница 26: ... 2 T T 1 4 3 6 Circulator Zone 2 Thermostat zone 2 5 2 T T 1 4 3 6 Water Heater Circulator Water Heater Thermostat Snap Set 5 1 2 C Boiler Thermostat Terminals Priority Relay 2 T T 1 4 3 5 6 Circulator Zone 1 Thermostat zone 1 Honeywell R845A Relay 120 H VAC N 2 T T 1 4 3 6 Circulator Zone 2 Thermostat zone 2 5 2 T T 1 4 3 6 Water Heater Circulator Water Heater Thermostat Snap Set 5 1 2 C High Vol...

Страница 27: ...y 120 H VAC N 2 T T 1 4 3 6 Circulator Zone 2 Circulator Zone 3 Thermostat zone 2 Thermostat zone 3 5 2 T T 1 4 3 6 5 High Voltage Low Voltage To Boiler 24 VAC Thermostat Leads 2 ON PRIORITY ZONING CIRCULATOR CIRC ON PR1 LIVENEUT T T 2 1 C WaterHeater ThermostatSnapSet PriorityZone Circulator Note Maximum of 4 total circulator zone when wiring 1 zone for priority ...

Страница 28: ...INTENTIONALLY LEFT BLANK ...

Страница 29: ...al Products Do not use automotive ethylene glycol or pe troleum based antifreeze Do not use any un diluted antifreeze This can cause substantial property damage serious injury or death CAUTION CAUTION WARNING HOT WATER CAN SCALD Water temperature over 125ºF can cause se vere burns instantly or death from scalds Feel water before bathing or showering Consumer Product Safety Commission and some stat...

Страница 30: ...er Thermostat Water heater thermostat is factory set to its lowest temperature This may or may not be suitable for your needs Turn thermostat knob clockwise to in crease water temperature Turn thermostat knob counter clockwise to decrease water temperature Bacteria can develop in the domestic water system if certain minimum water tempera tures are not maintained Failure to maintain at least 140 F ...

Страница 31: ...and valves See component manufacturer s instructions Review homeowner s maintenance responsibilities and their frequencies including any not listed in the following section WARNING DANGER 5 1 2 Homeowner monthly maintenance to in clude Check for air Manual air vent open and close briefly to re lease any air Check for leaks Visually check valves pipes and fittings for leaks Call qualified service t...

Страница 32: ...valve Draining Inner Tank Option 2 1 Connect a hose to the domestic water drain valve at the cold water inlet Direct the hose to a proper drain suitable place for drainage 2 Close the isolation valve on the DHW system hot outlet of the water heater 3 On the hot water outlet piping between the water heater and the isolation valve install a shrader air tank valve or some other fitting or means that ...

Страница 33: ...rywell P3DW01 SMART 40 P3DW02 SMART 50 P3DW03 SMART 60 80 P3DW04 SMART 100 120 6 P3WKITDT01 SMART 30 Dip tube P3WKITDT02 SMART 40 P3WKITDT03 SMART 50 P3WKITDT04 SMART 60 P3WKITDT08 SMART 80 100 P3WKITDT09 SMART 120 7 not shown P3WKITDT01 SMART 30 60 Dip tube recirculation P3WKITDT02 SMART 40 50 P3WKITDT08 cut to length SMART 80 100 120 8 P3KITWRS01 All Snap set wire harness 9 P3KNB02 All Knob 10 P...

Страница 34: ...26 CHAPTER 7 B A C D Chapter 7 WATER HEATER SPECIFICATIONS AND PERFORMANCES Auxiliary Connection Hot Water Outlet Fig 26 SMART Dimensions Side View Boiler Return Boiler Supply ...

Страница 35: ... 1 2 1 1 2 1 1 2 Boiler Ø 1 1 1 1 4 1 1 4 1 1 2 1 1 2 2 Auxiliary Ø 3 4 3 4 3 4 3 4 1 1 2 1 1 2 1 1 2 Dimensions Inches A 38 46 57 66 61 78 72 B 9 9 9 9 10 10 10 C 30 38 49 58 50 1 2 68 64 D 22 22 22 22 26 26 32 E 14 14 14 14 10 1 2 10 1 2 10 1 2 F 6 6 6 6 10 1 2 10 1 2 5 Dry well length Inches 25 29 37 47 47 51 51 Empty weight Lbs 115 135 165 190 271 362 479 Thermostat and Cover Plate Air Vent Fi...

Страница 36: ...emperature 200ºF Boiler water supply temperature Model Boiler Heating Capacity MBH Peak Flow Gal 10 min 1st Hour Flow Gal Hour Continuous Flow Gal Hour Circulator Min GPM SMART 30 115 60 235 210 8 SMART 40 130 70 270 240 9 SMART 50 180 95 370 330 12 SMART 60 320 145 635 590 21 SMART 80 340 165 690 630 24 SMART 100 380 185 775 700 26 SMART 120 445 235 915 820 30 Conditions 50ºF Domestic cold water ...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...ing available from Triangle Tube Available in capacities from 25 000 BTU hr to 5 000 000 BTU hr 95 AFUE High Efficiency Condensing Boiler Combi Power Range 110 MBH 155 MBH 199 MBH Turn Down Ratio up to 8 1 Natural Gas or Propane Universal Top Adapter PVC PP SST Outdoor Reset TTP Brazed Plate Heat Exchangers Instinct Condensing Boilers Maxi Flo Pool and Spa Heat Exchangers Constructed of high quali...

Отзывы: